Activate - Deactivate Sp; Selection Type; Measuring Range; Sp Signal - Intec PolyGard LGC/LG2-04 User Manual

Multi-point controller
Table of Contents

Advertisement

PolyGard
Multi-Point Controller
®
LGC-LG2 – UserManual
LGC-LG2 – UserManual
User Manual - LGC/LG2-04
LGC-LG2 – UserManual
3.6.1
Activate – Deactivate SP
Symbol
Description
SP 01
Sensor point
Active
SP Status
3.6.2

Selection Type

Assign Type to attached to transmitters.
Symbol
Description
SP 01
Sensor point
NH3
Type
1
Range Recommendations for Polygard sensors
2
During oxygen measurement falling signal!
3.6.3

Measuring range

The measuring range can be defined from 10 to 10000 . The measuring ranges in the above table are typical and
only recommendations actual ranges see the sensor manufacturing specifications.
The measuring range must agree with the signal (4 to 20 mA) attached transmitters.
(4 mA = Display=0, 20 mA = Display Measuring range = max. point)
3.6.4

SP Signal

Gas transmitter with electro-chemical - or catalytic bead sensors is linear for gas concentration proportional 4 to 20
mA signal.
Semiconductor gas sensors that are not linear and have a (exponential) signal. This signal leads to a non-linear 4
to 20 mA signal from the gas transmitter.
The Controller LGC/LG2-04 has the capability to monitor both type of gas transmitters, and other linear 4-20 mA
sensors. The type of signal is defined in this menu.
Symbol
Description
SP 01
Sensor Point
Linear
SP Signal
Polygard® is a registered trademark of MSR
Customer Services (858) 578-7887 & (888) GO INTEC
12700 Stowe Drive, Suite 100, Poway, CA 92064 | Ph: (858) 578.7887 & (888) GO.INTEC | relevantsolutions.com/inteccontrols
12700 Stowe Drive, Suite 100, Poway, CA 92064 | Ph: (858) 578.7887 & (888) GO.INTEC | relevantsolutions.com/inteccontrols
INTEC Controls, 12700 Stowe Dr., Suite 100, Poway, CA 92064
INTEC Controls | 12700 Stowe Drive, Suite 100, Poway, CA 92064 | Ph: (858) 578.7887 & (888) GO.INTEC | inteccontrols.com
Specifications subject to change without notice. | USA 131119 | Page 15 of 30
Specifications subject to change without notice. | USA 160104 | Page 15 of 30
Specifications subject to change without notice. | USA 200211 | Page 15 of 30
Setting
Function
Status
Selection SP No. (SP01 is the internal Transmitter)
not
active
= Sensor point enabled for reporting
active
not active = Sensor point disabled for reporting
Setting
Type
Status
CO
Carbon monoxide
Ex
Combusible Gase
NO
Nitric monoxide
NO
Nitric dioxide
2
NH
Ammonia
3
O
Oxygen
2
NH
CO
Carbon dioxide
3
2
R11
Refrigerant gase
R123
Refrigerant gase
R134
Refrigerant gase
R22
Refrigerant gase
TeSP
TeSPerature
RH
Humidity
Setting
Function
Status
Selection SP No.
linear
= Transmitter with linear Output signal
linear
not linear = Transmitter with non linear Output signal (future).
PolyGard
Fax (858) 578-4633 & (888) FX INTEC
www.inteccontrols.com
Page 15
Unit
ppm
%LEL
ppm
ppm
ppm
2
%V/V
ppm
ppm
ppm
ppm
ppm
°C
% RH
is a registered trademark of MSR-Electronic GmbH | LGC/LG2-04
Polygard® is a registered trademark of MSR | LGC/LG2-04
®
Specification subject to change without notice.
Measuring
1
range
.
0 – 300
0 – 100
0 – 50
0 – 25
0 – 300
0 – 25
0 – 2000
0 – 1000
0 – 100
0 – 1000
0 – 1000
0 – 150
0 – 100
LGC/LG2-04
Printed in USA 131119

Advertisement

Table of Contents
loading

Table of Contents