9 - Electricity
Before any operation on the electric box, check that the hoist supply is disconnected.
An isolator switch should be installed at a maximum of 6 meters from the hoist.
9-1 GENERALS
•
The customer must supply the power supply cable, the fuses and the main isolator switch (refer to the wiring diagram).
•
Check that the mains system is correct for the hoist.
•
Check that the voltage does not vary by more than + 5% from the nominal value.
•
Neutralize the electric sources.
•
Make sure that the main hoist electric power switch is off.
•
Do not use binding posts (luster terminals, etc.) to connect the power supply cable to the hoist.
•
Do not use rigid cable or cable with a section different to that indicated below to supply the hoist.
•
Never shunt the isolators, the power switches or the limitation or prevention equipment.
•
Never block, adjust or remove the limit stops or switches to go higher or lower than these allow.
Minimum cable sections:
Power supply:
Auxiliary current:
Control box/hoist:
9-2 LOW VOLTAGE CONTROL
9-2.1 ELECTRICAL CONNECTION
Connection:
1.
Remove the control box cover.
2.
Insert the cable (PS) into the box through the PG cable gland.
3.
Connect phases L1 - L2 - L3, and the ground wire to the terminal board X1(see 9.2).
4.
Check that the terminals are correctly tightened.
5.
Close the box.
6. Check the hoist operation.
The supply cable must be equiped with a power switch or an isolator in conformity with the regulation.
2
1.50 mm
2
0.75 mm
2
1.00 mm
The supply cable and main isolator switch must be supplied by the costummer.
CAUTION!
PS: Power supply
PB: Control box connection
Fuses for control voltage
Fuses for power supply
- 230 V
- 400 V
CAUTION!
9807 / 9.1
T 1,25 A
10 A
10 A