Toshiba MMY-SAP0806HT8P-E Service Manual page 193

Air-conditioner multi type, super modular multi system - e, stand alone type, outdoor unit
Table of Contents

Advertisement

Outdoor Unit
Pressure sensor characteristics
• Input/output wiring summary
High pressure side (PD)
Pin No.
Input/output name
1
OUTPUT
2
3
GND
4
+5V
• Output voltage vs. pressure
High pressure side (PD)
0.5
~
4.5V
0
~
3.92MPa
4.73
4.5
0.5
0
Indoor Unit
Temperature sensor characteristics
Indoor TA(TSA), TRA,TF(TFA) sensor
30
Resistance
[kΩ]
20
10
0
10
Lead wire color
White
Black
Red
3.92
4.15
Pressure (MPa)
20
30
40
Temperature [°C]
Low pressure side (PS)
Input/output name
Lead wire color
OUTPUT
GND
+5V
Low pressure side (PS)
0.5
~
3.5V
0
~
0.98MPa
5
3.5
0.5
0
0
9 .
8
1
4 .
50
60
- 193 -
White
Black
Red
7
P
e r
s s
u
e r
(
M
P
) a
Temperature [°C]
Resistance [kΩ]
0
33.8
5
26.1
10
20.4
15
16.0
20
12.6
25
10.0
30
8.0
35
6.4
40
5.2
45
4.2
50
3.5
55
2.8
60
2.3
5
1 .