Through channel 1 a voltage ranging from 0 V to 10 V is to be measured. In the
program, the code of output xx01 becomes 201 and that of output xx05 becomes
205, since module number 2 is assigned to the first expansion module. By resetting
inputs 201, and 205 to zero, a unipolar voltage measurement ranging from 0 V
through 10 V with a value range from 0 ... 4095 is defined.
The other tasks are accomplished in the same way. For details refer to the following
table:
Jetter AG
Channel #
A/D Value
Register
Channel # 1
3000
Channel # 2
3001
Channel # 3
3002
Channel # 4
3003
5 JX2-IA4 Module - Analog Inputs
Measurement settings for
Unipolar
Bipolar
201 = 0
205 = 0
202 =0
206 =1
204 = 0
208 = 0
Current
203 = 1