6-2-9. Operation Mode Selection Control

Outdoor unit
SW1: Cooling mode specified input switch
SW2: Heating mode specified input switch
NOTE
SW1: COOL mode selection switch
SW2: HEAT mode selection switch
Input signal
COOL (SW1)
HEAT (SW2)
ON
OFF
OFF
* The display
Operation mode selection control in progress)" appears on the remote controller
"
(
Indoor unit operation intervention function
The statuses of indoor units operating in a mode different from the selected operation mode can be changed
by changing the status of a jumper wire (J01) provided on the interface P.C. board of the outdoor unit.
Jumper lead
Unallowed indoor units in a mode other than the selected operation mode
are not treated as priority (thermostat OFF state).
(Unallowed indoor units)
Operation
Mode
J01 connected
(factory
Cooling
default)
Heating
Fan
Indoor units in a mode other than the selected operation mode are forcibly
switched to the selected operation mode.
PC board
selection
mode
J01 cut
Normal
Cool
Heat
Connection
cable
Interface PCB
C
N
5
1
0
Operation
Only cooling
OFF
operation allowed
Only heating
ON
operation allowed
OFF
Normal operation
Details of Processing
Operation State
Air blow operation at fan speed
set on remote control
Air blow operation at ultra-low
fan speed
Regular air blow operation at fan
speed set on remote control
Remote control operation/display
,
,
, or
can be selected When using the remote
Only
,
, or
can be
selected
Only
or
can be selected
Locally procured
Optional PCB
TB1
COM
COOL
P
J
1
7
HEAT
Shield
wire
Remarks
*
*
Remote control
,
indicator is
displayed.
control,
(mode
select control)
indicator is displayed.
- 71 -
SW1
SW2