Rockwell Automation Reliance Electric MD65 User Manual

Rockwell Automation Reliance Electric MD65 User Manual

Ac drive
Hide thumbs Also See for Reliance Electric MD65:
Table of Contents

Advertisement

sales@artisantg.com
artisantg.com
(217) 352-9330 |
|
Click HERE
Find the ABB / Baldor / Reliance 6MDEN-6P6102 at our website:

Advertisement

Table of Contents
loading

Summary of Contents for Rockwell Automation Reliance Electric MD65

  • Page 1 sales@artisantg.com artisantg.com (217) 352-9330 | Click HERE Find the ABB / Baldor / Reliance 6MDEN-6P6102 at our website:...
  • Page 2 MD65 AC Drive User Manual Version 2.0 Instruction Manual D2-3519-2...
  • Page 3 AC supply, or excessive ambient temperatures may result in malfunction of the system. MD65, VS Utilities, and Reliance are trademarks of Rockwell Automation. Trademarks not belonging to Rockwell Automation are property of their respective companies. ©2004 Rockwell Automation. All rights reserved.
  • Page 4: Table Of Contents

    ONTENTS Chapter 1 Introduction 1.1 Getting Assistance from Reliance Electric..... 1-1 Chapter 2 About the MD65 Drive 2.1 Identifying the Drive by Model Number......2-1 2.2 MD65 Drive Ratings, Model Numbers, and Frame Sizes ..............2-2 2.3 Kits and Accessories ............. 2-3 2.4 Storage Guidelines ............
  • Page 5 6.4.2 Typical Multiple Drive Connection Examples..6-9 6.5 Start and Speed Reference Control......6-10 6.6 Accel/Decel Selection ..........6-11 Chapter 7 Completing the Installation 7.1 Checking the Installation Before Applying Power to the Drive ............7-1 7.2 Powering Up After Installation is Complete....7-2 Chapter 8 Using the Integral Keypad to Program and Control the Drive 8.1 Keypad Components .............
  • Page 6 Appendix B Record of User Settings ............B-1 Appendix C Parameters Cross-Referenced by Name ......C-1 Appendix D CE Conformance Requirements .........D-1 Appendix E Accessories................E-1 Appendix F RS485 (MDI) Protocol ............F-1 Appendix G RJ45 Splitter Cable ............G-1 Appendix H StepLogic , Basic Logic and Time/Counter Functions ..H-1 Appendix I PID Setup................
  • Page 7 MD60 AC Drive User Manual...
  • Page 8 List of Figures Figure 2.1 – Identifying the Drive by Model Number........2-1 Figure 3.1 – Minimum Mounting Clearances ..........3-2 Figure 3.2 – Drive Dimensions and Weights..........3-3 Figure 3.3 – Drive Dimensions - NEMA 1/IP30 Kit Without Communication Option ............3-4 Figure 3.4 –...
  • Page 9 MD65 AC Drive User Manual...
  • Page 10 List of Tables Table 2.1 – Drive Ratings, Model Numbers, and Frame Sizes....2-2 Table 2.2 – Standard Kits and Accessories ..........2-3 Table 3.1 – Ambient Operating Temperatures and Mounting Clearances................3-2 Table 3.2 – Mounting Specifications ............3-6 Table 5.1 – Corrective Actions for Input Power Conditions ......5-4 Table 5.2 –...
  • Page 11 VIII MD65 AC Drive User Manual...
  • Page 12: Chapter 1 Introduction

    HAPTER Introduction This manual is intended for qualified electrical personnel familiar with installing, programming, and maintaining AC drives. This manual contains information on: • Installing and wiring the MD65 drive • Programming the drive • Troubleshooting the drive The latest version of this manual is available from http://www.theautomationbookstore.com or http://www.reliance.com/docs_onl/online_stdrv.htm.
  • Page 13 MD65 AC Drive User Manual...
  • Page 14: Chapter 2 About The Md65 Drive

    HAPTER About the MD65 Drive This chapter provides general information about the MD65 AC drive, including how to identify the drive. 2.1 Identifying the Drive by Model Number Each drive can be identified by its model number, as shown in figure 2.1.
  • Page 15: Md65 Drive Ratings, Model Numbers, And Frame Sizes

    2.2 MD65 Drive Ratings, Model Numbers, and Frame Sizes Similar MD65 drive sizes are grouped into frame sizes to simplify re-ordering and dimensioning. Refer to figures 3.2 through 3.4 for the dimensions of each frame size. Table 2.1 provides MD65 drive ratings, model numbers, and frame sizes.
  • Page 16: Kits And Accessories

    Table 2.1 – Drive Ratings, Model Numbers, and Frame Sizes (Continued) Drive Ratings Output Model Number Frame Input Voltage Current Size 600V 50/60 Hz 0.75 1.7 A 6MDEN-1P7102 3-Phase 3.0 A 6MDEN-3P0102 No Filter 4.2 A 6MDEN-4P2102 6.6 A 6MDEN-6P6102 9.9 A 6MDEN-9P9102 10.0...
  • Page 17: Storage Guidelines

    Table 2.2 – Standard Kits and Accessories (Continued) Kit Description Model Number Remote Handheld OIM (digital speed control, MD1CC full numeric keypad, CopyCat capable, IP30 (NEMA Type 1); includes 1.0 meter cable; panel-mount with optional Bezel Kit. Bezel Kit (panel mount for Remote Handheld MDBZL-N1 OIM) OIM Cable (1.0 meter OIM-to-RJ45 cable)
  • Page 18: Chapter 3 Mounting The Drive

    HAPTER Mounting the Drive This chapter provides information that must be considered when planning an MD65 drive installation and provides drive mounting information and installation site requirements. ATTENTION: Only qualified electrical personnel familiar with the construction and operation of this equipment and the hazards involved should install, adjust, operate, or service this equipment.
  • Page 19: Operating Conditions

    3.1.1 Operating Conditions Before deciding on an installation site, consider the following guidelines: • Protect the cooling fan by avoiding dust or metallic particles. • Do not expose the drive to a corrosive atmosphere. • Protect the drive from moisture and direct sunlight. •...
  • Page 20: Mounting Dimensions For The Md65 Drive

    3.1.3 Mounting Dimensions for the MD65 Drive Overall dimensions and weights are illustrated in figures 3.2, 3.3, and 3.4 as an aid to calculating the total area required by the MD65 drive. Dimensions are in millimeters and (inches). Weights are in kilograms and (pounds).
  • Page 21: Figure 3.3 - Drive Dimensions - Nema 1/Ip30 Kit Without

    79.1 (3.11) 64.1 (2.52) 40.6 (1.60) 25.6 (1.01) ∅ 22.2 (0.87) (8.39) 109.9 (4.33) 74.3 (2.93) 33.0 (1.30) Side View Bottom View Frame B 107.0 (4.21) ∅ 28.5 (1.12) 66.0 (2.60) 24.0 (0.94) ∅ 22.2 (0.87) (12.56) 152.2 (5.99) 111.2 (4.38) 60.0 (2.36)
  • Page 22: Figure 3.4 - Drive Dimensions - Nema 1/Ip30 Kit With

    25.0 (0.98) 77.5 (3.05) 50.0 (1.97) 22.5 (0.89) ∅ 22.2 (0.87) (9.61) 134.3 (5.29) 105.3 (4.15) 76.3 64.0 (3.00) (2.52) Side View Bottom VIew Frame B 25.0 (0.98) 108.7 (4.28) 92.2 (3.63) 69.2 (2.72) ∅ 28.5 45.7 (1.80) (1.12) 22.2 (0.87) ∅...
  • Page 23: Mounting The Drive

    3.2 Mounting the Drive Mount the drive upright on a flat, vertical, and level surface. Table 3.2 – Mounting Specifications Frame Screw Size Screw Torque -OR- DIN Rail M4 (#8-32) 1.56-1.96 N-m (14-17 in-lb) 35 mm M5 (#10-24) 2.45-2.94 N-m (22-26 in-lb) –...
  • Page 24: Chapter 4 Grounding The Drive

    HAPTER Grounding the Drive ATTENTION: The following information is merely a guide for proper installation. Rockwell Automation cannot assume responsibility for the compliance or the noncompliance to any code, national, local or otherwise for the proper installation of this drive or associated equipment.
  • Page 25: Rfi Filter Grounding

    Safety Ground - (PE) This is the safety ground for the drive that is required by code. One of these points must be connected to adjacent building steel (girder, joist), a floor ground rod, or bus bar. Grounding points must comply with national and local industrial safety regulations and/or electrical codes.
  • Page 26: Chapter 5 Installing Power Wiring

    HAPTER Installing Power Wiring ATTENTION: The user is responsible for conforming with all applicable local and national codes. Failure to observe this precaution could result in damage to, or destruction of, the equipment. ATTENTION: To avoid a possible shock hazard caused by induced voltages, unused wires in the conduit must be grounded at both ends.
  • Page 27: Verifying Drive Ac Input Ratings Match Available Power

    Step 2. Remove the finger guard (refer to figure 5.2). a. Press in and hold the locking tab. b. Slide finger guard down and out. Replace the finger guard and cover when wiring is complete. Figure 5.2 – Removing the Finger Guard 5.2 Verifying Drive AC Input Ratings Match Available Power It is important to verity that plant power meets the input power...
  • Page 28: Figure 5.3 - Removing The Jumper

    Disconnecting MOVs To disconnect MOVs, you must remove the external jumper located on the lower left side of the front of the drive. To remove the jumper, use the following procedure and refer to figures 5.3 and 5.4. Step 1. Open the cover.
  • Page 29: Input Power Conditioning

    5.2.2 Input Power Conditioning The drive is suitable for direct connection to input power within the rated voltage of the drive (see table 5.4). Table 5.1 lists certain input power conditions that may cause component damage or reduction in product life. If any of the conditions exist, install one of the devices listed in the “Corrective Action”...
  • Page 30: Power Terminal Block Connections

    5.4 Power Terminal Block Connections Table 5.3 – Power Terminal Block Specifications Frame Maximum Wire Size Minimum Wire Size Torque 1.7-2.2 Nm 5.3 mm (10 AWG) 1.3 mm (16 AWG) (16-19 in-lb) 2.9-3.7 Nm 8.4 mm (8 AWG) 1.3 mm (16 AWG) (26-33 in-lb) Maximum/minimum sizes that the terminal block will accept.
  • Page 31: Fuses And Circuit Breakers

    5.5 Fuses and Circuit Breakers The MD65 drive does not provide branch short circuit protection. This product should be installed with either input fuses or an input circuit breaker. National and local industrial safety regulations and/ or electrical codes may determine additional requirements for these installations.
  • Page 32: Table 5.4 - Drive, Fuse, And Circuit Breaker Ratings

    Table 5.4 – Drive, Fuse, and Circuit Breaker Ratings Drive Ratings Branch Circuit Power Output Ratings Input Ratings Protection Dissipation Model Circuit Number Voltage Breaker IP20 Open kW (HP) Amps Range kVA Amps Fuses Watts 100 - 120V AC 1-Phase Input, 0 - 230V 3-Phase Output 6MDVN-2P3102 0.4 (0.5) 90-132...
  • Page 33 Fuse ratings are the recommended values for use with each drive rating. Recommended fuse type: UL Class J, CC, T or Type BS88; 600 V (550 V) or equivalent. Circuit breaker ratings are the recommended values for use with each drive rating.
  • Page 34: Table 5.5 - Shielded Motor Cable Types Acceptable For 200-600 Volt Installations

    Shielded cable may also help reduce shaft voltage and induced bearing currents for some applications. In addition, the increased impedance of shielded cable may help extend the distance that the motor can be located from the drive without the addition of motor protective devices such as terminator networks.
  • Page 35: Reflected Wave Protection

    Table 5.5 – Shielded Motor Cable Types Acceptable for 200-600 Volt Installations Location Rating/Type Description Class I & Tray rated 600V, • Three bare copper conductors with 90°C (194°F) RHH/ XLPE insulation with impervious Division I RHW-2 corrugated continuously welded &...
  • Page 36: Chapter 6 Installing Control Wiring

    HAPTER Installing Control Wiring This chapter describes how to wire the signal and I/O terminal strip for stop, speed feedback, and remote control signals. To access the control terminal block, remove the drive cover (refer to chapter 5). Terminal block connections are detailed in figure 6.1. 6.1 Stop Circuit Requirements ATTENTION: You must provide an external, hardwired emergency stop circuit outside of the...
  • Page 37: Motor Start/Stop Precautions

    6.2 Motor Start/Stop Precautions ATTENTION: A contactor or other device that routinely disconnects and reapplies the AC line to the drive to start and stop the motor can cause drive hardware damage. The drive is designed to use control input signals that will start and stop the motor. If used, the input device must not exceed one operation per minute or drive damage can occur.
  • Page 38: I/O Wiring Recommendations

    6.3 I/O Wiring Recommendations Table 6.1 – Recommended Control and Signal Wire Minimum Insulation Wire Type(s) Description Rating Belden 8760/ 300 V 0.8 mm (18AWG), twisted pair, 100% 9460 (or equiv.) 75° C shield with drain. (167° F) Belden 8770 0.8 mm (18AWG), 3 conductor, (or equiv.)
  • Page 39: Wiring The Control Terminal Block

    6.4 Wiring the Control Terminal Block Enable Typical Typical Jumper (1)(4) SRC Wiring SNK Wiring Stop Start/Run FWD Direction/Run REV Digital Common Digital Input 1 Digital Input 2 Digital Input 3 Digital Input 4 Opto Common +24V +24V DC +10V +10V DC 0-10V (or ±10V) Input Analog Common...
  • Page 40: Table 6.3 - Control Terminal Definitions And Related Parameters

    Table 6.3 – Control Terminal Definitions and Related Parameters No. Signal Default Description Parameter Relay N.O. Fault Normally open contact for output relay. A055 Relay Common – Common for output relay. Relay N.C. Fault Normally closed contact for output relay. A055 Analog Output Select DIP Sets analog output to either voltage or current.
  • Page 41: I/O Wiring Examples

    6.4.1 I/O Wiring Examples Input/Output Connection Example Potentiometer P038 (Speed Reference) = 2 “0-10V Input” 1-10k Ohm Pot. Recommended (2 Watt minimum) Analog Input Bipolar Unipolar (Voltage) Unipolar (Current) 0 to +10V, 100k ohm P038 (Speed P038 (Speed P038 (Speed impedance Reference) = 2 “0-10V Reference) = 2 “0-10V...
  • Page 42 Input/Output Connection Example 2-Wire SNK Control - Internal Supply (SNK) Non-Reversing Stop-Run 2-Wire SRC Control - Internal Supply (SRC) External Supply (SRC) Run FWD/Run REV P036 (Start Source) = 2, 3 or 4 Stop-Run Stop-Run Input must be active for Forward Forward the drive to run.
  • Page 43 Input/Output Connection Example 3-Wire SNK Control - Internal Supply (SNK) Non-Reversing Stop Start 3-Wire SRC Control - Internal Supply (SRC) External Supply (SRC) Reversing P036 (Start Source) = Stop Stop A momentary input will Start Start start the drive. A stop input to I/O Terminal 01 Direction Direction...
  • Page 44: Typical Multiple Drive Connection Examples

    Input/Output Connection Example Analog Output A065 (Analog Out Sel) = 0 through 14 A065 (Analog Out Sel) The Analog Output Select DIP Switch must be set to match the analog output determines analog signal mode set in A065 (Analog Out Sel). output type and drive conditions.
  • Page 45: Start And Speed Reference Control

    6.5 Start and Speed Reference Control The drive speed command can be obtained from a number of different sources. The source is normally determined by P038 (Speed Reference). However, when A051 or A052 (Digital Inx Select) is set to option 2, 4, 5, or 6, and the digital input is active, A051 or A052 will override the speed reference commanded by P038 (Speed Reference).
  • Page 46: Accel/Decel Selection

    6.6 Accel/Decel Selection The selection of Accel/Decel rates can be made through digital inputs, RS485 communications and/or parameters. See figure 6.3. Jog Input Drive will Start and Run Enabled and Active: at Jog Speed. Drive Stopped A051, A052, A053 (Not Running) Drive will use A079 (Jog Accel/Decel) or A054 = 2, 11,12 Either...
  • Page 47 6-12 MD65 AC Drive User Manual...
  • Page 48: Chapter 7 Completing The Installation

    HAPTER Completing the Installation This chapter provides instructions on how to perform a final check of the installation before and after power is applied to the drive. ATTENTION: Only qualified electrical personnel familiar with the construction and operation of this equipment and the hazards involved should start and adjust it.
  • Page 49: Powering Up After Installation Is Complete

    • Verify that the Sink (SNK)/Source (SRC) Setup DIP Switch is set to match your control wiring scheme. See figure 6.1 for the location of this switch. Important: The default control scheme is Source (SRC). The Stop terminal is jumpered (I/O Terminals 01 and 11) to allow starting from the keypad.
  • Page 50: Using The Integral Keypad To Program And Control The Drive

    HAPTER Using the Integral Keypad to Program and Control the Drive Factory-default parameter values allow the drive to be controlled from the integral keypad. No programming is required to start, stop, change direction, or control speed directly from the integral keypad. This chapter provides an overview of the integrated keypad and how to use it to program and control the MD65 drive.
  • Page 51: Display Description

    8.1.1 Display Description The alpha-numeric display indicates the following: • Parameter number • Parameter value • Fault code 8.1.2 LED Descriptions Refer to figure 8.1 for the location of the LEDs described in table 8.1. Table 8.1 – LED Descriptions LED State Description Steady Red Indicates the drive is running.
  • Page 52: Key Descriptions

    8.1.3 Key Descriptions Refer to figure 8.1 for the location of the keys described in table 8.2. Table 8.2 – Key Descriptions Name Description • Program Enter/exit program mode. PROG • Scroll through parameter groups. • Back up one step in programming menu.
  • Page 53: About Parameters

    8.2 About Parameters To program the drive for a specific application, you adjust the appropriate parameters. The parameters are used to define characteristics of the drive. There are three types of parameters: • Numbered List Parameters Numbered list parameters allow a selection from two or more options.
  • Page 54: Viewing And Adjusting Basic (P) And Advanced (A) Parameters

    8.4 Viewing and Adjusting Basic (P) and Advanced (A) Parameters Use the following procedure to view and adjust the Basic and Advanced parameters. Table 8.3 – Viewing and Adjusting Basic (P) and Advanced (A) Parameters Procedure Sample Display VOLTS PROG Step 1.
  • Page 55: Viewing The Display (D) Parameters

    8.5 Viewing the Display (d) Parameters Use the procedure in table 8.4 to view Display parameters. Table 8.4 – Viewing the Display (d) Parameters Procedure Sample Display VOLTS PROG Step 1. Press to scroll through AMPS HERTZ the parameter menus until the PROGRAM FAULT Display Group parameters are...
  • Page 56: Chapter 9 Parameter Descriptions

    HAPTER Parameter Descriptions The following information is provided for each parameter along with its description: Parameter Number: Unique number assigned to each parameter. Parameter Name: Unique name assigned to each parameter. Range: Predefined parameter limits or selections. Default: Factory default setting. See also: Associated parameters that may provide additional or related information.
  • Page 57: Basic Program Group Parameters

    9.1 Basic Program Group Parameters The Basic Program Group contains the most commonly used parameters to simplify the start-up process. P031 Motor NP Volts Range: 20 VAC to Drive Rated Volts Default: Based on Drive Rating See also: d004, A084-A087 Set to the motor nameplate rated volts.
  • Page 58 P036 Start Source Range: 0 = Keypad 1 = 3-Wire 2 = 2-Wire 3 = 2-W Lvl Sens 4 = 2-W Hi Speed 5 = Comm Port 6 = Momt FWD/REV Default: 0 = Keypad See also: d012, P037 Sets the control scheme used to start the drive. Refer to section 6.5, Start and Speed Reference Control, for details about how other drive settings can override the setting of this parameter.
  • Page 59 6 = Momt FWD/REV: Drive will start after a momentary input from either the Run FWD Input (I/O Terminal 02) or the Run REV Input (I/O Terminal 03). I/O Terminal 1 “Stop” = stop according to the value set in Stop Mode (P037). P037 Stop Mode Range: 0 = Ramp, CF...
  • Page 60 4 = Ramp: Ramp to stop. 5 = Coast: Coast to stop. 6 = DC Brake: DC injection braking stop. 7 = DC BrakeAuto: DC injection braking stop with auto shutoff. Standard DC injection braking for the amount of time set in DC Brake Time (A080), or the drive shuts off if current limit is exceeded.
  • Page 61: Figure 9.1 - Accel Time 1 (P039)

    4 = Preset Freq: External frequency command as defined by Preset Freq x (A070-A077) when Digital Inx Sel (A051-A054) are programmed as “Preset Frequencies,” and the digital inputs are active. 5 = Comm Port: External frequency command from the communications port. 6 = Stp Logic: External frequency command as defined by Preset Freq x (A070-A077) and Stp Logic x (A140-A147).
  • Page 62: Figure 9.2 - Decel Time 1 (P040)

    Maximum Frequency / Decel Time = Decel Rate P035 [Maximum Freq] Speed P039 or A067 P040 or A068 Time [Accel Time x] [Decel Time x] Figure 9.2 – Decel Time 1 (P040) P041 Reset To Defalts Range: 0 = Ready/Idle 1 = Factory Rset Default: 0 = Ready/Idle...
  • Page 63: Advanced Group Parameters

    9.2 Advanced Group Parameters A051 Digital In1 Sel (I/O Terminal 05) A052 Digital In2 Sel (I/O Terminal 06) A053 Digital In3 Sel (I/O Terminal 07) A054 Digital In4 Sel (I/O Terminal 08) Range: 0 = Not Used 1 = Acc & Dec 2 2 = Jog 3 = Aux Fault 4 = Preset Freq...
  • Page 64 2 = Jog: When the input is present, the drive accelerates according to the value set in Jog Accel/Decel (A079) and ramps to the value set in Jog Frequency (A078). When the input is removed, the drive ramps to a stop according to the value set in Jog Accel/Decel (A079).
  • Page 65 15 = PID Disable: Disables PID function. Drive uses the next valid non-PID speed reference. 16 = MOP Up: Increases the value of Internal Freq (A069) at a rate of 2 Hz per second. Default for A069 is 60 Hz. 17 = MOP Down: Decreases the value of Internal Freq (A069) at a rate of 2 Hz per second.
  • Page 66 A055 Relay Out Sel Range: 0 = Ready/Fault 1 = At Frequency 2 = MotorRunning 3 = Reverse 4 = Motor Overld 5 = Ramp Reg 6 = Above Freq 7 = Above Cur 8 = Above DCVolt 9 = Retries Exst 10 = Above Anlg V 11 - Logic In 1 12 = Logic In 2...
  • Page 67 8 = Above DCVolt: Drive exceeds the DC bus voltage value set in Relay Output Level (A056). Use A056 to set the threshold. 9 = Retries Exst: Number of retries set in Auto Rstrt Tries (A092) is exhausted. 10 = Above Anlg V: The analog input voltage (I/O Terminal 13) exceeds the value set in Relay Out Level (A056).
  • Page 68: Table 9.1 - Trip Points For Digital Output Relay

    A056 Relay Out Level Range: 0.0 to 9999 (see table 9.1) Default: See also: A055, A058, A061 Sets the trip point for the output relay if the value of Relay Out Sel (A055) is 6, 7, 8, 10, 16, 17, 18, or 20. See table 9.1. Table 9.1 –...
  • Page 69 A058 Opto Out1 Sel A061 Opto Out2 Sel Range: 0 = Ready/Fault 1 = At Frequency 2 = MotorRunning 3 = Reverse 4 = Motor Overld 5 = Ramp Reg 6 = Above Freq 7 = Above Cur 8 = Above DCVolt 9 = Retries Exst 10 = Above Anlg V 11 = Logic In 1...
  • Page 70 Important: The value for A059 or A062 must be entered in percent of drive rated output current. 7 = Above Cur: Drive exceeds the current (% Amps) value set in Opto Outx Level (A059 or A062). Use A059 or A062 to set the threshold.
  • Page 71: Table 9.2 - On/Off Points For The Opto Outputs

    21 = NonRec Fault: Value set in Auto Rstrt Tries (A092) is exceeded, Auto Rstrt Tries (A092) is not enabled, or a non-resettable fault has occurred. 22 = EM Brk Cntrl: EM brake is energized. Program EM Brk Off Delay (A160) and EM Brk On Delay (A161) for desired action. A059 Opto Out1 Level A062...
  • Page 72: Table 9.3 - A064 Options

    Table 9.3 – A064 Options A064 Option Opto Out1 Logic Opto Out2 Logic NO (Normally Open) NO (Normally Open) NC (Normally Closed) NO (Normally Open) NO (Normally Open) NC (Normally Closed) NC (Normally Closed) NC (Normally Closed) A065 Analog Out Sel Range: 0 to 20 Default:...
  • Page 73: Figure 9.3 - Accel Time 2 (A067)

    A066 Analog Out High Range: 0 to 800% Default: 100% See also: A065 Scales the Maximum Output Value for the Analog Out Sel (A065) source setting. For example: A066 Setting A065 Setting A065 Max. Output Value 1 = OutCurr 0-10 5 V for 200% Drive Rated Output Current 8 = OutPowr 0-20 18 mA for 200% Drive Rated Power...
  • Page 74: Figure 9.4 - Decel Time 2 (A068)

    Maximum Frequency / Decel Time = Decel Rate P035 [Maximum Freq] Speed P039 or A067 P040 or A068 Time [Accel Time x] [Decel Time x] Figure 9.4 – Decel Time 2 (A068) A069 Internal Freq Range: 0.0 to 400.0 Hz Default: 0.0 Hz See also:...
  • Page 75: Table 9.5 - Selecting The Reference Source Using Presets

    A070 Preset Freq 0 A0711 Preset Freq 1 A0721 Preset Freq 2 A0731 Preset Freq 3 A0741 Preset Freq 4 A0751 Preset Freq 5 A0761 Preset Freq 6 A0771 Preset Freq 7 Range: 0.0 to 400.0 Hz Default: 0.0 Hz See also: P038, P039, P040, A051-A053, A067, A068, A140-A147, A150-A157...
  • Page 76: Figure 9.5 - Dc Brake Level (A081)

    A079 Jog Accel/Decel Range: 0.1 to 600.0 sec Default: 10.0 sec See also: A051-A054, A078 Sets the acceleration and deceleration time when a jog command is issued. Refer to parameters A051-A054 for information on how to jog the drive. A080 DC Brake Time Range: 0.0 to 99.9 sec (A setting of 99.9 = Continuous) Default:...
  • Page 77: Figure 9.6 - S Curve % (A083) Example

    A082 DB Resistor Sel Range: 0 = Disabled 1 = Normal RA Resistor (5% Duty Cycle) 2 = No Protection (100% Duty Cycle) 3 to 99 = Duty Cycle Limited (3% to 99% Duty Cycle) Default: 0 = Disabled See also: P037 Enables/disables external dynamic braking.
  • Page 78: Figure 9.7 - Boost Select (A084)

    A084 Boost Select Range: 0 = Custom V/Hz Variable Torque (typical fan/pump curves): 1 = 30.0, VT 2 = 35.0, VT 3 = 40.0, VT 4 = 45.0, VT Constant Torque: 5 = 0.0 no IR Compensation 6 = 0.0 7 = 2.5, CT 8 = 5.0, CT 9 = 7.5, CT...
  • Page 79: Figure 9.8 - Start Boost (A085)

    A085 Start Boost Range: 0.0 to 25.0% Default: 5.0% See also: P031, P032, P034, P035, A084, A086, A087, A088, A125 Sets the boost voltage (% of Motor NP Volts (P031)) and redefines the Volts per Hz curve when Boost Select (A084) is set to 0 = Cust V/Hz, and Torque Perf Mode (A125) is set to 0 = V/Hz.
  • Page 80: Figure 9.9 - Motor Ol Select (A090)

    A087 Break Frequency Range: 0.0 to 400.0 Hz Default: 15.0 Hz See also: P031, P032, P034, P035, A084, A085, A086, A088, A125 Sets the frequency where the break frequency is applied when Boost Select (A084) is set to 0 = Custom V/Hz, and Torque Perf Mode (A125) is set to 0 = V/Hz.
  • Page 81: Figure 9.10 - Derating Guidelines Based On Pwm Frequency (A091) Selection

    A091 PWM Frequency Range: 2.0 to 16.0 kHz Default: 4.0 kHz See also: A124 Sets the carrier frequency for the PWM output waveform. Figure 9.10 provides derating guidelines based on the PWM frequency setting. Important: Ignoring derating guidelines can cause reduced drive performance.
  • Page 82 A093 Auto Rstrt Delay Range: 0.0 to 300.0 sec Default: 1.0 sec See also: A092 Sets the time between restart attempts when Auto Rstrt Tries (A092) is set to a value other than zero. Refer to section 10.1.2 for more information on the Auto Restart/Run feature. A094 Start At PowerUp Range: 0 = Disabled...
  • Page 83 A096 Flying Start En Range: 0 = Disabled 1 = Enabled Default: 0 = Disabled See also: Enables/disables feature that allows the drive to reconnect to a spinning motor at actual RPM. ATTENTION: When starting with this feature enabled, the motor may temporarily run up to the maximum speed setting before settling at the speed setpoint.
  • Page 84 Default: 0 = Unlocked See also: When set to 1 = Locked, protects parameters against change by unauthorized personnel. A102 Testpoint Sel Range: 0 to FFFF Default: See also: d019 Used by Rockwell Automation field service personnel. 9-29 Parameter Descriptions...
  • Page 85 A103 Comm Data Rate Range: 0 = 1200 1 = 2400 2 = 4800 3 = 9600 4 = 19.2 K 5 = 38.4 K Default: 4 = 19.2 K See also: d015 Sets the serial port rate for the RS485 port. Important: Power to the drive must be cycled before any changes will affect drive operation.
  • Page 86 A106 Comm Loss Time Range: 0.1 to 60.0 sec Default: 5.0 sec See also: d015, A105 Sets the time that the drive will remain in communication loss before implementing the option selected in Comm Loss Action (A105). A107 Comm Format Range: 0 = RTU 8-N-1 3 = RTU 8-N-2...
  • Page 87: Figure 9.11 - Anlg In 0-10V Lo (A110)

    A109 Anlg Out Setpoint Range: 0.0 to 100% Default: 0.0% See also: A065 Sets the percentage of output desired by the user. If this is enabled via Analog Out Sel (A065), this determines the analog value that is output from the analog output (V or mA). A110 Anlg In 0-10V Lo Range: 0.0 to 100.0%...
  • Page 88 A112 Anlg In4-20mA Lo Range: 0.0 to 100.0% Default: 0.0% See also: d021, P034, P038 Sets the analog input level that corresponds to Minimum Freq (P034) if a 40-20 mA input is used by Speed Reference (P038). Setting this value larger than Anlg In4-20mA Hi (A113) inverts the analog signal.
  • Page 89 A116 Process Time Hi Range: 0.00 to 99.99 Default: 0.00 See also: d010, P035 Scales the time value when the drive is running at Maximum Freq (P035). When set to a value other than zero, Process Display (d010) indicates the duration of the process. A117 Bus Reg Mode Range: 0 = Disabled...
  • Page 90: Figure 9.12 - Skip Freq Band (A120)

    A setting of 0 disables this parameter. Frequency Command Frequency Drive Output Frequency 2x Skip Skip Frequency Frequency Band Time Figure 9.12 – Skip Freq Band (A120) A121 Stall Fault Time Range: 0 = 60 sec 1 = 120 sec 2 = 240 sec 3 = 360 sec 4 = 480 sec...
  • Page 91 Selects the drive action when an input signal loss is detected. Signal loss is defined as an analog signal less than 1 V or 2 mA. The signal loss event ends and normal operation resumes when the input signal level is greater than or equal to 1.5 V or 3 mA. If using a 0-10 V analog input, set Anlg In 0-10V Lo (A110) to a minimum of 20% (i.e., 2 V).
  • Page 92 A125 Torque Perf Mode Range: 0 = V/Hz 1 = Sensrls Vect Default: 1 = Sensrls Vect See also: A084, A085, A086, A087, A127 Enables/disables sensorless vector control operation. A126 Motor NP FLA Range: 0.1 to (Drive Rated Amps x 2) Default: Drive Rated Amps See also:...
  • Page 93 2 = Rotate Tune: A temporary command that initiates a Static Tune followed by a rotational test for the best possible automatic setting of Flux Current Ref (A129). A start command is required following the initiation of this setting. The parameter returns to 0 = Ready/Idle following the test, at which time another start transition is required to operate the drive in normal mode.
  • Page 94 A131 PID Trim Lo Range: 0.0 to 400.0 Default: See also: Sets the minimum positive value that is added to a PID reference when PID trim is used. A132 PID Ref Select Range: 0 = PID Disabled 1 = PID Setpoint 2 = 0-10V Input 3 = 4-20mA Input 4 = Comm Port...
  • Page 95 A135 PID Integ Time Range: 0.0 to 999.9 sec Default: 0.0 sec See also: Sets the value of the PID integral component when the PID mode is enabled by PID Ref Select (A132). A136 PID Diff Rate Range: 0.00 to 99.99 (1/sec) Default: 0.00 (1/sec) See also:...
  • Page 96: Table 9.6 - Related Parameters For Stp Logic Parameters (A140-A147)

    A140 Stp Logic 0 A141 Stp Logic 1 A142 Stp Logic 2 A143 Stp Logic 3 A144 Stp Logic 4 A145 Stp Logic 5 A146 Stp Logic 6 A147 Stp Logic 7 Range: 0001 to bAFF Default: 00F1 See also: P038, P039, Po40, A051-A054, A055, A058, A061, A067, A068, A070-A077, A150-A157 Parameters A140-A147 can be used to create a custom profile of...
  • Page 97 How StepLogic Works The StepLogic sequence begins with a valid start command. A normal sequence always begins with Stp Logic 0 (A140). Digit 0: Logic For Next Step This digit defines the logic for the next step. When the condition is met, the program advances to the next step.
  • Page 98: Figure 9.13 - Digit Settings

    Logic For Next Step Digit 0 Logic to Jump to a Different Step Digit 1 Different Step to Jump Digit 2 Step Settings Digit 3 Digit 3 Settings Required Accel/Decel StepLogic Commanded Setting Param. Used Output State Direction Accel/Decel 1 Accel/Decel 1 Accel/Decel 1 No Output...
  • Page 99: Figure 9.14 - Em Brk Off Delay

    A160 EM Brk Off Delay Range: 0.01 to 10.00 sec Default: 2.0 sec See also: P037 Sets the time the drive remains at minimum frequency before the relay or an opto is energized and the drive ramps to the commanded frequency. The relay or opto is typically connected to a user-supplied electromechanical brake coil relay.
  • Page 100 The relay or opto output is typically connected to a user-supplied electromechanical brake coil relay. Set Stop Mode (P037) to 8 “Ramp+EM B,CF” or 9 “Ramp+EM Brk” to enable the electromechanical brake option. Set Relay Out Sel (A055) and Opto Outx Sel (A058 or A061) to 22 “EM Brk Cntrl”...
  • Page 101: Display Group Parameters

    9.3 Display Group Parameters d001 Output Freq Range: 0.0 to Maximum Freq (P035) Default: Read Only See also: d002, d010, P034, P035, P038 Displays the output frequency present at terminals T1, T2, and T3 (U, V, and W). d002 Commanded Freq Range: 0.0 to Maximum Freq (P035) Default:...
  • Page 102: Figure 9.15 - Drive Status (D006) Bit Definitions

    d005 DC Bus Voltage Range: Based on Drive Rating Default: Read Only See also: Displays the present DC bus voltage level. d006 Drive Status Range: 0 = Condition False 1 = Condition True See figure 9.15 Default: Read Only See also: A095 Displays the present operating status of the drive.
  • Page 103: Figure 9.16 - Control Source (D012) Bit Definitions

    d010 Process Display Range: 0.00 to 9999 Default: Read Only See also: d001, A099 Displays the output frequency scaled by Process Factor (A099). Output Frequency x Process Factor = Process Display d012 Control Source Range: 0 to 9 See figure 9.16. Default: Read Only See also:...
  • Page 104: Figure 9.17 - Contrl In Status (D013) Bit Definitions

    d013 Contrl In Status Range: 0 = Input Present 1 = Input Not Present See figure 9.17 Default: Read Only See also: d002, P034, P035 Displays the status of the control terminal block control inputs. Important: Actual control commands may come from a source other than the control terminal block.
  • Page 105: Figure 9.19 - Comm Status (D015) Bit Definitions

    Displays the Main Control Board software version. d017 Drive Type Range: 1001 to 9999 Default: Read Only See also: Used by Rockwell Automation field service personnel. d018 Elapsed Run Time Range: 0 to 9999 Hours Default: Read Only See also: Displays the accumulated time drive is outputting power.
  • Page 106 d019 Testpoint Data Range: 0 to FFFF Default: Read Only See also: A102 Displays the present value of the function selected in Testpoint Select (A102). d020 Analog In 0-10V Range: 0.0 to 100.0% Default: Read Only See also: A110, A111 Displays the present value of the voltage at I/O Terminal 13 (100.0% = 10 V).
  • Page 107 d024 Drive Temp Range: 0 to 120 degree C Default: Read Only See also: Displays the present operating temperature of the drive power section. d025 Counter Status Range: 0 to 9999 Default: Read Only See also: Displays the current value of the counter when the counter is enabled.
  • Page 108: Chapter 10 Troubleshooting The Drive

    HAPTER Troubleshooting the Drive ATTENTION: The drive contains high voltage capacitors that take time to discharge after removal of mains supply. Before working on the drive, ensure isolation of mains supply from line inputs [R, S, T (L1, L2, L3)]. Wait three (3) minutes for capacitors to discharge to safe voltage levels.
  • Page 109: Manually Clearing Faults

    10.1.1 Manually Clearing Faults Step 1. Note the number of the fault code flashing on the display. Step 2. Address the condition that caused the fault. Refer to table 10.1 for a description of the fault and corrective actions. The cause must be corrected before the fault can be cleared.
  • Page 110: Table 10.1 - Fault Descriptions And Corrective Actions

    Table 10.1 – Fault Descriptions and Corrective Actions Fault Description Action • Auxiliary Y Auxiliary input interlock Check remote wiring. Input is open. • Verify communications programming for intentional fault. • Power Loss N DC bus voltage Monitor the incoming remained below 85% AC line for low voltage of nominal.
  • Page 111 Table 10.1 – Fault Descriptions and Corrective Actions (Continued) Fault Description Action • Heatsink Y Heatsink temperature Check for blocked or OverTemp exceeds a predefined dirty heat sink fins. value. Verify that ambient temperature has not exceeded 40°C (104°F) for IP 30/NEMA 1/UL Type 1 installations or 50°C (122°F) for Open type installations.
  • Page 112 Table 10.1 – Fault Descriptions and Corrective Actions (Continued) Fault Description Action • Phase UV N Excessive current has Check the motor and drive output terminal Short been detected wiring for a shorted between these two Phase UW condition. output terminals. Short •...
  • Page 113 Table 10.1 – Fault Descriptions and Corrective Actions (Continued) Fault Description Action F100 Parameter N The checksum read Set Reset to Defalts Checksum from the board does (P041) to 1 = Reset not match the Defaults. checksum calculated. F122 I/O Board Fail N Failure has been •...
  • Page 114: Troubleshooting Tables

    10.2 Troubleshooting Tables Use the following tables to troubleshoot the drive. If you cannot resolve the problem using these tables, contact Reliance Electric. 10.2.1 Problem: Drive Does Not Start From Terminal Block Start or Run Inputs Table 10.2 – Problem: Drive Does Not Start From Terminal Block Start or Run Inputs Possible Cause(s) Indication Corrective Action...
  • Page 115: Problem: Drive Does Not Start From Integral Keypad

    10.2.2 Problem: Drive Does Not Start From Integral Keypad Table 10.3 – Problem: Drive Does Not Start From Integral Keypad Cause(s) Indication Corrective Action • Integral keypad is not Start Key Set Start Source (P036) enabled. Status LED is to 0 = Keypad. not on.
  • Page 116: Problem: Motor Does Not Start

    10.2.4 Problem: Motor Does Not Start Cause(s) Indication Corrective Action No output voltage to the None Check the power circuit. motor. • Check the supply voltage. • Check all the fuses and disconnects. Check the motor. • Verify that the motor is connected properly.
  • Page 117: Problem: Motor And/Or Drive Will Not Accelerate To Commanded Speed

    10.2.5 Problem: Motor and/or Drive Will Not Accelerate to Commanded Speed Table 10.5 – Problem: Motor and/or Drive Will Not Accelerate to Commanded Speed Cause(s) Indication Corrective Action Acceleration time is None Reprogram P039 (Accel Time excessive. 1) or A067 (Accel Time 2). •...
  • Page 118: Problem: Drive Will Not Reverse Motor

    10.2.7 Problem: Drive Will Not Reverse Motor Direction. Table 10.7 – Problem: Drive Will Not Reverse Motor Direction Cause(s) Indication Corrective Action Digital input is not selected None Check Digital Inx Sel. Choose for reversing control. correct input and program for reversing mode.
  • Page 119 10-12 MD65 AC Drive User Manual...
  • Page 120: Appendix A Technical Specifications

    PPENDIX Technical Specifications Environment Altitude: 1000 m (3300 ft) maximum without derating Ambient Operating Open Type, IP 20: -10° C (14° F) to 50° C (122° F) Temperature: NEMA 1, IP30, UL Type 1: -10° C (14° F) to 40° C (104°...
  • Page 121 Accel/Decel: Two independently programmable accel and decel times. Each time may be programmed from 0-600 seconds in 0.1 second increments. Intermittent • 150% Overload capability for up to 1 minute. Overload: • 200% Overload capacity for up to 3 seconds Electronic Motor Class 10 protection with speed-sensitive response.
  • Page 122 Protective Features Motor Protection: Programmable I t overload protection provides Class 10 protection. See parameter P033. Overcurrent: 200% hardware limit, 300% instantaneous fault Over Voltage: • 100-120 V AC Input – Trip occurs at 405 V DC bus voltage (equivalent to 150 V AC incoming line •...
  • Page 123 MD65 AC Drive User Manual...
  • Page 124 PPENDIX Record of User Settings B.1 Basic Parameter Group Default Page Parameter Name Value User Setting P031 Motor NP Volts Varies P032 Motor NP Hertz 60 Hz P033 Motor OL Current Varies P034 Minimum Freq 0.0 Hz P035 Maximum Freq 60 Hz P036 Start Source 0 = Keypad...
  • Page 125 B.2 Advanced Parameter Group Default Page Parameter Name Value User Setting A051 Digital In1 Sel 4 = Preset Freq A052 Digital In2 Sel 4 = Preset Freq A053 Digital In3 Sel 4 = Preset Freq A054 Digital In4 Sel 5 = Local A055 Relay Out Sel 0 = Ready/Fault 9-11...
  • Page 126 Default Page Parameter Name Value User Setting A084 Boost Select 8 = 5.0, CT 9-23 7 = 2.5, CT (for 5.0, 7.5, and 10.0 HP drives only) A085 Start Boost 5.0% 9-24 A086 Break Voltage 25.0% 9-24 A087 Break Frequency 15.0 Hz 9-25 A088 Maximum Voltage...
  • Page 127 Default Page Parameter Name Value User Setting A115 Process Time Lo 0.00 9-33 A116 Process Time Hi 0.00 9-34 A117 Bus Reg Mode 1 = Enabled 9-34 A118 Current Limit 2 Drive Rated 9-33 Amps x 1.8 A119 Skip Frequency 0 Hz 9-34 A120 Skip Freq Band...
  • Page 128 Default Page Parameter Name Value User Setting A150 Stp Logic Time 0 30.0 sec 9-43 A151 Stp Logic Time 1 30.0 sec 9-43 A152 Stp Logic Time 2 30.0 sec 9-43 A153 Stp Logic Time 3 30.0 sec 9-43 A154 Stp Logic Time 4 30.0 sec 9-43 A155 Stp Logic Time 5...
  • Page 129 MD65 AC Drive User Manual...
  • Page 130 PPENDIX Parameters Cross-Referenced by Name Parameter Default Page Parameter Name Group Value 10V Bipolar Enbl A123 Advanced 0 = Uni-Polar In 9-36 Accel Time 1 P039 Basic 5.0 sec Accel Time 2 A067 Advanced 10.0 sec 9-18 Analog In 0-10V d020 Display Read Only 9-51...
  • Page 131 Parameter Default Page Parameter Name Group Value Comm Loss Action A105 Advanced 0 = Fault 9-30 Comm Loss Time A106 Advanced 5.0 sec 9-31 Comm Node Addr A104 Advanced 9-30 Comm Status d015 Display Read Only 9-50 Commanded Freq d002 Display Read Only 9-46 Compensation...
  • Page 132 Parameter Default Page Parameter Name Group Value Flux Current Ref A129 Advanced Based on Drive 9-38 Rating Flying Start En A096 Advanced 0 = Disabled 9-28 Internal Freq A069 Advanced 0.0 Hz 9-19 IR Voltage Drop A128 Advanced Based on Drive 9-38 Rating Jog Accel/Decel...
  • Page 133 Parameter Default Page Parameter Name Group Value PID Preload A139 Advanced 0.0 Hz 9-40 PID Prop Gain A134 Advanced 0.00 9-39 PID Ref Select A132 Advanced 0 = PID 9-39 Disabled PID Setpoint A137 Advanced 0.0% 9-40 PID Trim Hi A130 Advanced 9-38 PID Trim Lo...
  • Page 134 Parameter Default Page Parameter Name Group Value Stp Logic 0 A140 Advanced 00F1 9-41 Stp Logic 1 A141 Advanced 00F1 9-41 Stp Logic 2 A142 Advanced 00F1 9-41 Stp Logic 3 A143 Advanced 00F1 9-41 Stp Logic 4 A144 Advanced 00F1 9-41 Stp Logic 5...
  • Page 135 MD65 AC Drive User Manual...
  • Page 136 PPENDIX CE Conformance Requirements Conformity with the Low Voltage (LV) Directive and Electromagnetic Compatibility (EMC) Directive has been demonstrated using harmonized European Norm (EN) standards published in the Official Journal of the European Communities. The MD65 AC drive complies with the EN standards listed below when installed according to the User Manual.
  • Page 137 Essential Requirements for CE Compliance The following conditions must be satisfied for MD65 drives to meet the requirements of EN61800-3. • Grounding as described in figure D.1. Refer to chapter 4 for additional grounding recommendations. • Output power, control (I/O) and signal wiring must be braided, shielded cable with a coverage of 75% or better, metal conduit or equivalent attenuation.
  • Page 138 EN61000-3-2 • 0.75 kW (1 HP) 240 V 1-phase and 3-phase drives and 0.37 kW (0.5 HP) 240 V 1-phase drives are suitable for installation on a private low-voltage power network. Installations on a public low-voltage power network may require additional harmonic mitigation.
  • Page 139 MD60 AC Drive User Manual...
  • Page 140 PPENDIX Accessories Appendix E contains information on accessories available with the MD65 AC Drive. This appendix has information on: • Dynamic Brake Modules • EMC Line Filters • Operator Interface Modules (OIMs) Accessories...
  • Page 141 E.1 Dynamic Brake Modules Table E.1 – Dynamic Brake Modules Drive Ratings Min. Input Voltage Resistance Model Number 120V 50/60 Hz AK-R2-091P500 1-Phase 0.75 AK-R2-091P500 AK-R2-091P500 240V 50/60 Hz AK-R2-091P500 1-Phase 0.75 AK-R2-091P500 AK-R2-091P500 AK-R2-047P500 240V 50/60 Hz AK-R2-091P500 3-Phase 0.75 AK-R2-091P500 AK-R2-091P500...
  • Page 142 Frame A Frame B 30.0 61.0 (1.18) (2.40) 17.0 60.0 31.0 59.0 (2.36) (0.67) (1.22) (2.32) 316.0 335.0 386.0 405.0 (12.44) (13.19) (15.20) (15.94) SURFACES MAY BE 13.0 (0.51) Frame Model Number AK-R2-091P500, AK-R2-047P500, AK-R2-360P500 AK-R2-030P1K2, AK-R2-120P1K2 Figure E.1 – Dynamic Brake Modules: Dimensions Accessories...
  • Page 143 E.2 EMC Line Filters Table E.2 – EMC Line Filters Drive Ratings S Type Filter L Type Filter Input Voltage Model Number Model Number 120V 50/60 Hz – 6MDF-018BL 1-Phase 0.75 – 6MDF-018BL – 6MDF-018BL 240V 50/60 Hz 6MDF-018BL 1-Phase 0.75 6MDF-018BL 6MDF-018BL...
  • Page 144 (1.97) (3.94) 29.8 (3.07) (1.17) (8.54) (9.02) (8.50) 17.8 5.5 (0.22) (0.70) 24.0 (0.94) Dimensions are in mm and (in). Model Numbers: 6MDF-012BS, -BL; 6MDF-021BS, -BL; 6MDF-018BS, -BL Figure E.2 – Frame B EMC Line Filters: Dimensions Accessories...
  • Page 145 (2.36) (5.12) (3.54) (1.26) (11.69) (12.17) (11.69) 5.5 (0.22) (0.67) (1.18) Dimensions are in mm and (in). Model Numbers: 6MDF-018CS, -CL; 6MDF-034CS, -CL; 6MDF-025CL Figure E.3 – Frame C EMC Line Filters: Dimensions MD65 AC Drive User Manual...
  • Page 146 E.3 Operator Interface Modules (OIMs) Table E.3 – Operator Interface Modules/Accessories Description Model Number Remote Panel-Mount OIM (digital speed control, MD4LCD-PNL CopyCat capable, IP66 (NEMA 4x12) indoor use only, includes 2.9 meter cable) Remote Handheld OIM (digital speed control, full MD1CC numeric keypad, CopyCat capable, IP30 (NEMA Type 1);...
  • Page 147 17.6 (0.69) (4.09) (8.66) 2.9m (3.07) (2.60) (7.64) (4.92) 60.5 (2.38) 19.1 (1.50) (0.75) (0.19) Dimensions are in mm and (in). Figure E.4 – Remote OIM (M/N MD4LCD-PNL) MD65 AC Drive User Manual...
  • Page 148 11.1 (0.44) (3.66) 25.2 (0.99) (7.09) (2.64) (2.36) (6.06) (0.19) (3.03) 19.1 (0.75) 23.5 (0.93) Dimensions in mm and (in). Figure E.5 – NEMA Type 1 Bezel (M/N MDBZL-N1): Dimensions Accessories...
  • Page 149 E-10 Accessories...
  • Page 150 RS485 (MDI) Protocol MD65 drives support the RS485 (MDI) protocol to allow efficient operation with Rockwell Automation peripherals. In addition, some Modbus functions are supported to allow simple networking. MD65 drives can be multi-dropped on an RS485 network using Modbus protocol in RTU mode.
  • Page 151 Wiring terminations on the master controller will vary depending on the master controller used and “TxRxD+” and “TxRxD-” are shown for illustration purposes only. Refer to the master controller’s user manual for network terminations. Note that there is no standard for the “+”...
  • Page 152 Supported Modbus Function Codes The peripheral interface (MDI) used on MD65 drives supports some of the Modbus function codes. Table F.2 – Supported Modbus Function Codes Modbus Function Code Command Read Holding Registers Preset (Write) Single Register Important: Modbus devices can be 0-based (registers are numbered starting at 0) or 1-based (registers are numbered starting at 1).
  • Page 153 Writing (06) Logic Command Data The MD65 drive can be controlled via the network by sending Function Code 06 writes to register address 8192 (Logic Command). P036 (Start Source) must be set to 5 “RS485 (MDI) Port” in order to accept the commands. Table F.3 –...
  • Page 154 Writing (06) Reference The Speed Reference to a MD65 drive can be controlled via the network by sending Function Code 06 writes to register address 8193 (Reference). P038 (Speed Reference) must be set to 5 “RS485 (MDI) Port” in order to accept the Speed Reference. Table F.4 –...
  • Page 155 Reading (03) Feedback The Feedback (Output Frequency) from the MD65 drive can be read via the network by sending Function Code 03 reads to register address 8451 (Feedback). Table F.6 – Feedback Feedback Address (Decimal) Description A xxx.x decimal value where the decimal point is fixed. For 8451 example, a decimal “123”...
  • Page 156 Reading (03) Drive Error Codes The MD65 Error Code data can be read via the network by sending Function Code 03 reads to register address 8449 (Drive Error Codes). Table F.7 – Error Codes Logic Status Address Value (Decimal) (Decimal) Description No Fault Auxiliary Input...
  • Page 157 Reading (03) and Writing (06) Drive Parameters To access drive parameters, the Modbus register address equals the parameter number. For example, a decimal “1” is used to address parameter d001 (Output Freq) and decimal “39” is used to address parameter P039 (Accel Time 1). MD65 AC Drive User Manual...
  • Page 158 PPENDIX RJ45 Splitter Cable The MD65 drive provides a RJ45 port to allow the connection of a single peripheral device. The RJ45 Splitter Cable can be used to connect a second MDI peripheral device to the drive. Connectivity Guidelines ATTENTION: The peripherals may not perform as intended if these Connectivity Guidelines are not followed.
  • Page 159 Cable Accessories Slave Port Master Port PIN 1 PIN 8 Figure G.1 – RJ45 Splitter Cable (M/N AK-U0-RJ45-SCI) (PIN 5) PIN 8 (PIN 4) PIN 1 Figure G.2 – RJ45 Two-Position Terminal Block Module M/N AK-U0-RJ45-TB2P PIN 8 PIN 1 Figure G.3 –...
  • Page 160 Connecting One Temporary Peripheral MD65 Drive MD65 Serial Converter Handheld OIM Parameter 1 (Module Cfg) set to "Auto" (default) or "Master" and connected to Master port (M) on RJ45 Splitter Cable Parameter 9 (Device Type) set to "Auto" (default) or "Master" and connected to Master port (M) on RJ45 Splitter Cable Figure G.4 –...
  • Page 161 Connecting Two Permanent Peripherals NEMA 1 Bezel NEMA 4 with Handheld OIM Panel Mount OIM MD65 Drive Parameter 9 (Device Type) set to "Master" and connected to Master port (M) on RJ45 Splitter Cable Parameter 9 (Device Type) set to "Slave" and connected to Slave port (S) on RJ45 Splitter Cable Figure G.6 –...
  • Page 162 PPENDIX StepLogic , Basic Logic and Timer/Counter Functions Four MD65 drive logic functions provide the capability to program simple logic functions without a separate controller. • StepLogic Function Steps through up to eight preset speeds based on programmed logic. Programmed logic can include conditions that need to be met from digital inputs programmed as “Logic In1”...
  • Page 163 level programmed to the desired number of counts. When the counter reaches the count programmed into the output level the output will change state. The counter can be reset via a digital input programmed as “Reset Counter”. StepLogic Using Timed Steps To activate this function, set Speed Reference (P038) to 6 “Stp Logic”.
  • Page 164 StepLogic Using Basic Logic Functions Digital input and digital output parameters can be configured to use logic to transition to the next step. Logic In1 and Logic In2 are defined by programming Digital Inx Sel parameters (A051-A054) to option 23 “Logic In1” or option 24 “Logic In2”. Example •...
  • Page 165 The step time value and the basic logic may be used together to satisfy machine conditions. For instance, the step may need to run for a minimum time period and then use the basic logic to trigger a transition to the next step. Start Step 0 Step 1...
  • Page 166 • Digital In1 Sel (A051) = 4 “Preset Freq” – Digital In2 Sel (A052) = 18 “Timer Start” – Relay Out Sel (A055) = 16 “Timer Out” – Relay Out Level (A056) = 20.0 Sec – Preset Freq 1 (A071) = 30.0 Hz •...
  • Page 167 Counter Function Digital inputs and outputs control the counter function and are configured with Digital Inx Sel parameters (A051-A054) set to 19 “Counter In” and 21 “Reset Counter”. Digital outputs (relay and opto type) define a preset level and indicate when the level is reached. Level parameters Relay Out Level (A056), Opto Out1 Level (A059) and Opto Out2 Level (A062) are used to set the desired count value.
  • Page 168 StepLogic Parameters Table H.1 – Digit 3 – Defines the action during the step currently executing. Digit 3 Digit 2 Digit 1 Digit 0 Table H.2 – Digit 3 – Defines the action during the step currently executing. Accel/Decel StepLogic Setting Parameters Used Output State...
  • Page 169 Table H.4 – Digit 1 – Defines what logic must be met to jump to a step other than the very next step. Setting Description Logic Skip Step (jump immediately) SKIP Step based on the time programmed in the respective [Stp Logic Time x] parameter. TIMED Step if “Logic In1”...
  • Page 170 PPENDIX PID Set Up PID Loop The MD65 has a built-in PID (proportional, integral, differential) control loop. The PID loop is used to maintain a process feedback (such as pressure, flow or tension) at a desired set point. The PID loop works by subtracting the PID feedback from a reference and generating an error value.
  • Page 171 • When the PID Control Loop is disabled, the Commanded Speed is the Ramped Speed Reference. PID Feedback = Pressure Transducer Signal Pump PID Reference = Desired System Pressure Trim Control In Trim Control, the PID Output is added to the Speed Reference. In Trim mode, the output of the PID loop bypasses the accel/decel ramp as shown.
  • Page 172 • As tension increases or decreases during winding, the Speed Reference is trimmed to compensate. Tension is maintained near the Equilibrium set point. 0 Volts PID Reference = PID Feedback = Equilibrium Set Point Dancer Pot Signal 10 Volts Speed Reference PID Reference and Feedback PID Ref Sel (A132) is used to enable the PID mode (A132 does not equal 0;...
  • Page 173 PID Feedback Sel (A133) is used to select the source of the PID feedback. Table I.2 – PID Feedback Sel (A133) Options Option Description 0 “0-10V Input” Selects the 0-10V Input (default setting). Note that the PID will not function with a bipolar analog input. It will ignore any negative voltages and treat them like a zero.
  • Page 174 Invert Function For a 4-20mA signal, the following parameter settings are used so that a 20mA signal = 0% PID Reference and a 4mA signal = 100% PID Reference. • Angl ln 4-20mA Lo (A112) = 100.0% • Anlg In 4-20mA Hi (A113) = 0.0% •...
  • Page 175 PID Preload The value set in PID Preload (A139), in Hertz, will be pre-loaded into the integral component of the PID at any start or enable. This will cause the drive’s frequency command to initially jump to that preload frequency, and the PID loop starts regulating from there. PID Enabled PID Pre-load Value PID Output...
  • Page 176 PID Gains The proportional, integral, and differential gains make up the PID regulator. • PID Prop Gain (A134) The proportional gain (unitless) affects how the regulator reacts to the magnitude of the error. The proportional component of the PID regulator outputs a speed command proportional to the PID error.
  • Page 177 Guidelines for Adjusting the PID Gains 1. Adjust the proportional gain. During this step it may be desirable to disable the integral gain and differential gain by setting them to 0. After a step change in the PID Feedback: – If the response is too slow increase PID Prop Gain (A134). –...
  • Page 178 PID Reference PID Feedback Time Figure I.2 – Slow Response - Over Damped PID Reference PID Feedback Time Figure I.3 – Oscillation - Under Damped PID Reference PID Feedback Time Figure I.4 – Good Response - Critically Damped PID Set Up...
  • Page 179 I-10 PID Set Up...
  • Page 180 NDEX Numerics Comm Data Rate (A103) 9-30 Comm Format (A107) 9-31 10V Bipolar Enbl (A123) 9-36 Comm Loss Action (A105) 9-30 Comm Loss fault 10-5 Comm Loss Time (A106) 9-31 Comm Node Addr (A104) 9-30 Comm Status (d015) 9-50 A parameters 9-34 Commanded Freq (d002) 9-46...
  • Page 181 model numbers Phase VW Short 10-5 mounting Phase W to Gnd 10-4 operating conditions Power Loss 10-3 powering up after installing Power Unit 10-5 ratings SVC Autotune 10-5 storage guidelines SW OverCurrent 10-5 troubleshooting 10-1 10-11 UnderVoltage 10-3 Drive Overload fault 10-5 filter, RFI Drive Status (d006)
  • Page 182 about Advanced 9-34 Maximum Freq (P035) Basic Maximum Voltage (A088) 9-25 cross-referenced by name Minimum Freq (P034) model numbers 9-46 9-51 motor cable length 5-10 descriptions 9-51 motor cable types, 200-600 V Display 9-46 9-51 installations Motor NP FLA (A126) 9-37 record of user settings Motor NP Hertz (P032)
  • Page 183 Program Lock (A101) 9-29 Stp Logic 4 (A144) 9-41 protective features Stp Logic 5 (A145) 9-41 PWM Frequency (A091) 9-26 Stp Logic 6 (A146) 9-41 Stp Logic 7 (A147) 9-41 Stp Logic Status (d028) 9-52 SVC Autotune fault 10-5 SW Current Trip (A098) 9-28 Reflected Wave Protection 5-10...
  • Page 187 U.S. Drives Technical Support Tel: (1) 262.512.8176, Fax: (1) 262.512.2222, Email: support@drives.ra.rockwell.com, Online: www.ab.com/support/abdrives Publication D2-3519-2– April 2004 Copyright © 2004 Rockwell Automation, Inc. All Rights Reserved. Printed in USA.

Table of Contents