Communication; Connection Via Ups-Oct; Fig. 11 Example Of A Connection Via Ups-Oct With A Cu8130-0120 Ups And A Cx5240 Embedded Pc - Beckhoff CU8130-0120 Manual

Uninterruptible power supply (battery-backed)
Table of Contents

Advertisement

6.3

Communication

There are several ways to communicate with the UPS, for example to query the status or to control the
device state until shutdown.
The following options are available:
• Protocol-based communication via UPS-OCT (One Cable Technology) or USB.
• Digital signals for communication with non-protocol-capable end devices.
• TwinCAT PLC function blocks for querying the UPS operation.
The configuration and diagnosis of the UPS-OCT or USB communication method is carried out via the
Beckhoff UPS software on Windows 7 or Windows 10.
6.3.1

Connection via UPS-OCT

A special feature of the Beckhoff CU8130-0120 UPS is OCT (One Cable Technology) as a communication
technology between UPS and Industrial PC. The two connection cables (+24 V, 0 V) between the Industrial
PC and the UPS are used to supply power to the Industrial PC and for bidirectional, modulated data
transmission.
Fig. 11: Example of a connection via UPS-OCT with a CU8130-0120 UPS and a CX5240 Embedded PC.
Only the U1out interface of the UPS supports UPS-OCT communication. If you wish to use the UPS-OCT
technology, you must ensure that the Industrial PC supports UPS-OCT. You can use the U1out interface to
retrieve status data for diagnostic purposes or to configure the UPS.
CU8130-0120
Version: 1.0
Commissioning
21

Advertisement

Table of Contents
loading

This manual is also suitable for:

Cu8110-0120

Table of Contents