Specifications; Dimensions; Functions - Panasonic PAW-FC Installation And Maintenance Manual

Hide thumbs Also See for PAW-FC:
Table of Contents

Advertisement

13.1 Specifications

Built-in sensing element
Accuracy
Set-point range
Display range
Operating temp.
Operating humidity
Power consumption
Power supply
Relay & load
Protection class

13.2 Dimensions

Front view

13.3 Functions

Set-point Adjustment
The set-point buttons allow users to adjust the setpoint (in
0.5 °C increments) for the space.
Fan Speed
Users can select a fan speed (High, Medium, Low or
Automatic) by a short press of the FAN button.
Mode Control
Users can switch operating modes (Heating, Cooling, or
Ventilation) by pressing the Mode button.
Eco Mode
To begin Eco mode, do a short press of the ECO button until
the ECO icon flashes in the lower right corner of the LCD
display. In Cooling mode, the set-point is automatically
adjusted to 26 °C and the fan speed is set to Low. In Heating
mode, the set-point is automatically adjusted to 18 °C and the
fan speed is set to Low. To exit Eco mode, do a short press of
the ECO button to cancel Eco mode.
100 kΩ NTC, type 3
±1 °C
5 to 35 °C
0 to 50 °C (shown in 0.5 °C
increments)
0 to 50 °C
5 to 95 %RH (non-condensing)
< 1 W
90 to 240 Vac, 50/60Hz
Relay rating 5A
Load rating 2A resistive, 1A
Inductive
IP20
Back view
Housing
Dimensions
Wall box
Hole pitch
Control pollution degree
Operation type
Terminal sizing
Pollution degree
Agency approvals
Side view
Button Lockout Function
This function allows the buttons to be deactivated to prevent
thermostat operation by others.
Low Temperature Protection
If the room temperature drops below 5°C, Heating mode will
start automatically and the fan speed will be set to High. Once
the temperature reaches 7°C, the thermostat will switch off the
output.
Alert
In the event of an operating exception, the thermostat will
attempt to command the valve to close and place the device
in an inoperative state. The display will indicate the current
status with one of five diagnostic messages:
EEPROM:
Temperature sensor short-circuit:
Temperature sensor open-circuit:
Ambient temperature is higher than 50°C:
Ambient temperature is lower than 0°C:
34
Flame-retardant PC
86 x 86 x 14.5 mm
(3.40" x 3.40" x 0.57")
BS wall box, min. 35 mm depth
60 mm (standard)
Pollution Degree 2
Type 1.B
Max: 2 x 1.5 mm² or 1 x 2.5 mm²
conductors
2
European conformance CE:
IEC/EN 60730-1
IEC/EN 60730-2-9
EE
E1
E2
HI
LO

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents