Briggs & Stratton 12kW Installation And Operation Manual page 22

Single phase air-cooled standby generator system
Table of Contents

Advertisement

Available languages

Available languages

4
5
6
7
8
9
10
11
12
13
14
15
16
25
26
• For power output connection (L1, L2, Neutral (N), and Ground), refer to the National Electric and local codes.
• For communication wires use #18 AWG [1mm
• When connecting to the terminal block, fasten only one wire to each connector screw.
• Torque terminal block screws to 4.4 in-lb [0.49 Newton meter]. 
• Torque circuit breaker connections to 45 in-lb [5 Newton meter].
• Transfer switch connection. In terminal group (E) pin 1, 2 and 3 get connected to a Briggs & Stratton
switch (refer to the transfer switch installation manual).
22
2 Wire-Start
18AWG[1mm
conductors, 300V minimum,
90°C Cu wire.
2 Wire-Start
18AWG[1mm
conductors, 300V minimum,
90°C Cu wire.
E-Stop
18AWG[1mm
conductors, 300V minimum,
90°C Cu wire.
E-Stop
18AWG[1mm
conductors, 300V minimum,
90°C Cu wire.
Not Used
12VDC
18AWG[1mm
conductors, 300V minimum,
90°C Cu wire.
(B)
18AWG[1mm
conductors, 300V minimum,
90°C Cu wire.
(A)
18AWG[1mm
conductors, 300V minimum,
90°C Cu wire.
GND
18AWG[1mm
conductors, 300V minimum,
90°C Cu wire.
12VDC
18AWG[1mm
conductors, 300V minimum,
90°C Cu wire.
(B)
18AWG[1mm
conductors, 300V minimum,
90°C Cu wire.
(A)
18AWG[1mm
conductors, 300V minimum,
90°C Cu wire.
GND
18AWG[1mm
conductors, 300V minimum,
90°C Cu wire.
Utility
14AWG [2.5mm
minimum, 90°C Cu Wire
Utility
14AWG [2.5mm
minimum, 90°C Cu Wire
2
2
] twisted pair
Refer to Transfer switch
manual to verify if this
function is available.
2
] twisted pair
2
] twisted pair
E-Stop Switch
2
] twisted pair
E-Stop Switch
2
] twisted pair
Refer to the Amplify
Gateway Manual.
2
] twisted pair
2
] twisted pair
2
] twisted pair
2
] twisted pair
Refer to the InfoHub™
Premium Manual.
2
] twisted pair
2
] twisted pair
2
] twisted pair
2
] 300V
Transfer switch Utility
2
] 300V
Transfer switch Utility
] twisted pair conductors, no greater than 500 ft in length, 300 volt wire. 
Contact Close for
Genset Start. (Only for
transferswitch that
provides this option)
Mains monitoring must be
disabled in the controller.
Contact Open to Shutdown
Genset
Comm to WIFI module
Comm to Cellular module
Voltage Sensing for Genset
Start. Use either this signal
or 2-wire start signal for
Genset Start Signal.
®
 basic transfer