Ipm Continuity Check; Fan Motor - Carrier 38MHRC Service Manual

Outdoor unit single zone ductless system sizes 09 to 24
Hide thumbs Also See for 38MHRC:
Table of Contents

Advertisement

DIAGNOSIS AND SOLUTION (CONT)

IPM Continuity Check

Turn the power off, let the large capacity electrolytic capacitors discharge completely, then dismount the IPM. Use a digital tester to measure the
resistance between P and UVWN; UVW and N.
DIGITAL TESTER
(+)Red
(-)Black
N
U
P
V
W

Fan Motor

Measure the resistance value of each winding by using the tester.
MODEL
Brand
Black – Red (Main)
Blue –Black (AUX)
48
Table 18 — IPM Continuity Check
NORMAL RESISTANCE
VALUE
(Several MΩ)
Table 19 — Fan Motor
YKT-32-6-202L
Tongde
Ω
86
Ω
64
Specifications subject to change without notice.
DIGITAL TESTER
(+)Red
(-)Black
U
V
N
W
(+)Red
YKT-32-6-3L
YKT-48-6-206
Welling
Welling
213
152
156
142
NORMAL RESISTANCE
VALUE
(Several MΩ)
YKT-63-6-200L
Welling
88.5
138
SG-38MHRC-01