Honeywell ESSER 8010 Operation And Installation Instructions Manual page 40

Extinguishing control computer
Hide thumbs Also See for ESSER 8010:
Table of Contents

Advertisement

Extinguishing Control Computer 8010 – 19-Inch
F1
Fuse 4 A, voltage supply of the zone board + 12 V DC / GND
Primary fuse T 1A /H 250 V
F2
J9
jumper open:
jumper closed:
X1
Secondary transformer, 24 V DC, voltage supply of the zone board
X2
Mains connection terminals 230 V AC (L1, N, PE), 50 Hz
Max. cable cross section of the mains supply cable1.5 mm
X3
Plug for the ribbon cable to the power supply unit and relay board
X4
Plug-in contact for protective connection to the metal housing rear wall
X5
Primary transformer 230 V AC, transformer voltage supply
X16
64-pole terminal strip for connecting to the processor board
Programming: esserbus
Monitored detector zone to connect automatic fire detectors and
series 9200 technical alarm modules as well as esserbus
Detector zone-
transponders. (No End-of-line-resistor required)
No. 1 to 8
Programming: Standard detector zone:
Conventional zone to connect external dry contacts
Manual alarm
Terminal for manual call points (manual detector zone)
Emergency Stop Terminal for push-button controls Emergency Stop zone
Extra release
Terminal for push-button control (post-flooding zone)
Failure
Terminal, e.g. for a release system or manual contact to monitor
extinguishing
the extinguishing system
system
Blocking
Terminal for a manual contact (e.g. shut-off cock in the pipe
network)
Monitored control inputs
MG 14, MG 15
MG14
MG15
For mains voltage and protective earth connection, refer to the instructions in the chapter "Mains
connection and earthing".
40
Earth fault identification off
Earth fault identification on (factory setting)
®
zone
Control input >Buzzer off<
Control input >Reset<
2
Device with integrated
®
isolator required
End-of-line resistor
4.7k Ω normal/
1k Ω alarm
End-of-line resistor
10k Ω normal /
1k Ω alarm