3. A small Set window appears. Enter a new
value, then click OK.
4. The change will take effect in the setpoint
list.
Changing the Fan Speed
To change the fan speed, adjust the Supply Fan
Max Speed setpoint.
1. Click on the Setpoints and Setup tab.
2. Locate the Supply Air Setpoints group on
the screen.
3. Locate the Supply Fan Max Speed setpoint,
and click on the Max Speed button to the
right.
4. A small Set window appears. Enter the new
fan speed, then click OK.
The change is then reflected on the Setpoints
and Setup screen.
Valent Controls IOM

Manually Overriding a Setpoint

Many setpoints can be manually overridden
during troubleshooting. Refer to the
Override
section on page 52 for definitions of
override points.
1. Click on the Manual Override tab.
2. Set Enable Manual Override to On.
3. Locate the setpoint to override.
4. Depending on the setpoint, to override the
point:
Click on the Override button.
Click on the On or Off button.
Click and move the slider button to
increase or decrease the value.
Click on the 0-100% button, then use
the pop-up Set screen to enter a new
value.
The change is reflected for the setpoint on the
Manual Override screen.
The manual override mode is in effect for four
hours, after which setpoints return to the
previous state or Auto.
To stop an override, click on the Auto button. To
cancel the override mode before it expires, set
Enable Manual Override to Off.
23
Manual
IOM-C1-0616
Part Number 474626