Auto Reset; Manual Reset - Banner ES-UA-5A Manual

Emergency stop safety modules
Hide thumbs Also See for ES-UA-5A:
Table of Contents

Advertisement

E-Stop Safety Module
E-Stop Switch
Jumper
L1
Machine
Control
Circuits
Non-safety
Auxiliary Monitor
Contact
+V
Figure 4. Hookup: -Channel E-Stop Applications
WARNING . . .
If arc suppressors are used, they MUST be installed as shown across the actuator coil of the Master Stop Control Elements
(MSC1 to MSC4). NEVER install suppressors directly across the output contacts of the E-Stop Safety Module. It is possible
for suppressors to fail as a short circuit. If installed directly across the output contacts of the Safety Module, a short-circuited suppressor will
create an unsafe condition which could result in serious injury or death.
WARNING . . .
NEVER wire an intermediate device(s) (e.g., PLC, PES, PC), between E-Stop Safety Module outputs and the Master Stop
Control Element it switches in such a manner that in the event of a failure there is the loss of the safety stop command, OR
in such a manner that the safety function can be suspended, overridden, or defeated, unless accomplished with the same or greater
degree of safety.
Whenever forced-guided, mechanically linked relays are added as intermediate switching devices, a normally closed forced-guided monitor
contact from each relay must be added to the series feedback loop between Safety Module terminals S31 and S32.
Buy: www.ValinOnline.com | Phone 844-385-3099 | Email: CustomerService@valin.com
– Models ES-UA-5A and ES-VA-5A

Auto Reset

For power connection
see Figure 6.
ES-UA-5A
12-24V dc/115V ac
ES-VA-5A
S11
12-24V dc/230V ac
S21
MSC1
MSC3
S22
S31
MSC Monitor
S12
Contacts
or Jumper for No
Monitoring
S32
S34
MSC2
MSC4
S33
S32
Machine
Master Stop
S35
Control Elements
6A max.
L2
K1
K2
A
A
13
14
MSC1
*
6A max.
K1
K2
B
B
24
23
MSC2
*
6A max.
K1
K2
C
C
33
34
MSC3
*
6A max.
K1
K2
D
D
43
44
MSC4
*
6A max.
K1
E
*
51
52
Arc Suppressors
(see
below)
WARNING
K2
E
Y30
Y31
Y32
Y35
Outputs
Power Supply
Energized
Fault
12-24V dc
dc common
Wiring of Arc Suppressors
Interfacing MSCs

Manual Reset

For power connection
see Figure 6.
E-Stop Switch
ES-UA-5A
12-24V dc/115V ac
ES-VA-5A
S11
12-24V dc/230V ac
S21
S22
MSC Monitor
Reset Switch
S12
Contacts
or Jumper for No
Monitoring
S34
S33
Jumper
S32
S35
6A max.
L1
K1
K2
A
A
13
6A max.
K1
K2
B
B
23
Machine
Control
6A max.
Circuits
K1
K2
C
C
33
6A max.
K1
K2
D
D
43
6A max.
K1
E
Non-safety
Auxiliary Monitor
51
Contact
K2
E
Y31
Y32
Y35
Outputs
Power Supply
Energized
Fault
12-24V dc
+V
MSC1 MSC3
S31
S32
MSC2
MSC4
Machine
Master Stop
Control Elements
L2
14
MSC1
*
24
MSC2
*
34
MSC3
*
44
MSC4
*
*
52
Arc Suppressors
(see
below)
WARNING