Rehau NEA SMART 2.0 End User Manual page 41

Hide thumbs Also See for NEA SMART 2.0:
Table of Contents

Advertisement

Thermal actuator MINI 24 V
Operating voltage
Operating power
Inrush current
Maximum stroke
Actuation force
Degree of protection / Safety class
CE Conformity
Dimensions: (W x H x D in mm)
Cable length
Housing material
Housing color
Weight
Ambient temperature
Storage / transport temperature
Application environment
Actuator BALANCE 24 V
Operating voltage
Operating power
Inrush current
Maximum stroke
Actuation force
Control characteristic
Medium temperature
Storage temperature
Ambient temperature
Degree of protection / Safety class
Dimensions (W x H x D in mm)
Cable length
Housing color
Weight
Application environment
24 V AC/DC, +20 % ... -10 %
1.2 W
< 300 mA für max. 2 min.
3.5 mm
90 N ± 10 %
IP54 / III
acc. EN 60730
36 x 48 x 49
1 m
Polyamid
light grey (RAL 7035)
0.1 kg
0 °C ... +60 °C
-25 °C ... +60 °C
In dry closed rooms
24 V AC/DC, +20 % ... -10 %
< 0.5 W
30 mA for max. 200 ms
4.5 mm
100 N
PID, adaptive
0 - 60 °C
-25 °C to + 60 °C
max. 50 °C
IP54/III
37.8 x 95.3 x 53.2
1 m
RAL 9003
188 g
In dry closed rooms
End user manual
41

Hide quick links:

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the NEA SMART 2.0 and is the answer not in the manual?