Setpoint List
Setpoints, listed by the Description name, are defined in the
Description
1.0 Air Cooled Head Pressure
1.0 Air Cooled Head Pressure
Setpoint
10 Volts Opens Chilled Water
10 Volts Opens Chilled Water
Valve
10 Volts Opens Hot Water Valve 10 Volts Opens Hot Water Valve
2.0 Air Cooled Head Pressure
2.0 Air Cooled Head Pressure
Dehumidification Setpoint
Dehumidification Setpoint
2.0 Air Cooled Head Pressure
2.0 Air Cooled Head Pressure
Setpoint
Air Flow Monitoring Damper Area
Air Flow Monitoring Damper Flow
Air Flow Monitoring Damper K
Factor
Air Flow Monitoring Damper M
Factor
Air Flow Monitoring Damper
Setpoint
Air Flow Monitoring Device
AMD Transducer Range
Transducer Range
Air Flow Monitoring Exhaust
Cone Flow
Air Flow Monitoring Exhaust
Exhaust Inlet Cone K Factor
Cone K Factor
Air Flow Monitoring Supply Cone
Flow
Air Flow Monitoring Supply Cone
Supply Inlet Cone K Factor
K Factor
Air Flow Monitoring Thermal
AMD Thermal Dispersion Max
Dispersion Damper Max Velocity
Air Flow Monitoring Type
Air Source Heat Pump Allow
ASHP Allow Defrost Mode
Defrost Mode
Air Source Heat Pump Defrost
Cancel Condensing Setpoint
Air Source Heat Pump Defrost
Status
Air Source Heat Pump Electric
ASHP Electric Heat Defrost
Heat Defrost
ASHP Electric Heat Defrost
Air Source Heat Pump Electric
Enable. Call Valent for
Heat Defrost Enable
Air Source Heat Pump Low
ASHP Low Ambient Compressor
Ambient Compressor Lockout
Setpoint
Alarm Reset
Alarm Status
Ambient Cooling Lockout
Ambient Heating Lockout
BACnet Time Synch
BACnet UDP Port
Bapi Space Sensor Enable
Bapi Space Sensor Enable
Chilled Water Valve Position
Chilled Water Valve Off Position
When Unit Off
CO2 Control
Maximum Damper Control
CO2 Damper Maximum Position
CO2 Deadband
Valent Controls IOM
UMT Name
LCD Name
= Editable
= Editable
—
Setpoint
—
Valve
—
—
—
Setpoint
AMD Damper Area
—
AMD Airflow
AMD
AMD K Factor
—
AMD M Factor
—
Damper Setpoint
SETPOINT
—
Exhaust Airflow
EXHAUST
—
Supply Airflow
SUPPLY
—
—
Velocity
Type
—
—
ASHP Defrost Cancel
—
Condensing Setpoint
ASHP Defrost Status
ASHP
—
—
Password.
—
Lockout Setpoint
Alarm Reset
ALARM RESET
Alarm Status
ALARM STATUS
AMB Lockout
AMB LOCKOUT
AMB Lockout
AMB LOCKOUT
Time Synch
—
UDP Port Number
—
—
—
CO2 Control
—
—
Position
CO2 Deadband
—
Setpoint Descriptions
Web UI Name
Min
= Editable
Air Cooled Cond Temp
90°F
—
—
—
—
Air Cooled Cond Temp
90°F
Air Cooled Cond Temp
90°F
Damper Area
—
Air Flow AMD
—
K Factor AMD
—
M Factor
—
Damper Spt
—
AMD Transducer Range
—
Air Flow Exhaust
—
K Factor Exhaust Fan
—
Air Flow Supply
—
K Factor Supply Fan
—
TD AMD Max Velocity
—
AFMS Installed?
—
—
—
ASHP Defrost Cancel
55°F
—
—
—
—
ASHP Electric Defrost
—
ASHP Low Ambient
10°F
Alarm Reset
—
Alarm Status
—
Cooling Lockout
50°F
Heating Lockout
65.0°F
—
—
—
—
—
—
—
CO2 Enabled
—
CO2 Damper Max
0%
CO2 Deadband
0 ppm
29
section on page 40.
Max
Default
States
140°F
115°F
—
—
False
False, True
—
True
False, True
140°F
115°F
—
140°F
115°F
—
—
—
—
—
—
—
—
—
—
—
—
—
—
0 cfm
—
—
0-1 InWc
0-.25, 0-.5, 0-1, 0-2
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
True
False, True
80°F
60°F
—
Normal, 1x Defrost, 2x Defrost,
3x -> Aux Heat, Defrosting, Defrost
—
Normal
Disabled, Low Sat -> Aux Heat,
Low Amb -> Aux Heat, Aux Heat,
Not Installed
—
Disabled
Enabled, Disabled
—
—
Password required.
50°F
17°F
—
—
False
False, True
—
Normal
Alarm, Normal
90°F
55°F
—
100.0°F
80.0°F
—
—
Disabled
—
—
47808
—
—
False
False, True
Closed
Closed, Open
—
—
Enabled, Disabled
100%
30%
—
500 ppm 100 ppm
—
IOM-C1-0616
Part Number 474626