Installing The 3-Way Regulating Valve - Accessory - Panasonic PAW-FC Installation And Maintenance Manual

Hide thumbs Also See for PAW-FC:
Table of Contents

Advertisement

6.2 Installing the 3-way regulating valve - accessory

The water flow has to be controlled by installing the motorized thermo-electric valves supplied an accessory or by installing motorized
field supplied valves.
Ref.
Description
1
Actuator
Valve ½"
2
Valve ¾"
Valve 1"
3
Shell
4
Clips
5
Gasket
-
With 4–pipes models, first install the valve assembly
for the cold circuit followed by the valve assembly for
the hot circuit.
-
Connect the valve assemble to the coil and fasten it
by a 30Nm torque.
-
Insulate the valve assembly.
Gasket type
Rubber
Fibre
-
Fit the actuator on the valve body, route the valve
cable through the box and connect it to the terminal
block as shown in the figure below.
N
Neutral
L
Phase
Lc
Condensate Pump phase
H
Heating
C
Default contact condensate pump
V
Cooling valve
V1, V2, V3
Motor speed
2-pipe
PAW-FC2*-U020 to
PAW-FC2*-U040
1
-
1
-
1
3
2
Torque [Nm]
10 / 12
25 / 30
PAW-FC2*-U050 to
PAW-FC4*-U020 to
PAW-FC2*-U070
PAW-FC4*-U040
1
-
-
1
1
3
2
14
4-pipe
PAW-FC4*-U050 to
PAW-FC4*-U070
2
1
1
-
1
3
4
Cables routing
2
-
1
1
1
3
4

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents