PAW-FC-RC1 is a 230 VAC electronic fan-coil thermostat for
room temperature control. It is suitable for every kind of building
where reduced energy consumption and high comfort need to be
met. The ability to switch between control modes depending on
occupancy, makes it particularly suitable for public spaces, such
as hotel rooms, offices, schools, hospitals, etc.
The modular design makes it easy to install and the flush
mounting gives the unit a discreet appearance.
WARNING: HAZARD OF ELECTRIC SHOCK, EXPLOSION, OR ARC FLASH.
Follow safe electrical work practices and applicable local
codes.
Read and understand the instructions before installing
the product. Follow the instructions during installation.
Installation, wiring, testing or service must be performed
only by qualified persons in accordance with all
applicable codes and regulations.
Do not use the product for life or safety applications.
Do not install the product in hazardous or classified
locations.
Do not exceed the product's ratings or maximum limits.
The product may use multiple voltage/power sources.
A qualified person is one who has skills and knowledge related to the construction and operation of this electrical equipment and
installations, and has received safety training to recognize and avoid the hazards involved.
If this product is used in a manner not specified by the manufacturer, the protection provided by the product may be impaired.
No responsibility is assumed by Schneider Electric for any consequences arising out of the use of this material.

11.1 Specifications

Supply voltage
Power consumption
Protection class
Ambient humidity
Ambient temperature
Measuring range, temperature
Sensor element, temperature
Accuracy, temperature
Display
Display type
Output signal, temperature
Setpoint adjustment
Mounting
Installation
Digital inputs (DI)
Digital outputs (DO)
Failure to follow these instructions will result in serious injury or death.
230 V ~ (207...253 V ~
50/60 Hz)
< 2 VA
IP30
10...90% R.H. (non-
condensing)
0...50°C
0...50°C, external sensor at
Temp / AI: 0...80°C
NTC
±0.5 K
Built-in
LED-backlit LCD
NTC
5...35°C
Room (flush-mounted with
screw distance cc 60 mm)
Fan-coils, 2 or 4-pipe
1 x Closing potential-free
contact
3 x Relay outputs for 3-step
fan control, 230 VAC, Max. 5
A
2 x Relay outputs for On/Off
valve actuators, 230 V AC,
Turn off ALL power supplying equipment before working
on or inside the equipment.
Use a properly rated voltage sensing device to confirm
that all power is off.
Do NOT depend on the product for voltage indication.
Products rated only for basic insulation must be installed
on insulated conductors.
Current transformer secondaries (current mode) must be
shorted or connected to a burden at all times.
Remove all wire scraps and tools, replace all doors,
covers and protective devices before powering the
equipment.
Analogue inputs (Temp / AI)
Change-over function
DI or Temp / AI
Communication port
Internal serial port, type
Internal serial port, built-in protocol
Internal serial port, commun. speed
Internal serial port, parity
Internal serial port, stop bit
Cable connection
Dimensions, external (W x H x Da)
Weight, incl. packaging
Material, housing and base
Material, fire resistance
Color, housing and base
27
Max. 5 A
1 x PT1000 (standard: for
the clamp-on sensor to
install at the heat pump
supply pipeline or for other
functions)
Manual or automatically via
1
RS485
Modbus (RTU)
9600 bps (4800...38400
bps)
Even (Even, Odd, None)
1 (1 or 2)
Screw terminals max. 1.5
2
mm
(AWG 16)
95 x 95 x 50.5 mm
0.24 kg
Polycarbonate, PC
UL 94 V-0
Signal white RAL 9003