Table 3-2 Internal Environment Standard Of The Rack - Huawei OceanStor S2600 Routine Maintenance

Hide thumbs Also See for OceanStor S2600:
Table of Contents

Advertisement

OceanStor S2600 Storage System
Routine Maintenance
Reference Standard
The checking items mainly include the layout of the power cables and the pasting of the service
cable labels. The specific checking items are shown in

Table 3-2 Internal environment standard of the rack

Serial
Numb
er
1
2
3
4
5
6
7
8
9
10
11
Procedure
l
Issue 01 (2009-09-27)
Checking Item
General layout of
cables
Layout of the power
cables
Layout of the service
cables
Labeling and pasting
of cables
Free slots
Connector of the
power cables
Connector of the
signal cables
Grounding cables
Power cables
Service network port
connection
Serial port
connection
Check that the force electricity cables and weak electricity cables are respectively laid from
the two sides of the cabinet. That means the separation of the service cables and power
cables.
Huawei Proprietary and Confidential
Copyright © Huawei Technologies Co., Ltd.
3 On-Site Routine Maintenance Guide
Table
Remarks
The force electricity cables and weak electricity cables
should be respectively laid from the two sides of the
cabinet. That means the separation of the service cables and
power cables.
Keep them orderly and neat. Be consistent with the layout
style of other cables in the machine room.
Keep them orderly and neat. Be consistent with the layout
style of other cables in the machine room.
The handwriting on the labels is clear and the contents are
accurate. Labels are firmly pasted on cables.
The free slots must be covered by filler panels to ensure the
heat dissipation of the device and the neat appearance.
The power cables are firmly inserted into the power
sockets.
The cables of the device are firmly connected.
The grounding cables of the disk enclosure are connected
to the grounding clips of the disk enclosure and the
grounding connectors of the cabinet, and the screws of the
clips are fastened.
The power cables are connected to the power supply of the
disk enclosure in redundancy mode (two groups of cables).
The service network cables are normally connected to the
service network port and the host port or the switch.
The serial port cannot be connected to the network switch.
3-2.
3-3

Advertisement

Table of Contents
loading