Latching Mode; Horn Function - Intec PolyGard LGC/LG2-04 User Manual

Multi-point controller
Table of Contents

Advertisement

PolyGard
Multi-Point Controller
®
LGC-LG2 – UserManual
LGC-LG2 – UserManual
User Manual - LGC/LG2-04
LGC-LG2 – UserManual
3.5.3

Latching Mode

Definition Latching Function
Symbol
Description
R 01
Relay No.
No
Latching Mode No
Acknowledging of a latching relay in the menu „Relay Status" is possible only if the sensor value is smaller than
the Staged set point including hysteresis. With this condition the status
Example: Relay R2 assigned to Latching mode
On
Alarm 2
Off
Display in the Menu
Status Relay
On
Relay 2
Off
Reset in the Menu
On
Status Relay
Off
3.5.4

Horn Function

With this parameter the relay is defined as a horn relay and can be acknowledged with the following possibilities.
By pressing one of the arbitrary 6 pushbuttons. (Only possible in the starting menu).
Automatic acknowledging when the time runs out.
By an external pushbutton. (Assignment appropriate digital input).
The horn function is activated only if at least one of the two parameters (time or digital input) is set.
Special function Response
After acknowledging the relay via Pushbutton or external DI the time starts. If this time runs out and if the stage is
still exceeded, the relay is energized again..
Symbol
Description
R 04
Relay No.
Reset
Mode
Time
DI
Polygard® is a registered trademark of MSR
Customer Services (858) 578-7887 & (888) GO INTEC
INTEC Controls, 12700 Stowe Dr., Suite 100, Poway, CA 92064
12700 Stowe Drive, Suite 100, Poway, CA 92064 | Ph: (858) 578.7887 & (888) GO.INTEC | relevantsolutions.com/inteccontrols
12700 Stowe Drive, Suite 100, Poway, CA 92064 | Ph: (858) 578.7887 & (888) GO.INTEC | relevantsolutions.com/inteccontrols
INTEC Controls | 12700 Stowe Drive, Suite 100, Poway, CA 92064 | Ph: (858) 578.7887 & (888) GO.INTEC | inteccontrols.com
Specifications subject to change without notice. | USA 160104 | Page 12 of 30
Specifications subject to change without notice. | USA 131119 | Page 12 of 30
Specifications subject to change without notice. | USA 200211 | Page 12 of 30
Setting
Function
Status
Selection Relay
No
Yes
Gas Concentration greater
R2
R2
R2
Off
On
On
Setting
Function
Status
Selection Relay
0 =
Acknowledge the relay at time run out, or via Pushbutton
0
1 = Acknowledge the relay over Pushbutton, af time run off and
alarm is still acting, relay is set again. (Response function).
Time for function Automatic acknowledging or Response function
120
0 = non acknowledging function
0
Assignment, which digital input acknowledges the relay.
Fax (858) 578-4633 & (888) FX INTEC
= Latching Mode non active
= Latching Mode active
Latching is
smaller as Threshold
R2
R2
On
Latching
PolyGard
is a registered trademark of MSR-Electronic GmbH | LGC/LG2-04
Polygard® is a registered trademark of MSR | LGC/LG2-04
®
www.inteccontrols.com
Page 12
overlay.
R2
Off
LGC/LG2-04
Specification subject to change without notice.
Printed in USA 131119