Adjustment Of The Setpoint; Sealing; Function Test - Danfoss PCVA Instructions Manual

Pressure relief controller, safety pressure relief controller
Table of Contents

Advertisement

Available languages

Available languages

Instructions
7
Start-up
VI.JA.D2.5B
PCVA, PCVSAA

Adjustment of the Setpoint

7.6
The setpoint of the pressure must be adjusted at
the pilot controller AVA 1. The setpoint range is
indicated on the rating plate of the actuator.
1
Procedure
1. Prior to the differential pressure adjustment,
start the system as described in section 7.4.
The differential pressure can also be adjusted
while the bypass 2 is opened.
2. Adjust the flow rate at a valve in flowdirection
after the controller PCVA.
Value approx. 50 % of the max. flow rate 3.
p2
2
Regler PCVA
3
0
50%
3. Adjustment of the pressure by turning the
setpoint adjuster 4.
Turning to the right, increases the setpoint.
Turning to the left, reduces the setpoint.
7.7
The setpoint adjusters may be sealed.
P1
7.8
Check the pressure of the running system with
different load situations.
If the pressure is exceeded in either direction,
adjust the pressure as described in section 7.6.
V
max
SW 22
4

Sealing

Function Test

© Danfoss | 2016.06 | 11