DIAGNOSIS AND SOLUTION (CONT)
Over voltage or too low voltage protection diagnosis and solution (P1)
Description: An abnormal voltage rise or drop is detected by checking the specified voltage detection circuit.
Possible causes:
• Power supply problems
• System leak or block
• Faulty PCB
Troubleshooting
Check the power supply.
Check the connections and wires.
Check the voltage between P and N.
Replace the reactor.
NOTE: Measure the DC voltage between the P and N port. The normal value should be around 310V.
44
Yes
Yes
Yes
Check the reactor.
Yes
Fig. 48 — Test
Specifications subject to change without notice.
Stop the unit.
No
Correct the connections or
No
replace the wires.
No
Replace the IPM board.
No
Replace the outdoor main PCB.