Example of ConfigureCmd
Description
Device
Config
ReportReq
Config
ReportRsp
R718IA2
ReadConfig
ReportReq
ReadConfig
ReportRsp
(1) Configure R718IA2 device parameter MinTime = 1min, MaxTime = 1min, BatteryChange = 0.1v
Downlink: 0141003C003C0100000000
Device Return:
8141000000000000000000 (configuration success)
8141010000000000000000 (configuration failure)
(2) Read R718IA2 device parameter
Downlink: 0241000000000000000000
Device Return:
8241003C003C0100000000 (device current parameter)
Example for MinTime/MaxTime logic:
Example#1 based on MinTime = 1 Hour, MaxTime= 1 Hour, Reportable Change i.e. BatteryVoltageChange=0.1V
MaxTime
Sleeping(MinTime)
Wakes up and collects data
REPORTS 3.6V
Note: MaxTime=MinTime. Data will only be report according to MaxTime (MinTime) duration regardless BatteryVoltageChange value.
Cmd
DeviceType
ID
MinTime
0x01
(2bytes Unit: s)
0x81
(0x00_success)
0x41
0x02
MinTime
0x82
(2bytes Unit: s)
Wakes up and collects data
REPORTS 3.6V
NetvoxPayLoadData
MaxTime
(2bytes Unit: s)
Status
Reserved (9Bytes, Fixed 0x00)
MaxTime
(2bytes Unit: s)
MaxTime
Sleeping(MinTime)
Wake up and collects data
6
BatteryChange
(1byte Unit:0.1v)
Reserved
(8Bytes, Fixed 0x00)
BatteryChange
(1byte Unit: 0.1v)
REPORTS 3.6V
Reserved
(4Bytes, Fixed0x00)
Reserved
(4Bytes, Fixed 0x00)