Upgrading or Downgrading the Firmware
The Firmware on the IPSDU8 can be upgraded or downgraded as required using a compatible
Firmware Update Package (FUP) provided by American Dynamics.
Procedure 3-22 Upgrading/Downgrading the Firmware
1 Complete Procedure 3-20 to back up the current configuration settings.
2 Ensure that the browser is displaying the Front Page (if not refer to Procedure 3-1).
3 Select the UPDATE FIRMWARE button.
The Firmware Upgrade page is displayed, as shown in Figure 3-18.
4 Enter the name of the FUP (including network path) to be used, or select Browse... and use
the file browser to locate and select the FUP.
5 Select Update Firmware.
The Firmware Update Progress page is displayed, as shown in Figure 3-19.
Figure 3-18 Firmware Upgrade page
Web Configuration