Installation; Unit Location - Recommendations - Panasonic PAW-FC Installation And Maintenance Manual

Hide thumbs Also See for PAW-FC:
Table of Contents

Advertisement

PAW-
EC fan 2-pipe
1)
Lo / Med / Hi
Total cooling capacity
1)
Lo / Med / Hi
Sensible cooling capacity
Water flow
Lo / Med / Hi
Water pressure drop
Lo / Med / Hi
2)
Lo / Med / Hi
Heating capacity
PAW-
EC fan 4-pipe
1)
Lo / Med / Hi
Total cooling capacity
1)
Lo / Med / Hi
Sensible cooling capacity
Water flow
Lo / Med / Hi
Water pressure drop
Lo / Med / Hi
2)
Lo / Med / Hi
Heating capacity
Water flow
Lo / Med / Hi
Water pressure drop
Lo / Med / Hi
1) According to Eurovent standard. Air: 27°C DB / 19°C WB. Water in/out: 7°C / 12°C.
2) According to Eurovent standard. Air: 20°C. Water in/out: 45°C / 40°C.

5. Installation

CAUTION
-
The unit installation work must be done by qualified personnel according to the local rules and this manual.
-
The unit should not be installed in a bathroom, a laundry, a sauna or a swimming-pool.
During the installation:
Take care to avoid any rough handling or impacts when
unloading and moving the appliance.
Before hoisting into position, test lift to insure stability and
balance. Avoid twisting or uneven lifting of the units.
The units shall be carefully inspected before unit
installation to make sure that no handling damage has
occurred.
5.1 Unit location – Recommendations
Select the unit location with the following aspects in mind:
Choose an area free from obstructions which may cause
uneven air distribution and/or return.
Consider using an area where installation is easy.
Choose a position that allows for the clearances required.
Look for a position in the room which ensures the best
possible air distribution.
Install unit in a position where condensate can easily be
piped to an appropriate drain.
FC2E-U020
FC2E-U030
kW
1,6 / 1,8 / 2,4
1,9 / 2,9 / 4,0
kW
1,3 / 1,5 / 2,0
1,4 / 2,2 / 3,1
l/h
267 / 306 / 409
325 / 497 / 688
kPa
4,2 / 6,9 / 11,2
3,5 / 8,6 / 14,6
kW
2,2 / 2,5 / 3,2
2,3 / 3,7 / 4,5
FC4E-U020
FC4E-U030
kW
1,4 / 1,5 / 2,0
2,0 / 2,7 / 3,4
kW
1,2 / 1,4 / 1,9
1,5 / 2,1 / 2,6
l/h
234 / 262 / 344
344 / 464 / 581
kPa
6,6 / 9,1 / 14,0
4,4 / 8,2 / 11,7
kW
0,8 / 0,9 / 1,2
2,2 / 3,1 / 3,8
l/h
132 / 153 / 201
374 / 530 / 658
kPa
25,7 / 33,4 / 53,6
13,7 / 24,2 / 35,0
FC2E-U040
FC2E-U050
2,8 / 3,5 / 4,7
3,4 / 4,4 / 6,1
2,1 / 2,7 / 3,6
2,6 / 3,5 / 4,7
481 / 604 / 808
579 / 765 / 1050
6,8 / 11,4 / 18,6
8,4 / 13,1 / 22,2
3,7 / 4,6 / 6,2
4,5 / 6,0 / 8,1
FC4E-U040
2,6 / 3,2 / 4,0
2,1 / 2,6 / 3,3
442 / 556 / 690
6,7 / 10,9 / 15,5
3,0 / 3,5 / 4,1
521 / 603 / 699
24,2 / 30,9 / 39,8
All these sections have been inspected before leaving the
factory. It is therefore important to insure that no bolts,
screws or other fixing system are loosened or missing
before the commissioning. During the handling of the
machine it is mandatory to provide all the devices
necessary to guarantee personal safety.
Positions to avoid:
Exposure to direct sunlight.
Exposure to oil vapours.
Areas close to heat sources.
Installation in areas with high frequency waves.
On damp walls or in positions that may be exposed to
water hazard.
Where curtains or furniture may obstruct free air circulation.
Positions too close to heating sources which may damage
the unit.
10
FC2E-U060
FC2E-U070
3,7 / 5,5 / 7,2
4,1 / 6,5 / 9,6
2,7 / 4,1 / 5,4
3,0 / 4,9 / 7,2
640 / 944 / 1243
700 / 1119 / 1649
3,4 / 7,6 / 11,7
5,8 / 13,1 / 24,6
4,5 / 7,4 / 10,0
5,2 / 9,2 / 13,0
-
FC4E-U060
FC4E-U070
-
3,0 / 5,0 / 6,6
3,2 / 6,1 / 7,9
-
2,3 / 3,8 / 5,1
2,6 / 4,7 / 6,3
-
516 / 858 / 1144
549 / 1041 / 1366
-
6,0 / 14,1 / 22,4
7,2 / 19,2 / 30,1
-
3,7 / 5,5 / 7,0
4,5 / 7,1 / 9,8
-
636 / 939 / 1210
776 / 1214 / 1686
-
7,6 / 13,8 / 20,7
10,2 / 20,8 / 36