APPLIANCE SPECIFICATIONS

Extraneous light / advanced ignition
During the pre-ventilation phase t1 there shall be no flame
signal. Should the signal be present, for example for
advanced ignition due to bad tightness of the electrovalve,
external lighting, short-circuit in the photo-resistance or
in the connecting cable.When the pre-ventilation time
t1 has elapsed, the control-box brings the
burner to the emergency stop and cuts off fuel
inflow even during the safety time.
No flame
If there is no flame at the end of the safety period, the control device
immediately causes a lock-out stop.
No flame when running
If there is no flame signal during normal working, the control device
will carry out a maximum of three repetitions and if there is still no
flame the device will go immediately into lock-out.
The count is reset at zero each time consents are given (W,SB,R).
The control device is released by pressing for about a second on
the continuous red lamp button.
Program Legend
LMO output signals
LMO input signals
A' Beginning of starting cycle for burners
with light-oil pre-heater
A Beginning of starting cycle for burner
without light-oil pre-heater
B Flame presence
C Working position
D Adjustment stop by "R"
tw
Light-oil preheater waiting time
t1
Pre-ventilation time
t3
Pre-starting time
TSA Safety time
t3n Post-starting time
t4
Time interval between "BV1-BV2"
Tension
Type
V ~
220/240
LMO 24.111B2
Safety at
Pre-ventilation
low voltage
t1
YES
16 s
8 / 16
0006080951_201401
Pre-starting
Safety
Post-starting
time
t3
t2max
15 s
TSA
Time
Interval
t3n
BV1-BV2=t4
10s
15 s