Exhaust Transition Assembly; Exhaust Duct Connection Requirements - Seeley Climate Wizard CW-H10 Installation & Operation Manual

Indirect evaporative cooler
Hide thumbs Also See for Climate Wizard CW-H10:
Table of Contents

Advertisement

INSTALLATION

EXHAUST TRANSITION ASSEMBLY

The exhaust transition is supplied in knock-down form and its
components are to be found beneath the lid of the cooler and
inside the component kit.
1. Lift the large top panel and locate;
2 x EXHAUST SIDE RAILS (1176mm Long)
2 x EXHAUST GRILLE
2 x EXHAUST CAPS (CW-H15S Plus Only)
2. Fit the EXHAUST SIDE RAILS to the inside vertical faces
of the large top panel with the supplied 10 x SCREW PAN
PHILLIPS 8AB*1/2" SS. Ensure the foam seal faces down.
3. Fit the supplied 3 x PLASTIC GROMMET SIZE 14 to the
rear lid panel upstand square holes.
4. Fit the supplied 2 x PLASTIC GROMMET SIZE 14 to the
EXHAUST CENTRE POST.
5. Position the large top panel over the top of the cooler, with
the rear u-channel over the top of the upstand, the side rails
sitting on the tops of the cooler side walls and the end posts
sitting on the outside of the front tray.
ILL2427-A
ILL2427-A
ILL2428-A
ILL2428-A
ILL2429-A
ILL2429-A
ILL2428-A
6. Slip the 2 x EXHAUST GRILLE and 1 x EXHAUST CENTRE
POST into position, retained inside the top panel front
u-channel.
CW-H15S Plus ONLY: Before fitting to the cooler, slide an
EXHAUST CAP over the back of each EXHAUST GRILLE.
The EXHAUST CAP covers the top portion of the EXHAUST
GRILLE, and is designed to optimise the CW-H15S Supercool
performance.
7. Screw the exhaust transition assembly to the cooler body
with the supplied 11 x SCREW SEMS HEX 14 x 3/4" ZP.
3 x Rear Upstand, 3 x Left Side, 3 x Right Side, 2 x Centre
Post.
8. Fit the supplied 4 x M6 x 35MM SET SCREW, STAINLESS
STEEL FLAT WASHER, NYLON FLAT WASHER to the tops
of both core access doors. Apply a liberal coat of anti-seize
paste to the screw thread prior to fitment.

EXHAUST DUCT CONNECTION REQUIREMENTS

If required, the exhaust discharge opening may be ducted away
from the cooler. When designing the exhaust duct please note
the following;
• The exhaust air is warm and heavily laden with moisture.
Ensure the exhaust opening is located and oriented in such a
way as to avoid exhaust air re-entering the cooler inlet.
• Access to the heat exchanger cores requires the removal of
the cooler lid/exhaust transition. Ensure any additional ducting
is readily removable and/or lightweight.
• Where an installation requires extended exhaust ducts, the
increase in static load should not exceed 20 Pa (0.08 in wg).