Precipitation Sums; List Of Commands; Pwd22/52 Command Set; Help - Vaisala PWD22/52 User Manual

Vaisala present weather detector
Table of Contents

Advertisement

Chapter 5 ________________________________________________________________ Operation

Precipitation Sums

List of Commands

VAISALA _______________________________________________________________________ 57
PWD22/52 has no internal clock for automatic resetting of the sum data
at certain times. This can be done by the host with the following
command:
PW id C
E
C
R
C
where
E
C
C
R
PWD22/52 then responds to the accepted command with the ASCII
A
character <
(06 hex).
K
The host computer can also maintain its own sum calculated from the
continuous PWD22/52 data. This may be safer, if the PWD22/52 power
breaks often and resets the sums before the scheduled time. The water
sum is automatically reset, when it reaches 99.99 mm and the snow sum
at 999 mm.

PWD22/52 Command Set

HELP

By typing HELP, the operator receives information about available
commands.
Table 14
Command Set
Command
OPEN
CLOSE
MES Number
AMES Number Interval
CLRS
STA
PAR
HIST Parameter
INTV Time
=
ESC (ASCII character 1B hex).
=
Carriage Return (13 hex.)
Description
Assigns the line for operator
commands.
Releases the line for automatic
messages.
Displays data message.
Automatic message (with parameters
Number and Interval).
Clears precipitation sums.
Displays status.
Parameter message.
For Vaisala systems use.
For Vaisala systems use.

Advertisement

Table of Contents
loading

This manual is also suitable for:

Pwd22Pwd52