Extinguishing Control Computer 8010 – 19-Inch
11
Specification
Main voltage
Rated frequency
Rated current
Supply voltage
for external devices
Battery capacity
Battery charging voltage
Ambient conditions
Ambient temperature
Storage temperature
Protection type
Protection rating
Housing
Colour
Weight
Dimensions (W x H x D):
VdS approval
CE certificate
Alarm zone inputs 1 to 8
Technical zones
Relay contacts
Relays 1 to 8
Relays 9 to 11
Relays 12 and 13
72
:
230 V AC
:
50 Hz
:
0,7 A
:
24 V DC
:
2 x 12 V / 12 Ah
:
13.65 V DC @ 25 °C
:
class 3k5 in accordance to DIN EN 60721-3-3
:
-5 °C to +45 °C
:
-10 °C to +50 °C
:
I in accordance to DIN EN 60950-1
:
IP 30
:
Sheet steel
:
Light grey, similar RAL 7035 / blue, similar RAL 5003
:
approx. 10,1 kg (without rechargeable battery)
:
483 x 132 x 403 (mm), without handle bars
:
G 200090 (series 2), G 205064 (series 3)
:
0786 – CPD - 20223
®
:
esserbus
zone:
Monitored detector zone for connecting automatic fire detectors and
series 9200 technical alarm modules, as well as esserbus
Do not connect an End-of-line resistor
Standard zone:
To connect external dry contacts
End-of-line resistor (4,7k Ω normal / 1k Ω alarm)
:
Monitored detector zone to connect series 9000 manual call points and/or
dry contacts
End-of-line resistor (10k Ω normal / 1k Ω alarm)
:
Changeover contacts, max. 30 V DC / 2 A
Operating mode dry contact or positive-switching / monitoring can be
selected via jumpers (factory setting = monitored)
:
Changeover contacts, max. 30 V DC / 2 A
Programmable, relays 10 and 11 with selectable function
>Emergency Operation Trouble< and >Emergency Operation Fire<
:
Dry contact (NO), max. 230 V AC / 2 A
suitable to switch AC Mains voltage
®
transponders.
FB 798955.GB0 / 09.07