General; Accessories / Options - Honeywell ESSER 8010 Operation And Installation Instructions Manual

Extinguishing control computer
Hide thumbs Also See for ESSER 8010:
Table of Contents

Advertisement

Extinguishing Control Computer 8010 – 19-Inch
1

General

The Extinguishing Control Computer 8010 – 19-inch a fire alarm control panel with an integrated controller for
use in extinguishing systems and provides the connection of automatic fire detectors and Manual call points.
With a total of eight automatic detector zones and 30 connectable automatic fire detectors for each zone, it is
possible to monitor a single extinguishing area as defined by the VdS Guideline 2496.
In addition, five permanently assigned inputs are available for connecting technical zones of units, for example
the manual detector zone or the Emergency Stop zone. The required control functions can be realized with the
total of 13 programmable relay outputs.
A maximum of 100 additional outputs could be realised by using the optional esserbus
The Extinguishing Control Computer 8010 can be directly connected to the analog loop of the fire alarm system
8000 / IQ8Control via the esserbus
Control Computers can be operated on one loop with other loop devices, e.g. fire detectors or esserbus
transponders. This enables up to eight individual extinguishing areas to be monitored via one analog loop.
The Extinguishing Control Computer 8010 - 19-Inch is programmed with the programming software LKDE from
version V02.00 or higher.
Any operation on the installed fire alarm system must only be carried out by authorised personal in
accordance with relevant safety procedures and in coordination with the emergency services.
VdS compliant fire alarm systems must be designed in accordance with VdS guidelines.
Additional and updated Informations
The described features, specifications and product related informations in this manual correspond to
the date of issue (refer to date on the front page) and may differ due to modifications and/or
amended Standards and Regulations of the System design, Installation and Commissioning.
Updated
documentations
www.esser-systems.de homepage.
®
esserbus
and essernet
LED Indicator description
LED lights up
continuously
1.1

Accessories / Options

Part. No.
Type
788014.GB
Extinguishing Control Computer 8010 series 3 – 19-inch design with operating panel (3HE)
Extinguishing Control Computer 8010 series 3 – 19-inch design without operating panel (3HE)
788015
788024.GB
Extinguishing Control Computer 8010 series 2 – 19-inch design with operating panel (3HE)
788025
Extinguishing Control Computer 8010 series 2 – 19-inch design without operating panel (3HE)
788653
Terminal card for C-mounting rail incl. 50-pole D-SUB cable, length 1m
Terminal card for C-mounting rail incl. 50-pole D-SUB cable, length 2m
788654
808615
esserbus
4
®
communication transponder (Part No 808615). Up to eight Extinguishing
and
informations
®
are registered trademarks in Germany.
LED flashes
®
communication transponder
®
are
available
for
LED flashes yellow / red
transponders.
®
comparison
on
the
FB 798955.GB0 / 09.07

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

788010788011788012788013788024788025 ... Show all