16-Point Module 1 - valent VPR Series Controls Instruction Operation & Maintenance

Table of Contents

Advertisement

Analog Output
1
OA Damper Output
2
3
Modulating Heat Percentage
4
Supply Fan Speed Output
5
Electric Heat Output
Digital Scroll Output /
6
Chilled Water Output
7
Modulating Hot Gas Reheat
8

16-Point Module 1

Universal Input
1
Space Static Pressure
2
Exhaust Temperature
3
Refrigerant Pressure A
4
Exhaust Fan Status
5
CO
Level
2
6
Heat Wheel Status
7
Mixed Air Temperature
8
Refrigerant Pressure B
Digital Output
1
Exhaust Fan Start/Stop
2
Energy Recovery Wheel Start/Stop
3
Reversing Valve Output
4
Condenser Fan Start/Stop
Valent Controls IOM
Terminals
Type
AO1
0-10 VDC (0-100%). Used for
0V
(analog) modulating dampers.
0V
AO2
0-10 VDC (0-100%) / 0-10 VDC (0-
AO3
100% or 100-0%) Direct or reverse
0V
acting for hot water valve
Default: Reverse
0V
0-10 VDC (0-100%)
AO4
AO5
0-10 VDC (0-100%)
0V
0-5 VDC (0-100%) / 0-10 VDC
0V
(0-100% or 100-0%) Direct or reverse
AO6
acting for chilled water valve
Default: Direct
AO7
0-10 VDC (0-100%)
0V
0V
0-10 VDC (0-100%)
AO8
Terminals
Type
U1
0-10 VDC (-0.5 to 0.5 InWc)
0V
0V
10kΩ Thermistor, Type III
U2
U3
0-10 VDC (0-750 psi)
0V
0V
Contact Closed = Fan ON
U4
U5
0-10 VDC (0-2000 ppm)
0V
0V
Contact Closed = Stopped
U6
(wired to N/C relay)
U7
10kΩ Thermistor, Type III
0V
0V
0-10 VDC (0-750 psi)
U8
Terminals
Type
D1
2-position relay
1C2
1C2
2-position relay
D2
D3
2-position relay
3C4
3C4
2-position relay
D4
27
Notes
Notes
Notes
Heat Pump Reversing Valve
On = Heat, Off = Cool
IOM-C1-0616
Part Number 474626