Feig Electronic VEK MNH Operating Manual page 43

Traffic detector
Table of Contents

Advertisement

VEK MNH
Symbol
Description
Direction A: Loop 1→Loop 2 or direction B: Loop 2→1
Dir A, Dir B
L1, L2
Loop 1 or 2
Out A, Out B
Signal output direction A or B
LM
Logic module
LOC
Loop coverage counter
DLC
Direction logic counter
Tab. 29: Key to symbols
Direction logic system
With all the logics, the first loop covered determines the direction of counting or of travel. If loop 1 is
covered first, the signal output and counting is done for direction A (see "0 Direction detection
principle", page 42).
In the factory settings, travel direction A is output via hardware output 1, and travel direction B via
hardware output 2. The assignment of the signal outputs can be changed (see "11.8 Assigning an
output to a loop (Assignment)", page 40).
NOTE
Counter readings in the Detector Tool
The counter readings are displayed in the Detector Tool. It should be noted that the counter
overflows at 65,535 (2
The counter readings are not protected against power failure!
DIP
Detector Tool
OFF
OFF
ON
On
Tab. 30: Setting direction detection
VEK MNH Operating Manual v1.3 en
16
) and is automatically erased.
Direction detection
Switched off (factory settings)
Switched on
43 | 56
Description of settings