Check code
Outdoor 7-segment display
Main
remote
Check
Sub-code
controller
code
E18
–
–
00:
No outdoor unit
E19
E19
01:
Connection of outdoor unit
from other line
E20
E20
02:
Connection of indoor unit
from other line
Location
of
Description
System status
detection
Trouble in
Indoor
Stop of
unit
communication
corresponding
between indoor
unit
header and
follower units
Trouble in
I/F
All stop
number of
outdoor unit
I/F
Connection to
All stop
other line found
during
automatic
address setting
- 141 -
Check code detection
Check items (locations)
condition(s)
Periodic communication
• Check remote controller
between indoor header and
wiring.
follower units cannot be
• Check indoor power supply
maintained.
wiring.
• Check P.C. boards of
indoor units.
There is no outdoor unit in
• Check connection of
one line.
indoor-outdoor
communication line.
• Check for trouble in outdoor
P.C. board (I/F).
Equipment from other line is
Disconnect inter-line tie cable
found to have been
in accordance with automatic
connected when indoor
address setting method
automatic address setting is
explained in "Address
in progress.
setting" section.