Using BACnet Communications

Wiring
The connection for BACnet IP is a standard
CAT5 Ethernet port which is located on the
bottom of the controller.
The connection for BACnet MSTP should be
made with shielded 18-22 AWG, twisted pair,
stranded wire (Belden 3106A or Belden 3107A)
connected to the three-position RS-485
connector on the bottom of the controller.
BACnet connections on the bottom of the JENEsys controller.

Using LonTalk Communications

Wiring
The wiring for LonTalk communications should
be made with shielded 18-22 AWG, twisted pair,
stranded wire connected to the two-port LonTalk
connector on the TOP of the controller.
LonTalk adapter on the top side
of the controller (orange plug)
Valent Controls IOM
BACnet IP connection
BACnet MSTP connection
25
Changing the BACnet IP Settings
The BACnet IP settings for the JENEsys
controller are available in the
the LCD display. For information on how to
access the IP settings, refer to
or MSTP Settings
on page 9.
BACnet is an optional feature which must be
licensed. Although data will appear for viewing
on the communication menu, settings cannot be
changed if the unit has not been licensed.
Changing the BACnet MSTP Settings
The BACnet MSTP setting for the JENEsys
controller are available in the
the LCD display. For information on how to
access the MSTP settings, refer to
BACnet IP or MSTP Settings
BACnet is an optional feature which must be
licensed. Although data will appear for viewing
on the communication menu, settings cannot be
changed if the unit has not been licensed.
Checking the LonWorks Settings
The JENEsys controller's LonWorks settings are
available in the
POINTS
more information, refer to
Settings
on page 9.
LonTalk is an optional feature which must be
licensed. Although data will appear for viewing
on the communications menu, settings cannot
be changed if the unit has not been licensed.
POINTS
menu of
Reviewing BACnet IP
POINTS
menu of
Reviewing
on page 9.
menu on the LCD. For
Reviewing LonWorks
IOM-C1-0616