Jetter JetWeb JX2-IA4 Operator's Manual page 14

Table of Contents

Advertisement

14
Operating Parameters - Electrical Safety
Parameter
Class of Protection
Dielectric Test
Voltage
Overvoltage
Category
Operating Parameters (EMC) - Emitted Interference
Parameter
Enclosure
Operating Parameters (EMC) - Immunity to
Interference of Housing
Parameter
Magnetic Field with
Mains Frequency
RF Field, amplitude-
modulated
ESD
Value
III
Functional ground is connected
to chassis ground internally.
II
Value
Frequency 30 -230 MHz,
limit 30 dB (µV/m)
at 10 m distance
frequency band 230-1000 MHz,
limit 37 dB (µV/m)
at 10 m distance
(class B)
Value
50 Hz, 60 Hz
30 A/m
Frequency band 27 - 1000
MHz
Test field strength 10 V/m
AM 80 % with 1 kHz
Criterion A
Discharge through air:
Test peak voltage 15 kV
(Humidity Rating RH-2 / ESD-4)
Contact Discharge:
Test peak voltage 4 kV
(severity level 2)
Criterion A
JetWeb
Reference
DIN EN 61131-2
DIN EN 61131-2
DIN EN 61131-2
Reference
DIN EN 50081-1
DIN EN 55011
DIN EN 50081-2
Reference
DIN EN 61000-6-2
DIN EN 61000-4-8
DIN EN 61131-2
DIN EN 61000-6-2
DIN EN 61000-4-3
DIN EN 61000-6-2
DIN EN 61131-2
DIN EN 61000-4-2