4 Data Exchange Example
4.2

XG5000 program

4.2.1

P2P Block definition

We will define 1 P2P block for each value that we want to transfer following the previously table, and
associate a specific conditionnal action flag to the different elements (for read or write).
In the project tree, double click on 'P2P Block' under communication module – [P2P 01].
1st
2nd
Set the different table elements for the first line as following:
Item
Ch
Driver Setting
P2P function
Conditional flag
Command type
No. of variables
Data size
Destination station
Destination station number
20
Setting
Note
2
XGT Channel number
Mod. RTU Clt
fixed
READ
Read or Write function
M10
Flag to trigger the communication
1. Single
Select 2. if want to read several
word registers in 1 command
1
fixed
Enter value if read several word
registers in 1 command
Enable
To define Modbus ID
1
Modbus ID of the targeted device