Toshiba MMY-SAP0806HT8P-E Service Manual page 151

Air-conditioner multi type, super modular multi system - e, stand alone type, outdoor unit
Table of Contents

Advertisement

Check code
Outdoor 7-segment display
Main
remote
Check
Sub-code
controller
code
10:Element short circuit
11:Position detection circuit
trouble
13:Motor lock trouble
P22
P22
14:Motor current trouble
1C:TH sensor
temperature trouble
1D:TH sensor short
circuit/release trouble
1E:Vdc voltage trouble
01: Compressor 1 side
02: Compressor 2 side
P26
P26
01: Compressor 1 side
02: Compressor 2 side
P29
P29
P31
Location
of
Description
System status
detection
Outdoor fan
IPDU
All stop
IPDU trouble
All stop
All stop
All stop
All stop
All stop
All stop
IPM short-
IPDU
All stop
circuit protection
trouble
IPDU
Compressor
All stop
position
detection circuit
trouble
Indoor
Other indoor
Stop of
trouble
unit
corresponding
(group follower
unit
unit trouble)
- 151 -
Check code detection
Check items (locations)
condition(s)
(Sub code: 10)
Fan IPDU over current
protection circuit
Check fan motor.
Flow of current equal to or
Check for trouble in fan
greater than the specified
IPDU P.C. board.
value is detected during
startup of the fan.
(Sub code: 11)
• Check fan motor.
• Check connection of fan
Fan IPDU position
motor connector.
detection circuit Position
• Check for trouble in fan IPDU
detection is not going on
P.C. board.
normally.
(Sub code: 13)
Gusty wind, an obstruction,
Check fan motor.
or another external factor
Check for trouble in fan
Speed estimation is not
IPDU P.C. board.
going on normally.
(Sub code: 14)
• Check fan motor.
Fan IPDU over current
• Check connection of fan
protection circuit
motor connector.
Flow of current equal to or
Check for trouble in fan
greater than the specified
IPDU P.C. board.
value is detected during
operation of the fan.
(Sub code: 1C)
Higher temperature than
Check fan motor.
Check for trouble in fan
the specified value is
IPDU P.C. board
detected during operation
of the fan.
(Sub code: 1D)
Check for trouble in
The resistance value of
fan IPDU P.C. board.
the sensor is infinite or
zero (open or short circuit).
Check power voltage of
(Sub code: 1E)
the main power supply.
Fan IPDU DC voltage
Check for defect in fan IPDU
protection circuit
P.C. board.
The DC voltage higher or
Check connection of fan
lower than the specified
IPDU P.C. board.
value is detected.
Overcurrent is momentarily
Check connector
detected during startup of
connection and wiring on
compressor.
A3-IPDU P.C. board.
Check for trouble in
compressor (layer short-
circuit).
Check for trouble in
outdoor P.C. board
(A3-IPDU).
Position detection is not
• Check wiring and
going on normally.
connector connection.
• Check for compressor
layer short-circuit.
• Check for trouble in A3-
IPDU P.C. board.
There is trouble in other
• Check indoor P.C. board.
indoor unit in group,
resulting in detection of
E07/L07/L03/L08.