4
Jetter AG
Technical Data
Technical Data - JX2-IA4 Module
Power Supply
Connections to the basic unit via system bus
Input terminals
Enclosure
Dimensions (H x W x D in mm):
Weight
Mounting
Input quantity
Voltage Range
Value range (voltage)
Current range
Value range (current)
Input impedance
Resolution (voltage)
Resolution (current)
Sampling interval
Heat loss of CPU logic circuit
Electrical isolation
•
centralised arrangement: via
basic unit
•
decentralised arrangement:
via power supply module
JX2-PS1.
Male connector SUB-D, 9 pins
Plug-in terminal blocks
Aluminium, painted
115 x 45 x 69
190 g
DIN Rail
4 channels:
- U
1-4
- I
1-4
- Unipolar
DC 0 .. 10 V
- Bipolar
DC -10 .... +10 V
- Unipolar
0 ... 4095
- Bipolar
-2048 ... 2047
0 ... 20 mA
0 ... 2047
220 Ω
- Current
12 Bit
11 Bit
< 13 ms
0.3 W
None
4 Technical Data
for voltage
for current