7.5.2 Relay outputs 1 to 8

Free programmable relays for low voltages (max. 30 V DC / 2A).
The relay mode can be configured via a jumper to >positive switching/monitoring< or >dry contact<.
Example with Relay 7
Terminal card
30
29
28
27
Fig. 40: Schematic wiring of the dry contact mode – position of jumpers
Example with Relay 7
The cable to the external connected device is monitored in this operation mode.
Terminal card
Monitoring
(Current measurement)
30
Fig. 41: Schematic wiring of the t "positive switching/monitoring" mode – position of jumpers
FB 798955.GB0 / 09.07
dry contact (Relay terminal card type Phoenix)
positive switching/monitoring (Relay terminal card Type Phoenix)
24V DC
29
28
27
R*
Extinguishing Control Computer 8010 – 19-Inch
Power supply and relay board
Power supply and relay board
Jumper for relay 7 in Pos. „monitoring"
REL 7
dry
contact
moni-
toring
F6
REL 7
dry
contact
moni-
toring
F6