ECP200 STEPPER ELECTRONIC BOARD FOR STEPPER VALVE CONTROL User manual ENGLISH READ AND KEEP Software Rel.: 1 REV. 01-21 ELECTRICAL BOARDS FOR REFRIGERATING INSTALLATIONS...
ECP200 STEPPER TABLE OF CONTENTS INTRODUCTION CHAP. 1 Page 4 General information Page 5 Product identification codes TECHNICAL SPECIFICATIONS CHAP. 2 Page 6 2.1 Technical characteristics Page 7 2.2 Warranty conditions DATA PROGRAMMING CHAP. 3 Page 8 Control panel Page 8...
Page 4
CHAPTER 1: INTRODUCTION GENERAL INFORMATION DESCRIPTION: The ECP200 STEPPER is a cell control electronic board for the management of refrigeration systems with integrated control of the motorised electronic expansion valve and consent for motorised condensing units. It allows the complete management of all the components present in a refrigeration system, such as the compressor, EEV Stepper, evaporator fans, defrosting resistors, cell light and thermostat-controlled door anti-fog resistance.
Page 5
Chap. 1 - Introduction ECP200 STEPPER RS485 for connection to the TeleNET supervision network or to a network with Modbus-RTU protocol. Parameter import / export via USB. Software upgradeable via USB. Cell light activation with key on the panel or via Door switch.
Page 6
Chap. 2 - Technical specifications ECP200 STEPPER CHAPTER 2: TECHNICAL SPECIFICATIONS TECHNICAL SPECIFICATIONS Electronic board power supply 12-24 Vac 10% 50-60Hz Voltage 12-24 Vdc Maximum power consumption Maximum absorption allowed 1,5W (With all loads connected) General Features Temperature probes: NTC 10K 1%...
Pego S.r.l. declines all responsibility for possible inaccuracies contained in this manual, if due to printing or transcription errors. Pego S.r.l. reserves the right to make any changes to its products that it deems necessary or useful, without affecting their essential characteristics.
Chap. 3 - Data programming ECP200 STEPPER DOWN / DEFROST Pressed for more than 3 seconds activates manual defrost (if the activation conditions are met). Pressed for more than 3 seconds during defrosting, it ends the present defrosting. ...
Chap. 3 - Data programming ECP200 STEPPER KEY COMBINATIONS 1ST-LEVEL PROGRAMMING If pressed simultaneously for more than 3 seconds, they allow access to the first level programming menu. LEAVING THE PROGRAMMING If pressed simultaneously for more than 3 seconds within any programming menu.
Chap. 3 - Data programming ECP200 STEPPER FIRST LEVEL PROGRAMMING (User level) To access the first-level configuration menu you must: 1. Press simultaneously and hold for more than 3 seconds the ( ) and ( ) keys until the first programming variable appears on the display.
Chap. 3 - Data programming ECP200 STEPPER 2ND-LEVEL PROGRAMMING (Installer level) To access the second programming level you must: 1. Press and hold the UP ( ), DOWN ( ), and CELL LIGHT keys for more than 3 seconds.
Page 14
Chap. 3 - Data programming ECP200 STEPPER Auxiliary relay temperature setting -45 ÷ +99°C 17 = tPF % fixed opening (N.O.) 16 = Compressor protection, display only (N.O., EcA) 15 = Condenser fan protection, display only (N.O., EFc) 14 = Evaporator fan protection, display only (N.O., EFE) 13 = Oil pressure switch protection (N.O., EcO)
Page 15
Chap. 3 - Data programming ECP200 STEPPER -7 (NO) = DO5 relay energised by the solenoid valve control -6 (NC) = Relay de-energised in standby -5 (NC) = Contact for sump resistance command (AUX relay closed if compressor output not active).
Page 16
Chap. 3 - Data programming ECP200 STEPPER 3RD-LEVEL PROGRAMMING (EEV PARAMETERS) 3.10 To access the third programming level you must: 1. Press and hold the UP ( ) and STAND-BY keys for more than 3 seconds. 2. Select with the ( ) key or the ( ) key the variable to be modified.
Page 17
ECP200 STEPPER 0 = NTC Type of temperature transducer (S4): sets the type of 1 = PT1000 transducer used to detect the temperature (S4) 2 = PTC (-45/80 °C) Pressure (bar) corresponding to 4mA or 0V referred to -1.0 ÷ EP2 bar the evaporation pressure probe (S5).
ECP200 STEPPER threshold (minimum saturated evaporation temperature referred to sensor S5). Represents the minimum evaporation pressure, expressed in saturated degrees, below which -45°C ÷ (MOP-1) -45°C the LOP protection is activated. In case of LPO the control opens the valve to prevent the compressor from stopping due to low pressure (mechanical pressure switch).
Page 19
Chap. 3 - Data programming ECP200 STEPPER 4TH-LEVEL PROGRAMMING (STEPPER VALVE PARAMETERS) 3.13 To access the fourth programming level press and hold the SET and STANDBY keys for more than 3 seconds. When the first programming variable appears, the system automatically switches to standby.
Chap. 3 - Data programming ECP200 STEPPER Closing steps. Number of additional steps to achieve the complete closing of the valve, it is used to realign the valve to the physical HSP ÷ 999 position of fully closed. Driver and valve are then ready for adjustment and both aligned to 0 (zero).
Chap. 3 - Data programming ECP200 STEPPER REFRIGERATION FLUID TEMPERATURE TABLE 3.15 The following table shows the evaporation temperature limits (tS5, see ch. 5.15) according to the type of refrigeration fluid set (ErE parameter). Parameter Temperature Temperature Encoding ErE parameter...
Chap. 3 - Data programming ECP200 STEPPER THERMOSTAT OPERATING MODE 3.18 COLD CALL MODE The COMPR. output is activated when the temperature measured by the Ambient probe reaches or exceeds the SET-POINT value +r0 and remains active until the temperature drops below the SET-POINT.
5) Appropriately connect the electronic valve (see Appendix A2 and A4) with the control off. 6) Turn on the ECP200 STEPPER control. When switched on, after an initialization phase (“ini” is displayed and the valve is completely closed) the control starts adjusting the cell and the overheating temperature.
Chap.4 - Options ECP200 STEPPER CHAPTER 4: OPTIONS TELENET MONITORING/SUPERVISION SYSTEM To insert the panel into a TeleNET network, follow the diagram below. Refer to the TeleNET manual for instrument configuration. IMPORTANT: During configuration under the “Module” option select the item "ECP200EEV instrument“.
CHAPTER 5: DIAGNOSTICS DIAGNOSTICS The ECP200 STEPPER controller warns the operator in case of any anomalies through the alarm codes displayed on the display and an audible signal emitted by a buzzer (if present). The audible alarm is silenced by pressing the UP key (the error code remains) and is reactivated by pressing the SET key.
Page 26
Chap. 5 - Diagnostics ECP200 STEPPER • Check the compressor status. • Check the compressor protection oil Compressor oil pressure switch protection insertion: the outputs are all deactivated except for pressure switch. • If the problem persists, contact technical the alarm one, if present.
Attachments ECP200 STEPPER ATTACHMENTS CONNECTION DIAGRAM DIGITAL INPUTS 2) Digital input 1 (Door switch) 4) Digital input 3 (Man in cell alarm) 3) Digital input 2 (Compressor protection) 12) Digital input 4 11) GND (common digital inputs 1 and 2)
Attachments ECP200 STEPPER VALVE CONNECTION Valve (par. tEU) PIN 1A PIN 2A PIN 2B PIN 1B 1 = Carel EXV GREEN BROWN YELLOW WHITE 2 = Danfoss ETS 25-50 GREEN WHITE BLACK 3 = Danfoss ETS 100 GREEN WHITE BLACK...