Page 1
PACKAGED ROOFTOP AIR CONDITIONING UNITS Form 100.50-NOM6 (1207) New Release INSTALLATION, OPERATION & MAIN TE NANCE 035-21979-002 YPAL 050 YPAL 051 YPAL 060 YPAL 061 DESIGN LEVEL F SIMPLICITY ELITE CONTROL LD13271...
READ BEFORE PROCEEDING! GENERAL SAFETY GUIDELINES This equipment is a relatively complicated ap pa ra tus. Dur ing installation, operation, maintenance or service, in di vid u als may be exposed to certain com po nents or conditions in clud ing, but not limited to: re frig er ants, oils, materials un der pressure, rotating com po nents, and both high and low voltage.
BASE MODEL NUMBER YPAL050-061 Base Product Type Nominal Capacity :YORK :Packaged Rooftop :Air Cooled :Scroll JOHNSON CONTROLS It is the responsibility of operating/service personnel to verify the ap pli ca bil i ty of these doc u ments to the equip ment in question.
BASE MODEL NUMBER ...3 CHANGEABILITY OF THIS DOCUMENT ...3 NOMENCLATURE ...3 TABLE OF CONTENTS ...4 LIST OF TABLES ... 11 LIST OF FIGURES ...12 SECTION 1 – INTRODUCTION ...13 ECOLOGICAL AND ECONOMICAL DESIGN ...13 Condensing Section ...13 Heating Section ...14 AIR MANAGEMENT ...15 CONTROLS ...15 INDOOR AIR QUALITY ...15...
Page 5
FIELD WIRING ...33 Thermostat ...33 Fan input ...33 Space Sensor ...33 CO2 Sensor ...34 Occupied / Unoccupied Input ...34 Shutdown Input ...34 Smoke Purge Input ...34 BAS Economizer Input ...34 Fault Output ...34 VAV Heat Relay Output ...35 Supply Air Temperature Reset ...35 COMMUNICATION ...35 DIRTY FILTER SWITCH ...35 FIELD CONTROL WIRING CONNECTIONS ...36...
Page 7
Space Sensor – Hard Wired or Communicated ...65 Cooling Operation – Occupied or Unoccupied ...65 Heating Operation – Occupied or Unoccupied ...66 Stand Alone ...66 Cooling Operation – Occupied or Unoccupied ...67 Heating Operation – Occupied or Unoccupied ...67 VARIABLE AIR VOLUME (VAV) ...68 Cooling - Occupied with Thermostat ...68 Cooling –...
Page 8
COMFORT VENTILATION ...81 Sequence of Operation ...82 Conditions of Operation ...82 EXCESSIVE SAT (SUPPLY AIR TEMPERATURE) CONTROL ...82 Cooling ...82 Heating ...83 SPACE SENSOR WITH SET POINT ADJUSTMENT ...84 Sequence of Operation ...84 SPACE SENSOR FAULT OVERRIDE ENABLE ...85 Sequence of Operation ...85 REMOTE CONTROL ...85 Sequence of Operation ...85 REDLINE ...85...
Page 9
Modulating Damper with Fixed Speed Exhaust ...93 Sequence of Operation ...93 Modulating Exhaust with a VFD ...93 Sequence of Operation ...94 PRE-OCCUPANCY PURGE ...94 Criteria for Operation ...94 Sequence of Operation ...94 ENERGY RECOVERY VENTILATOR ...95 Sequence of Operation ...95 LOW VOLTAGE PROTECTION ...95 OUTDOOR AIR HEATING LOCKOUT ...95 HOT GAS BYPASS ...95...
FIG. 1-1 – PACKAGED ROOFTOP AIR CON DI TION ING UNIT ECOLOGICAL AND ECONOMICAL DESIGN • High Effi ciency eco rooftop units are optimized for HFC-410A refrigerant. YORK provides the FIRST standard product offering that meets the latest ASHRAE 90.1 energy effi ciency require- ments. •...
Introduction • Compressor Sound Blankets – Optional factory in stalled sound blankets can be installed to further reduce com pres sor sound attenuation. • Replaceable core fi lter driers – The optional re place able core fi lter driers on the eco a con ve nient means for maintaining and optimiz- ing the units refrigeration system.
AIR MANAGEMENT • DWDI Airfoil fans – High effi ciency fans are used to im prove ap pli ca tion fl exibility, and ad- dress sound and ap pli ca tion con cerns. • Building pressure control – Ex haust fans and barometric relief dampers are available to meet building pressure control requirements.
Introduction • Factory Shrinkwrap – All eco can be ordered from the factory with an optional factory-fresh shrinkwrap pack ag ing. This elimi- nates the contractors worries about dirt and debris clogging up condenser coils or moisture leaking into the air han dler on the units way to the job site or rigging yard.
SECTION 2 – INSTALLATION APPROVALS Designed certifi ed by CSA, ETL, CETL as follows: 1. For use as a forced air furnace with cooling unit (gas heat models). 2. For outdoor installation only. 3. For installation on combustible ma te ri al and may be installed directly on combustible fl...
In cases where space is limited, please call your local York representative for additional information. The clearances shown are to provide adequate condenser airfl...
RIGGING AND HANDLING Proper rig ging and handling of the equip ment is man da to ry during un load ing and setting it into position to re tain warranty status. All lifting lugs must be used to pre vent twisting and damage to the unit. Care must be taken to keep the unit in the upright po si tion during rigging and to prevent damage to the water-tight seams in the unit casing.
Installation TABLE 2-2 – UNIT WEIGHTS - 050-061 MODELS MODEL SIZE BASIC UNIT* ECONOMIZERS NO OUTSIDE AIR 25% OUTSIDE AIR FIXED POSITION MAUAL DAMPER 25% OUTSIDE AIR 2 POSITION ACTUATED DAMPER FULL MODULATION WITH MINIMUM POSITION POWER EXHAUSTS FAN, MOTOR, MODULATING DAMPER AND HOOD FAN, MOTOR, VFD, BAROMETRIC DAMPER AND HOOD GAS HEAT...
UNIT WEIGHTS (CONTINUED) TABLE 2-4 – UNIT CORNER WEIGHTS - 050-061 MODELS MODEL BASIC UNIT BASIC UNIT W/ ECON. BASIC UNIT W/ ECON. & HEATING BASIC UNIT W/ ECON. & HEATING & POWER EXHAUST MODEL BASIC UNIT BASIC UNIT W/ ECON. BASIC UNIT W/ ECON.
Installation ROOF CURB INSTALLATION YORK offers an optional roof curb designed specifi cally for the eco2 foot print. This curb comes as an open condenser model and is shipped disassembled and requires fi eld assembly during installation. Refer to the Installation Manual that is shipped with the roof curb for specifi...
TABLE 2-5 – PHYSICAL DATA – 050-061 MODELS UNIT SIZE GENERAL DATA LENGTH WITHOUT HOOD (INCHES) WIDTH (INCHES) HEIGHT (INCHES) UNIT EER/ IPLV UNIT EER/ IPV GAS HEAT COMPRESSOR DATA (SEE TABLE 2-6) QUANTITY TYPE UNIT CAPACITY STEPS REFRIGERANT (410A) SYSTEM 1 SYSTEM 2 SUPPLY FAN...
Installation FORM 100.50-NOM6 (1207) GENERAL ARRANGEMENT DRAWINGS (CONTINUED) BOTTOM SUPPLY / SIDE RETURN FIG. 2-4 – GENERAL ARRANGEMENT DRAWING (CONT.) LD08370 JOHNSON CONTROLS...
Installation CURB LAYOUT DRAWING / 050-061 MODELS 71.83 NOTES: 1. Unit must be installed square and level. 2. Curb confi guration for “bottom” return and “bottom” supply. 3, These drawings are not intended as construction documents for the fi eld fabricated roof curbs. Johnson Controls will not be responsible for the unit fi...
ELECTRICAL SERVICE SIZING In order to use the electrical service required for the cooling only eco2 rooftop, use the appropriate calculations listed below from U.L. 1995. Based on the confi guration of the rooftop, the calculations will yield different MCA (minimum circuit ampacity), and MOP (maximum overcurrent protection).
Installation ELECTRIC DATA (CONTINUED) TABLE 2-9 – SUPPLY AND EXHAUST FAN MOTOR DATA - ODP HIGH EFFICIENCY NOMINAL VOLTAGE MOTOR 208/3/60 230/3/60 380/3/60 14.0 13.8 21.7 20.0 13.3 28.2 26.0 17.5 41.0 38.0 24.5 53.0 48.0 32.0 66.0 62.0 39.0 84.0 72.0 46.0...
Installation FILTERS Two-inch “throwaway” filters are standard and factory installed in a filter rack located prior to the evaporator coil. Any optional pre-filters ordered with the unit will be shipped inside the unit, but must be field installed. The unit can also be ordered with an extended cabinet and 95% efficient post-filters.
AIR HOODS FOR ECONOMIZER There are two (2) economizer outside air intake hoods pro vid ed with the unit. The front and rear hoods are made operational per the following instructions: • Remove the screws holding the economizer hood ship ping covers in place. Discard covers. •...
Installation CO2 Sensor The addition of a fi eld installed CO2 sensor is required for Demand Ventilation operation. The default input span for the control is 0 to 2,000 ppm with an output voltage range of 0 to 10 VDC. The fi eld will need to supply an external power supply for the sensor.
VAV Heat Relay Output This is a 24 VDC output that is turned on when the unit is in the heating mode. The fi eld can use this as a signal to trigger the opening of the VAV boxes for heating operation.
Installation FIELD CONTROL WIRING CONNECTIONS Wiring Notes: 1. Wiring shown indicates typical wiring. Refer to the IOM manual for more detailed wiring methods and options. 2. All wiring is Class 2, low voltage. 3. Maximum power available from the 24 VAVC terminal is 40 VA. 4.
POWER WIRING Field wiring to the unit must conform to provisions of National Electrical Code (NEC) ANSI / NFPA 70- Lat est Edition and / or local ordinances. The unit must be electrically grounded in accordance with the NEC and / or local codes. Voltage tolerances, which must be main tained during starting and running con di tions, are in di cat ed on the unit data plate.
Installation SINGLE-POINT POWER SUPPLY WIRING Line 1 Field Power Line 2 Line 3 Supply Earth Ground NOTES: 1. All fi eld wiring must be provided through a fi eld-supplied fused dis con nect switch to the unit terminals (or optional mold ed disconnect switch).
SINGLE-POINT POWER SUPPLY WIRING WITH NON-FUSED DISCONNECT SWITCH Line 1 Field Power Line 2 Line 3 Supply Earth Ground NOTES: 1. All fi eld wiring must be provided through a fi eld-supplied fused disconnect switch to the unit terminals (or optional molded disconnect switch).
Installation DUAL-POINT POWER SUPPLY WIRING Line 1 Field Power Line 2 Line 3 Supply #2 Earth Ground Line 1 Line 1 Field Power Field Power Line 2 Line 2 Line 3 Line 3 Supply #1 Supply #1 Earth Earth Ground Ground NOTES: 1.
TABLE 2-16 – THREE PHASE POWER SUPPLY CONDUCTOR SIZE RANGE 050-061 Models Supply Single Point Voltage 208V (2*) 250 kcmil-500 kcmil 230V (2*) 250 kcmil-500 kcmil 380V-60 6 AWG-400 kcmil 460V 6 AWG-400 kcmil 575V 6 AWG-400 kcmil JOHNSON CONTROLS CONTROLS Single Point Dual Point TB...
Installation TRANSDUCER PNEUMATIC TUBING Static Pressure Control Plastic Tubing (Pneumatic Tubing) Duct static transducers (all VAV units) and any unit with an op tion al building pressure control trans duc er, require pneumatic tubing to be fi eld supplied and in stalled. Both the duct static transducer (VAV only) and optional building pressure transducer are mounted behind the right hand damper door.
Economizer Economizer Compartment Compartment FIG. 2-12 – ATMOSPHERIC SENSOR PROBE The atmospheric probe should be mounted on the support post on the control side of the unit between the Economizer and the Filter compartment. JOHNSON CONTROLS FORM 100.50-NOM6 (1207) Filter Filter Compartment Compartment...
Installation DUCT SYSTEM Duct Connection Guidelines All intake and discharge air duct connection to the unit may be made directly to the unit. These air duct con nec tions should be on fl exible material and should be installed so they are suffi ciently loose. Duct runs and transitions must be made carefully to hold friction loss to a min i mum.
GAS PIPING Proper sizing of the gas piping depends on the cubic feet per hour of gas fl ow required, specifi c gravity of the gas and the length of run. National Fuel Gas Code Z223.1 – latest Edition should be followed in all cases unless superseded by local codes or gas company requirements.
Installation 6. The furnace and its individual manual shut-off valve must be disconnected from the gas supply piping system during any pressure testing of that system at test pressures in excess of 0.5 PSIG. Disconnect gas piping from unit when leak testing at pressures greater than 0.5 PSIG.
To protect warranty, this equip ment must be in stalled and ser viced by an authorized JOHNSON CONTROLS ser vice me chan ic or a qualifi ed service per son ex pe ri enced in air han dling and con dens er unit in stal la tion. Installation must com ply with all ap- pli ca ble codes, par tic u lar ly in regard to elec tri cal wiring and oth er safety...
Startup The supply, exhaust and return fans have tie down bolts are installed at the factory to prevent movement in the fan assemblies during shipment. THESE HOLD DOWN BOLTS MUST BE REMOVED PRIOR TO OPERATION OF THE ABOVE FANS. There are eight bolts per assembly two at each comer of the fan skids, front and rear.
17. Verify Variable Frequency Drive setpoints for VAV unit Supply Fan and optional Variable Frequency Drive Exhaust and/or Return Fan drives. The Sup- ply Fan VFD is located to the right of the electrical control box in the supply fan blower compartment. Refer to separate manual for VFD operation sup- plied with the unit.
Startup INITIAL START-UP After all of the preceding checks have been com plet ed and the control pan el has been programmed as re quired, the unit may be placed into op er a tion. 1. Place the Unit Switch in the control panel to the ON position.
Example: The suction pressure is 130 PSIG and the suction line temperature is 57 °F Suction Line Temperature Saturation Temperature for 130 PSIG Evaporator Superheat When adjusting the expansion valve, the adjusting screw should be turned not more than one turn at a time, al low ing suf fi...
GAS HEAT MODELS Pre-Start Checks: • When starting up these units, it is imperative that ALL gas fi ttings within the unit (in addition to the fi eld installed gas connections) are leak checked with a soap solution as part of the unit commissioning process.
Startup • Check the supply pressure. It must be within the limitations shown in Table 3-2. Supply pressure should be checked with all gas appliances in the building at full fi re. At no time should the standby gas pressure exceed 13.5" WC, nor the operating pressure drop below 4.5"...
2-11/16” thru 2-15/16” 3-7/16” thru 3-15/16” JOHNSON CONTROLS Oil Analysis: Use York Type “T” POE oil (clear) for units charged with R-410A refrigerant. The type of refrigerant and amount per system is listed on the unit rating plate. A change in the oil color or odor may be an indication of contaminates in the refrigeration system.
Maintenance Condenser Coils Dirt should not be al lowed to accumulate on the con dens er coil surfaces. Cleaning should be as often as nec es sary to keep coil clean. PERIODIC MAINTENANCE – THREE TO SIX MONTHS Disconnect and lock-out power from the unit anytime service is being per- formed on the fan sec tion.
An incorrectly aligned and tensioned belt can sub stan tial ly shorten belt life or overload blow er and motor bear ings, shortening their life ex pect an cy. A belt tensioned too tightly can over load the motor electrical, causing nui sance trip ping of the motor overloads and/or motor fail ure and/or shaft fail ure.
Maintenance Filter Drier Replacement The fi lter/drier should be replaced any time work is per formed on the refrigerant circuit. The rooftop unit comes with sealed type (non-replaceable) cores as stan dard. If the unit is not equipped with the op tion al valve package (suction, discharge, &...
Disconnect and lock-out power from the unit anytime service is being per- formed on the fan sec tion. Failure to do so could result in serious in ju ry or death due to the fan turning on while work is in progress. Fan Motor 1.
Maintenance Prior to installing the bearing on the shaft, it should be worked around in the housing to make sure that self-alignment will be obtained where the bear ing is in stalled. After the shaft journal has been in spect ed for clean li ness, metal chips or burrs, the bearing is slipped, not forced, onto the shaft.
Do not apply excessive force to the bear ing hous ing (pillow block or bear ing hous ing (pillow block or fl ange) when installing the bearing fl ange) when installing the bearing on the shaft. FIG. 4-7 – ECCENTRIC CAM LOCKING COL LAR BEARING INSTALLATION BEARING INSTALLATION JOHNSON CONTROLS...
Page 62
FORM 100.50-NOM6 (1207) THIS PAGE INTENTIONALLY LEFT BLANK JOHNSON CONTROLS...
SECTION 5 – SEQUENCE OF OPERATION UNIT TYPE The Simplicity Control is capable of being confi gured for either Constant Volume (CV) or Variable Air Volume (VAV) operation. To confi gure the unit for VAV operation a 10,000 to 20,000 ohm resister must be installed on the P7 (CV/VAV) connector on the control board.
Sequence of Operation “COOLING MODE OPERATION ENABLED” – must be enabled using Parameter 53 under the PROGRAM key on the Simplicity control board or under the COOLING SETUP tab in the Simplicity PC software package. “HEATING MODE ENABLED FOR OPERATION” –...
Occupied Heating There are three stages of heating available: • W1 – First Stage of Heating • W2 – Second Stage of Heating • W3 – Third Stage of Heating See the Heating section of this manual for a description of the heating staging.
Sequence of Operation The Simplicity Control will stage off the cooling as follows: • If the space temperature is within 0.5° F of the “CV OCCUPIED COOLING SETPOINT” or “CV UNOCCUPIED COOLING SETPOINT” the control turns off the System 2 compressors, if on, with a 30 second delay between the com- pressors provided the minimum compressor run times have been satisfi...
• “CV UNOCCUPIED HEATING SETPOINT” – using Parameter 13 under the PROGRAM key on the Simplicity control board or under the HEATING SETUP tab in the Simplicity PC software package. • “SPACE SENSOR FAULT OVERIDE EN- ABLED” must be turned on – using Parameter 8 under the PROGRAM key on the Simplicity control board or under the SYSTEM OPTIONS tab in the Simplicity PC software package.
Sequence of Operation The Simplicity Control will stage off the heat as follows: • When the return air temperature is 2.4° F below the “CV OCCUPIED HEATING” or “CV UN- OCCUPIED HEATING SETPOINT” the third stage of heating will turn off. •...
– The Simplicity Control uses the temperature difference calculated when the first com- pressor was turned on to verify the supply air temperature will not drop 5.0° F or more below the cooling “VAV COOLING SUPPLY TEMP UPPER SAT SETPOINT” or “VAV COOLING SUPPLY AIR TEMP LOWER SETPOINT”.
Sequence of Operation • When the supply air temperature is 5.0° F or more above the cooling “VAV UPPER COOLING SAT SETPOINT” or “VAV LOWER COOLING SAT SETPOINT” the Simplicity Control will energize the fi rst compressor. • The control records the supply air temperature right before the compressor is turned on and compares it to the supply air temperature after 5 minutes of operation.
Occupied Cooling – Stand Alone The following System Parameters must be programmed through the Simplicity Control for VAV Stand Alone operation: • “VAV COOLING SUPPLY AIR TEMP UP- PER SETPOINT” – using Parameter 23 under the PROGRAM key on the Simplicity control board or under the COOLING SETUP tab in the Simplicity PC software package.
Sequence of Operation Cooling – Unoccupied Stand Alone The Simplicity Control cannot operate unoccupied cooling with this method of control. Heating – Occupied Stand Alone The following parameters must be programmed into the Simplicity Control: • “VAV OCCUPIED HEATING ENABLED” –...
• If the outdoor air temperature is less then the economizer supply air temperature set point, compressors will not operate regardless of the “OUTDOOR AIR TEMP COOLING LOCK- OUT” set point. LOW AMBIENT OPERATION A condenser fan VFD can be installed on condenser fan # l.
Sequence of Operation SUPPLY FAN OPERATION Constant Volume (CV) The following values need to be programmed: “COOL, FAN ON DELAY” – Using parameter 4 under the PROGRAM key on the Simplicity control board or under the FAN tab in the Simplicity PC software package.
The Simplicity Control monitors the operation of the supply fan by checking the status of a digital input from an air proving switch. After 90 seconds of operation, the Simplicity Control looks for a high state (24-volt input) from the air proving switch circuit at the “APS” connections at the P11 connector on the Simplicity control board.
Sequence of Operation VAV Supply Fan Speed Control The following values need to be programmed: “DUCT PRESSURE SETPOINT” – Using parameter 30 under the PROGRAM key on the Simplicity control board or under the FAN tab in the Simplicity PC software package.
Single Enthalpy The following parameters must be programmed to allow economizer operation: “ECONOMIZER OUTSIDE AIR ENTHALPY SETPOINT” – must be programmed using Parameter 37 under the PROGRAM key on the Simplicity control board or under the ECONOMIZER/EXHAUST tab in the Simplicity PC software package. “OUTSIDE AIR HUMIDITY SENSOR INSTALLED”...
Sequence of Operation “OUTSIDE AIR HUMIDITY SENSOR INSTALLED” - must be disabled using Parameter 36 under the PROGRAM key on the Simplicity Control board or under the EQUIPMENT INSTALLATION tab in the Simplicity PC software package. “RETURN AIR HUMIDITY SENSOR INSTALLED” - must be disabled using Parameter 38 under the PROGRAM key on the Simplicity Control board or under the EQUIPMENT INSTALLATION tab in the...
• When the space temperature is equal to or greater than 2.0° F above the “VAV SUPPLY AIR TEMP RESET SETPOINT” the Simplicity Control will use the “VAV COOLING SUPPLY AIR TEMP LOWER SETPOINT”. Economizer / Compressor Operation The Simplicity Control will use outdoor air without compressor operation when the following is true: •...
Sequence of Operation Constant Volume The following conditions must be met in order for Economizer Loading to function: • The outdoor air temperature must be greater than the return air temperature. • Economizer must be installed but not active. • A call for fi...
COMFORT VENTILATION Comfort Ventilation is a Constant Volume control mode that uses the economizer to control the supply air temperature. When outdoor air conditions allow, the economizer will modulate the outside / return air mix to keep supply air temperatures within the upper and lower Comfort Ventilation set points.
Sequence of Operation TABLE 5-6 HEAT STAGE ON WHEN SPACE INPUT SATISFIED OAT VS OAT COMFORT ZONE SAT VS SAT COMFORT ZONE ECON OPERATION BELOW BELOW BELOW ABOVE ABOVE ABOVE WITHIN WITHIN WITHIN Sequence of Operation Tables 5-4 thru 5-6 use the following defi nitions: •...
• The Simplicity Control will monitor the supply air temperature and compare it to the “SUPPLY AIR TEMP LIMIT COOLING SETPOINT”. If the supply air temperature is 0.1° F or more below this value and the compressor minimum run time requirement has been met the Simplicity Control will turn off the compressor.
Sequence of Operation • The Simplicity Control then starts a 3 minute timer. • If after 3 minutes the supply air temperature is equal to or less than the “SUPPLY AIR TEMP LIMIT HEATING SETPOINT” minus 10.1° F the Simplicity Control will turn the heat stage back on provided there is still a demand for the staged off heat stage.
SPACE SENSOR FAULT OVERRIDE ENABLE The Unit Controller will self confi gure when it identifi es a space sensor has been installed. Once it identifi es that a space sensor is connected, if the input is then removed the control will generate a Space Temperature Sensor Alarm (19).
Sequence of Operation The Simplicity Elite control will keep the compressors off line for 5 minutes. After 5 minutes, the Simplicity Elite control will turn the compressor back on with a 30 second delay between compressors and resume normal operation. After 5 minutes Simplicity Elite control will reset this communicated input back to “OFF”...
• Intelli-Start will only work on a Constant Volume system using a space sensor. • Intelli-Start will only work when the internal scheduling feature is used. It will not work using a hard wired or communicated Occupied com- mand. • Intelli-Start will only function during the fi...
Sequence of Operation • If heating mode is selected the Simplicity Elite control will also compare the current outdoor temperature to the outdoor temperature recorded during the previous start up period. – If the current outdoor air temperature is 10.0° F or more below the previous day the Simplic- ity Elite control will add 5inutes to the above calculated recovery time for every 10.0°...
HYDRONIC HEAT The following parameters must be programmed to use Hydronic Heat: “HEATING MODE ENABLED FOR OPERATION” must be enabled using Parameter 54 under the PROGRAM key of the Simplicity Elite control board or under the HEATING SETUP tab in the Simplicity PC software package.
Sequence of Operation Manual This option uses a manually adjustable outdoor air damper that can set in a fi xed position to control the amount of outdoor air that is brought into the building for ventilation. As long as the supply fan is operative, ventilation air will be brought into the building.
Defi nitions “IAQ SENSOR RANGE” –This establishes the span the Simplicity Elite control uses in PPM. 0 PPM would be equal to a 0 volts input to the Simplicity Elite control, “IAQ SENSOR RANGE” would be equal to 10 volts input to the Simplicity Elite control.
Sequence of Operation When the outdoor temperature is equal to or less than the “LOW AMBIENT ECONOMIZER SETPOINT” the Simplicity Elite control will set the minimum position of the outdoor damper to the programmed “LOW AMBIENT ECONOMIZER MINIMUM POSITION” setting. When the outdoor temperature is 1.0°...
Sequence of Operation When the building static pressure is 0.015” WC or more above the “BUILDING PRESSURE SETPOINT” the Simplicity Elite control closes the output to the exhaust fan motor. The output is at the “EXH” terminal of the P13 connector. When the building static pressure is 0.015”...
Sequence of Operation “ B U I L D I N G S TAT I C P R E S S U R E S E N S O R INSTALLED” – must be turned on using Parameter 85 under the PROGRAM key on the Simplicity Elite control board or under the EQUIPMENT INSTALLATION tab in the Simplicity PC software package.
ENERGY RECOVERY VENTILATOR If the unit has an Energy Recovery Ventilator installed the exhaust fan needs to operate any time the supply fan is energized. This feature can be programmed to only occur in the occupied mode or in both the occupied and unoccupied mode.
Sequence of Operation The following parameters must be programmed: “SPACE TEMP TRENDING ALARM TEMP”- must be programmed under SYSTEM OPTIONS tab of the Simplicity PC software package. “SPACE TEMP TRENDING ALARM TIME”- must be programmed under SYSTEM OPTIONS tab of the Simplicity PC software package.
“Economizer Minimum Position” Alarm • The supply air temperature must be below the “SUPPLY AIR TEMP ALARM SETPOINT FOR HEATING” set point and the following sequence of events have occurred: – All the stages of heating must have been on for 10 or more minutes.
Sequence of Operation “Economizer Minimum Position” Alarm • The supply air temperature must be above the “SUPPLY AIR TEMP ALARM SETPOINT FOR COOLING” set point and the following sequence of events have occurred: – All the stages of cooling must have been on for 10 or more minutes.
SECTION 6 – USER INTERFACE There are three different methods that can be used to interface with the Simplicity Elite control: • Program buttons and display on the Unit Control- • Communication between the Unit Controller and a PC or Personal Computer using “Simplicity PC”.
User Interface Control Center If the program button is pushed while in the program mode, the control will exit the program mode and store any changed data even if the operator failed to press the Alarm/Change button to accept any changes. TEST/UP BUTTON When not in the program mode, if the Test/Up button is pushed and released once within fi...
TABLE 6-1 - PARAMETER POINTS LIST ADDRESS DESCRIPTION NUMBER RUN TEST HEAT FAN ON DELAY HEAT FAN OFF DELAY COOL FAN ON DELAY COOL FAN OFF DELAY ADDRESS TURN OFF CONTINUOUS FAN WHEN STARTING CONSTRUCTION MODE UNOCCUPIED OVERRIDE TIME PERIOD CV OCCUPIED COOLING SETPOINT CV OCCUPIED HEATING SETPOINT CV UNOCCUPIED COOLING SETPOINT...
Page 102
User Interface Control Center TABLE - 6-1 - PARAMETER POINTS LIST (CONT.) ADDRESS DESCRIPTION NUMBER OUTSIDE AIR HUMIDITY SENSOR INSTALLED ECONOMIZER OUTSIDE AIR ENTHALPY SETPOINT RETURN AIR HUMIDITY SENSOR INSTALLED ECONOMIZER OUTSIDE AIR TEMP ENABLE SETPOINT DEMAND VENTILATION (IAQ) ENABLED IAQ SENSOR RANGE IAQ SETPOINT POWER EXHAUST INSTALLED...
Page 103
TABLE - 6-1 - PARAMETER POINTS LIST (CONT.) ADDRESS DESCRIPTION NUMBER 72/73/74/ ALARM ARRAY 75/76 VAV / CV SELECTION HOT GAS REHEAT HOT GAS PRESENT ON COMPRESSOR # 1 COMPRESSORS AVAILABLE FOR COOLING STAGES OF HEAT AVAILABLE DUCT STATIC READING BUILDING STATIC PRESSURE LOW AMBIENT KIT INSTALLED BUILDING STATIC PRESSURE SENSOR INSTALLED...
Simplicity Control to a PC or Personal Computer with “Simplicity PC” software installed. “Simplicity PC” software is available through the York UPG web site. The instructions for downloading the software are as follows: Simplicity PC Download 1.
Page 105
FORM 100.50-NOM6 (1207) 3. Left click on software LD13037 Left click on Software JOHNSON CONTROLS...
User Interface Control Center 4. Left click on Simplicity Software and follow the directions for downloading the program into your computer. USB Adapter Drive - Simplicity Pocket PC 5. Two additional programs are available for down- loading. If you are running the “Simplicity PC” software on a Pocket PC you must also download Simplicity Pocket PC.
7. The FREEnet USB Adapter comes with a standard USB cable. The “A” end plugs into the computer and the “B” end into the FREEnet USB Adapter. 8. The FREEnet Serial Adapter comes with a standard 9-pin Serial Extension Cable. It has a computer standard 9-pin male connector to plug into the adapter and the same style 9-pin female connec- tor to plug into the computer.
Page 108
User Interface Control Center 2. Click on the “Add” button and a dialog box will appear as shown below. Left click on Add button 3. In the “Connection Type” dialog box, select “Se- rial/USB Direct Connection”. Click on the “Port Number”...
Page 109
4. In the dialog box, click the “Add” button. The “Add Connection” dialog box will close and the main Simplicity window will appear. In the left pane of the main screen is a tree. Under “My Connections”, the name of the device installed in the computer port connecting the computer to the simplicity network will appear.
Page 110
User Interface Control Center 8. The right hand side of the screen fi lls with a series of tabs. The tabs allow you to access, read, and change settings for that device. Click on the tab that corresponds to the information you wish to access.
FORM 100.50-NOM6 (1207) SIMPLICITY PC DATA SCREENS The following pages identify the data contained in each of the tabs. Move the cursor to the tab and left click to open. DEVICE NAMES LD13015 EQUIPMENT INSTALLATION LD13016 JOHNSON CONTROLS...
Page 112
User Interface Control Center FORM 100.50-NOM6 (1207) SENSOR READINGS LD13017 JOHNSON CONTROLS...
Page 113
FORM 100.50-NOM6 (1207) ECONOMIZER/EXHAUST LD13018 JOHNSON CONTROLS...
Page 114
User Interface Control Center FORM 100.50-NOM6 (1207) FANS LD13019 JOHNSON CONTROLS...
Page 115
FORM 100.50-NOM6 (1207) COOLING SETUP LD13020 JOHNSON CONTROLS...
Page 116
User Interface Control Center FORM 100.50-NOM6 (1207) COOLING STATUS LD13021 JOHNSON CONTROLS...
Page 117
FORM 100.50-NOM6 (1207) HEATING SETUP LD13022 JOHNSON CONTROLS...
Page 118
User Interface Control Center FORM 100.50-NOM6 (1207) HEATING STATUS LD13023 JOHNSON CONTROLS...
Page 119
FORM 100.50-NOM6 (1207) SYSTEM OPTIONS LD13024 JOHNSON CONTROLS...
Page 120
User Interface Control Center FORM 100.50-NOM6 (1207) OUTPUTS/STATUS LD13025 JOHNSON CONTROLS...
Page 121
FORM 100.50-NOM6 (1207) INPUTS LD13014 COMFORT/DEMAND VENTILATION LD13026 JOHNSON CONTROLS...
Page 122
User Interface Control Center FORM 100.50-NOM6 (1207) GRAPHIC LD13027 CLOCK LD13028 JOHNSON CONTROLS...
Page 123
Weekly Schedule The weekly schedule can only be programmed using the Simplicity PC software under the WEEKLY SCHEDULE SETTINGS tab. The weekly schedule has two Occupied/Unoccupied times for each of the seven WEEKLY SCHEDULE SETTINGS JOHNSON CONTROLS FORM 100.50-NOM6 (1207) days.
Page 124
User Interface Control Center Holiday Schedule The holiday schedule can only be programmed using the Simplicity PC software under the HOLIDAY SCHEDULE tab. There are 20 holiday schedules. To program a holiday schedule left click on the box next to the holiday event you want to program. Click on the down arrow key to set the start date, the current HOLIDAY SCHEDULE FORM 100.50-NOM6 (1207)
Page 125
FORM 100.50-NOM6 (1207) ALARMS LD13031 JOHNSON CONTROLS...
User Interface Control Center REVISING SETTINGS To change a set point move the curser to the value you want to change and left click and highlight the item. FORM 100.50-NOM6 (1207) Left click to highlight Double click to open change screen JOHNSON CONTROLS LD13032...
Page 127
FORM 100.50-NOM6 (1207) To open the change screen double left click. The screen will show the current value and the acceptable range. Us the numeric key pad to enter the revised setting. Left click on “Update” and the value will be change at the Unit Controller. LD13033 JOHNSON CONTROLS...
Page 128
User Interface Control Center To change a value move the curser to the value you want to change and left click and highlight the item. FORM 100.50-NOM6 (1207) Left click to highlight Double click to open change screen JOHNSON CONTROLS LD13034...
Page 129
FORM 100.50-NOM6 (1207) The screen will show the current value and option. Move the curser and left click on the option you want to turn on. Left click on “Update” and the value will be change at the Unit Controller. LD13035 JOHNSON CONTROLS...
User Interface Control Center TABLE 6-2 - SIMPLICITY ELITE DATA MAP Writing to any register not in this list may cause erratic operation INITIAL/ ADDRESS ADDRESS DEFAULT (HEX) (DEC) VALUE (HEX) 00 H 00 L 01 H 01 L 02 H 02 L 03 H 03 L...
Page 131
TABLE - 6-2 - SIMPLICITY ELITE DATA MAP (CONT.) INITIAL/ ADDRESS ADDRESS DEFAULT (HEX) (DEC) VALUE (HEX) 15 L 21 L 16 H 22 H 16 L 22 L 17 L 23 H 17 H 23 L JOHNSON CONTROLS VALUE VALUE 1 = W2 ON (HEATING 2ND STAGE) 1 = W3 ON (HEATING 3RD STAGE)
Page 132
User Interface Control Center TABLE - 6-2 - SIMPLICITY ELITE DATA MAP (CONT.) INITIAL/ ADDRESS ADDRESS DEFAULT (HEX) (DEC) VALUE (HEX) 18 H 24 H 18 L 24 L 19 H 25 H 19 L 25 L 1A H 26 H VALUE VALUE 1 = ADDRESS / DOWN BUTTON PRESSED...
Page 133
TABLE - 6-2 - SIMPLICITY ELITE DATA MAP (CONT.) INITIAL/ ADDRESS ADDRESS DEFAULT (HEX) (DEC) VALUE (HEX) 1A L 26 L 1B H 27 H 1B L 27 L 1C H 28 H 1C L 28 L 1D H 29 H 1D L 29 L 1E H...
Page 134
User Interface Control Center TABLE - 6-2 - SIMPLICITY ELITE DATA MAP (CONT.) INITIAL/ ADDRESS ADDRESS DEFAULT (HEX) (DEC) VALUE (HEX) 1F H 31 H 1F L 31 L 20 H 32 H 20 L 32 L 21 H 33 H 21 L 33 L 22 H...
Page 135
TABLE - 6-2 - SIMPLICITY ELITE DATA MAP (CONT.) INITIAL/ ADDRESS ADDRESS DEFAULT (HEX) (DEC) VALUE (HEX) 43 L 67 L 44 H 68 H 44 L 68 L 45 H 69 H 45 L 69 L 46 H 70 H 46 L 70 L 47 H...
Page 136
User Interface Control Center TABLE - 6-2 - SIMPLICITY ELITE DATA MAP (CONT.) INITIAL/ ADDRESS ADDRESS DEFAULT (HEX) (DEC) VALUE (HEX) 113 H 71 H - 73 L - 115 L 116 H 74 H - 76L - 118 L 119 H 77 H - 79 L - 121 L...
Page 137
TABLE - 6-2 - SIMPLICITY ELITE DATA MAP (CONT.) INITIAL/ ADDRESS ADDRESS DEFAULT (HEX) (DEC) VALUE (HEX) A4 H 164 H A4 L 164 L A5 L 165 L A6 L 166 L A7 L 167 L A8 H 168 H A8 L 168 L A9 H...
Page 138
User Interface Control Center TABLE - 6-2 - SIMPLICITY ELITE DATA MAP (CONT.) INITIAL/ ADDRESS ADDRESS DEFAULT (HEX) (DEC) VALUE (HEX) B4 H 180 H B5 H 181 H B5 L 181 L B6 H 182 H B7 H 183 H B7 L 183 L B8 H...
Page 139
TABLE - 6-2 - SIMPLICITY ELITE DATA MAP (CONT.) INITIAL/ ADDRESS ADDRESS DEFAULT (HEX) (DEC) VALUE (HEX) C6 H 198 H C6 L 198 L C7 H 199 H C7 L 199 L C8 H 200 H C8 L 200 L C9 H 201 H C9 L...
Page 140
User Interface Control Center TABLE - 6-2 - SIMPLICITY ELITE DATA MAP (CONT.) INITIAL/ ADDRESS ADDRESS DEFAULT (HEX) (DEC) VALUE (HEX) 215 L D8 H 216 H D8 L 216 L D9 H 217 H D9 L 217 L DB H 219 H DB L 219 L...
SECTION 7 – PARAMETER DESCRIPTIONS AND OPTIONS TABLE 7-1 – DEFINITIONS MENU ITEM ACCUMULATED UNOCCUPIED OVERRIDE TIME ACTIVE ALARM ADDRESS APS DATA BUILDING PRESSURE SETPOINT BUILDING STATIC PRESSURE BUILDING STATIC PRESSURE SENSOR INSTALLED COMFORT VENTILATION FOR COOLING ENABLED COMFORT VENTILATION FOR HEATING ENABLED COMFORT VENTILATION LOWER SETPOINT COMFORT VENTILATION UPPER SETPOINT...
Page 142
Parameter Description and Options TABLE 7-1 – DEFINITIONS (CONTINUED) MENU ITEM COMP 2 OUTPUT COMP 2 OVERLOAD SWITCH COMP 3 ASCD ACTIVE COMP 3 ASCD TIMER COMP 3 MIN RUN TIME COMP 3 OUTPUT COMP 3 OVERLOAD SWITCH COMP 4 ASCD ACTIVE COMP 4 ASCD TIMER COMP 4 MIN RUN TIME COMP 4 OUTPUT...
Page 143
TABLE 7-1 – DEFINITIONS (CONTINUED) MENU ITEM COOL FAN OFF DELAY COOL FAN ON DELAY COOLING MODE OPERATION ENABLE COOL 1 (Y1) COOL 2 (Y2) COOL 3 (Y3) COOL 4 (Y4) CURRENT BUS ADDRESS CV CURRENT OPERATING COOLING SETPOINT CV CURRENT OPERATING HEATING SETPOINT CV OCCUPIED COOLING SET POINT CV OCCUPIED HEATING SET POINT CV UNOCCUPIED COOLING SET POINT...
Page 144
Parameter Description and Options TABLE 7-1 – DEFINITIONS (CONTINUED) MENU ITEM DIRTY FILTER SWITCH INSTALLED DUCT PRESSURE SETPOINT DUCT PRESSURE SHUTDOWN SETPOINT DUCT STATIC READING ECONOMIZER DAMPER OUTPUT STATUS ECONOMIZER DAMPER POSITION FOR EXHAUST TURN OFF ECONOMIZER DAMPER POSITION FOR EXHAUST TURN ON ECONOMIZER FIRST STAGE SETPOINT ECONOMIZER INSTALLED...
Page 145
TABLE 7-1 – DEFINITIONS (CONTINUED) MENU ITEM ERV UNOCCUPIED FAN ENABLE EXHAUST DAMPER POSITION FOR EXHAUST TO TURN OFF EXHAUST DAMPER POSITION FOR EXHAUST TO TURN ON EXHAUST FAN OUTPUT EXHAUST DAMPER / VFD OUTPUT STATUS EXHAUST VFD INSTALLED FAN (G) THERMOSTAT INPUT FAN ASD TIMER FAN OFF DELAY TIMER FOR COOL FAN OFF DELAY TIMER FOR HEAT...
Page 146
Parameter Description and Options TABLE 7-1 – DEFINITIONS (CONTINUED) MENU ITEM HEAT 1 MIN RUN TIMER HEAT 2 (W2) HEAT 2 ASCD TIMER HEAT 2 MIN RUN TIMER HEAT 3 (W3) HEAT 3 ASCD TIMER HEAT 3 MIN RUN TIMER HEAT FAN OFF DELAY HEAT FAN ON DELAY HEATING MODE ENABLED FOR OPERATION...
Page 147
TABLE 7-1 – DEFINITIONS (CONTINUED) MENU ITEM HSP1 HSP2 HSP3 HSP4 HYDRONIC HEAT ACTUATOR VALVE REVERSE ACTING HYDRONIC HEATING ENABLED HYDRONIC HEATING STAGE #1 SUPPLY AIR SETPOINT HYDRONIC HEATING STAGE #2 SUPPLY AIR SETPOINT IAQ SENSOR RANGE IAQ SETPOINT INDOOR FAN (G) INDOOR FAN MIN RUN TIME INDOOR FAN OUTPUT INDOOR FAN VFD OUTPUT...
Page 148
Parameter Description and Options TABLE 7-1 – DEFINITIONS (CONTINUED) MENU ITEM INTELLI-START OPERATION ENABLE LAST ALARM 1 LAST ALARM 2 LAST ALARM 3 LAST ALARM 4 LAST ALARM 5 LEAD-LAG EQUALIZE COMPRESSOR RUN TIME ENABLED LIMIT SWITCH #1 LIMIT SWITCH #2 LIMIT SWITCH #3 LOADSHED LOW AC SUPPLY VOLTAGE DETECTED...
Page 149
TABLE 7-1 – DEFINITIONS (CONTINUED) MENU ITEM LPS3 LPS4 MAXIMUM IAQ ECONOMIZER POSITION METER OF UNOCCUPIED OVERRIDE ENABLED METRIC OPERATION MINIMUM RUN TIME FOR COMPRESSORS MINUTE MODULATING POWER EXHAUST INSTALLED MONTH MORNING WARM-UP / VAV RETURN AIR TEMP SETPOINT MORNING WARM-UP ENABLE NETWORK OCCUPIED FLAG OCC INPUT OCCUPIED INPUT ENABLED...
Page 150
Parameter Description and Options TABLE 7-1 – DEFINITIONS (CONTINUED) MENU ITEM OUTSIDE AIR HUMIDITY OUTSIDE AIR HUMIDITY SENSOR INSTALLED OUTSIDE AIR TEMP POWER EXHAUST INSTALLED PRE-OCCUPANCY PURGE ENABLE PRE-OCCUPANCY PURGE TIME (HOURS OF DAY) PRE-OCCUPANCY PURGE TIME (MINUTES OF DAY) PURGE SWITCH REDLINE REMOTE CONTROL INPUT ENABLE FOR THIRD...
Page 151
TABLE 7-1 – DEFINITIONS (CONTINUED) MENU ITEM SPACE SENSOR DETECTED SPACE SENSOR FAULT OVERRIDE ENABLE SPACE TEMP SPACE TEMP TRENDING ALARM TEMP SPACE TEMP TRENDING ALARM TIME SPACE TEMPERATURE OFFSET RANGE STAGES OF HEAT AVAILABLE STATE COMPRESSOR OFF - LOW SUPPLY VOLTAGE STATE COMPRESSORS OFF - LOW AMBIENT TEMPERATURE...
Page 152
Parameter Description and Options TABLE 7-1 – DEFINITIONS (CONTINUED) MENU ITEM SUPPLY AIR TEMP LIMIT FOR COOLING ENABLE SUPPLY AIR TEMP LIMIT FOR HEATING ENABLED SUPPLY AIR TEMP LIMIT HEATING SETPOINT TEMPERATURE/HUMIDITY (RETURN) CONTROL ENABLED THIRD PARTY BAS ECONOMIZER ENABLED TURN OFF CONTINUOUS FAN WHEN STARTING HEAT UNIT MODEL NUMBER...
ANALOG INPUT OPERATION This section describes the control operation of the (29) twenty-nine analog inputs. These inputs are used by the control to monitor and respond to unit temperatures, pressures, enthalpy, etc. The location of each of these connections on the Unit Controller is contained in Table 8-8.
The Discharge Transducer has a range of 0 to 650 PSIG, with a linear output of 0 to 5 DC volts. Table 8-5 illustrates the DC volt output from the transducer for a given discharge pressure. Suction Pressure Transducer The optional suction pressure transducer is located in the common suction line of the tandem compressors for each refrigerant circuit.
Service Sensor Two CO sensors are used in conjunction with the “DEMAND VENTILATION” option. In “DEMAND VENTILATION” the Unit Control monitors the CO of the outdoor air and the CO level in the conditioned space and varies the amount of ventilation air based on the relationship between these two values.
TERMINALS FIG. 8-1 – CONNECTOR LOCATIONS TABLE 8-8 – WIRING DATA CONNECTOR # TYPE JOHNSON CONTROLS TERM 24VAC IDENTIFICATION WIRE # DESCRIPTION BUILDING PRESSURE INPUT - BUILDING PRESSURE INPUT + CV/VAV CV VAV CONFIGURATION RESISTOR DUCT STATIC PRESSURE INPUT - DUCT STATIC PRESSURE INPUT + DEMAND VENTILATION INPUT - DEAMND VENTILATION INPUT +...
Page 158
Service TABLE 8-8 – WIRING DATA (CONTINUED) CONNECTOR # TYPE COMM COMM COMM TERMINAL TERMINAL TERMINAL TERMINAL IDENTIFICATION WIRE # DESCRIPTION EXD+ EXHAUST FAN VFD / DAMPER OUTPUT+ HGR- NOT USED HGR+ NOT USED HWV- HOT WATER VALVE OUTPUT - HWV+ HOT WATER VALVE OUTPUT + VFD-...
Page 159
TABLE 8-8 – WIRING DATA (CONTINUED) CONNECTOR # TYPE TERMINAL TERMINAL TERMINAL FIELD INPUT FIELD INPUT FIELD INPUT FIELD INPUT FIELD INPUT FIELD INPUT FIELD INPUT FIELD INPUT FIELD INPUT FIELD INPUT FIELD INPUT FIELD INPUT FIELD INPUT FIELD INPUT FIELD INPUT FIELD INPUT FIELD INPUT...
Service LIGHT EMITTING DIODE The light emitting diode (LED) installed on the Unit Controller is used to indicate the functionality of the Unit Controller and the unit. Normal operation is indicated by the LED fl ashing ON and OFF at a rate of one-second.
TABLE 8-9 – ALARM CODE DESCRIPTIONS ALARM CODE COMPRESSOR SYSTEM 1 (COMPRESSORS 1A, 1B) LOCKED OUT ON HIGH PRESSURE CONTROL. THE CIRCUIT OPENED THREE TIMES WITHIN A 2-HOUR WINDOW. COMPRESSOR SYSTEM 1 (COMPRESSORS 1A, 1B) LOCKED OUT ON HIGH PRESSURE CONTROL. THE CIRCUIT OPENED THREE TIMES WITHIN A 2-HOUR WINDOW.
Page 162
Service TABLE 8-9 – ALARM CODE DESCRIPTIONS (CONTINUED) ALARM CODE THE SUPPLY FAN BINARY OUTPUT HAS BEEN TURNED ON FOR 90 SECONDS AND THE AIR PROVING SWITCH CIRCUIT HAS NOT CLOSED. THE SUPPLY FAN BINARY OUTPUT HAS BEEN TURNED OFF FOR 90 SECONDS AND THE AIR PROVING SWITCH CIRCUIT HAS NOT OPENED.
ALARM TROUBLE SHOOTING Refrigerant System Alarm Codes (01, 02, 03, 04, 09, 10, 11, 12) The first 12 alarms involve controls intended to protect the compressors. Each compressor system is equipped with external circuitry monitoring hardware intended to protect the compressor in case the operating characteristics of the refrigerant system fall outside the safe operating envelope for the compressor.
Service 24 VAC power is supplied to the compressor protection module for compressor 2A from wire 443 at terminal C30 of the P12 connector. The binary input back to the Unit Controller from the compressor protection module is wire 442 at terminal C30 of the P12 connector. 24 VAC power is supplied to the compressor protection module for compressor 2B from wire 445 at terminal C40 of the P12 connector.
Supply Air Temperature Sensor Alarm (20) This alarm indicates the supply air temperature input is either open or shorted. The display will show a value of –40.0° F. The supply air temperature input is at SAT+ and SAT- of the P11 connector. To trouble shoot compare the resistance of the input to the actual supply air temperature using Table 8-1.
Service Outdoor Humidity Sensor Alarm (29) This alarm indicates the outdoor humidity sensor is out of range. When this occurs the Unit Controller will switch economizer operation to Dry Bulb. The Outdoor Humidity analog input is at OH+ wire 333 of the P6 connector and OH- wire 334 of the P6 connector.
Supply Air Temperature Cooling Alarm (38) The Unit Controller compares the supply air temperature to the “SUPPLY AIR TEMP ALARM FOR COOLING” and initiates the alarm based on the following criteria: • All the stages of cooling have been on for 10 or more minutes.