Time, Date; Analog Output; Define The Failure Relay; Power On Time - Intec PolyGard LGC/LG2-04 User Manual

Multi-point controller
Table of Contents

Advertisement

PolyGard
Multi-Point Controller
®
LGC-LG2 – UserManual
LGC-LG2 – UserManual
User Manual - LGC/LG2-04
LGC-LG2 – UserManual
3.7.6

Time, Date

Input and correction of the system time and date. Selection of the time and date format.
Symbol
Description
US
Time format
hh.mm.ss Time
TT.MM.JJ Date
3.7.7

Analog Output

The Controller has two analog outputs (AO) with 4 to 20 mA signal per control module. Each of the analog outputs
can be assigned the signal of one or more sensor points. The assignment occurs in the menu „SP Setup" for
each SP. The sensor point sends the signal that is defined in the menu „C/A Mode".
The Controller determines from the signal of all assigned sensor points the minimum, the maximum or the average
value and sends this value to the analog output. The determination of which value is sent is defined in this menu
„Analog Output X". The analog output can be calibrated with for 4 and 20 mA. In addition the AO can be adjusted
with an ampere meter attached (measuring range 25 mA) then respective AO factor can be changed to adjust the
analog output 4 and/or 20 mA . During AO calibration no evaluation is made of the sensor point signals. This
calibration is factory-set. The factors should only be changed if you have an accurate amp meter.
Symbol
Description
Select
Max.
Output mode
4.0
Calibration
20.0
3.7.8

Define the Failure Relay

Define the Failure Relay. See also malfunction management (3.1)
Symbol
Description
05
Failure Relay R05
3.7.9

Power On Time

Sensors need a warm up period, until the chemical process of the sensor reaches a stable condition. During this
warm up period the current signal can lead to unwanted false alarm. Therefore the Controller starts reporting after
switching on of the power supply and the delay On Time is passed. While this time runs off, the Controller does not
report alarms. The power on status is displayed in the display.
Symbol
Description
30 s
Power On Time

3.7.10 Activation of expansions modules

The Multi point Controller can have expansions modules; therefore only activate Expansions modules for every
four sensor points in addition to the controller module.
Polygard® is a registered trademark of MSR
Customer Services (858) 578-7887 & (888) GO INTEC
INTEC Controls, 12700 Stowe Dr., Suite 100, Poway, CA 92064
12700 Stowe Drive, Suite 100, Poway, CA 92064 | Ph: (858) 578.7887 & (888) GO.INTEC | relevantsolutions.com/inteccontrols
12700 Stowe Drive, Suite 100, Poway, CA 92064 | Ph: (858) 578.7887 & (888) GO.INTEC | relevantsolutions.com/inteccontrols
INTEC Controls | 12700 Stowe Drive, Suite 100, Poway, CA 92064 | Ph: (858) 578.7887 & (888) GO.INTEC | inteccontrols.com
Specifications subject to change without notice. | USA 160104 | Page 20 of 30
Specifications subject to change without notice. | USA 131119 | Page 20 of 30
Specifications subject to change without notice. | USA 200211 | Page 20 of 30
Default
Function
Status
EU = Display time and date in EU format
US
US = Display time and date in US format
hh.mm.ss = Input the correct time (EU format)
hh.mm.ss am = Input the correct time (US format)
TT.MM.JJ = Input the correct date (EU format)
MM.TT.JJ = Input the correct date (US format)
Default
Function
Status
Min.
= Spends the minimum value of all assigned SP
Max.
Max.
= Spends the maximum value of all assigned SP
Average = Spends the average value of all assigned SP
4.0
4.0
= Calibration factor at 4 mA
20.0
20.0
= Calibration factor at 20 mA
Default
Function
Status
R05 = Define the failure relay
Default
Function
Status
30 s
XX = Define the Power On Time (sec.)
PolyGard
Fax (858) 578-4633 & (888) FX INTEC
www.inteccontrols.com
Page 20
is a registered trademark of MSR-Electronic GmbH | LGC/LG2-04
Polygard® is a registered trademark of MSR | LGC/LG2-04
®
Specification subject to change without notice.
LGC/LG2-04
Printed in USA 131119

Advertisement

Table of Contents
loading

Table of Contents