Extinguishing Control Computer 8010 – 19-Inch
2.7

Revision mode

The Extinguishing Control Computer 8010 can be switched to the revision mode via the function keys on the
operating panel.
Unlocked
In operation
The revision mode display has priority over the test mode. If an alarm zone is for example in test
mode and the revision mode is switched on in addition, the state of the >Test mode< LED changes
from ON to flashing.
In the deactivated revision mode the >Test mode< LED lits continuously.
Example: Revision mode
In operation
Extinguishing system
activated
Extinguishing system
enabled
Test operation
Emergency release
Switching off
Test operation
Extra releasing 1
Outputs
Alarm
Fig. 13: Indication and Operation – switching on revision mode
Selecting the revision mode activates all outputs programmed with the status function >Revision<. All outputs of
the Extinguishing Control Computer remain activated until the revision mode is deactivated.
Example: Revision mode
In operation
Extinguishing system
activated
Extinguishing system
enabled
Test operation
Emergency release
Switching off
Test operation
Extra releasing 1
Outputs
Alarm
Fig. 14: Indication and Operation – switching off revision mode
Zones and outputs which are disconnected or out of order will not send an alarm in the event of a fire!
16
For operation, it is necessary to enable the keypad via the key-switch.
switching on
In operation
Extinguishing system
activated
Extinguishing system
enabled
On
Emergency release
Switching off
Test operation
Extra releasing 1
Outputs
Alarm
switching off
In operation
Extinguishing system
activated
Extinguishing system
enabled
Emergency release
Switching off
Test operation
Extra releasing 1
Outputs
Alarm
In operation
Extinguishing system
activated
Extinguishing system
enabled
Off
Emergency release
Switching off
Test operation
Extra releasing 1
Outputs
Alarm