3.3.3
Wiring for 3-wire PNP
Power supply:
18 to 50 Vdc +10%, 1.5 W
Signal output:
Maximum 0.4 A
Load in example from PLC, relay, bulb, etc.
Fuse on power supply: maximum 4 A, slow or fast, HBC, 250 V
Figure 3-5: 3-Wire PNP: Power Supply and Signal Output Connections
PE
Power supply
Quick Start Guide
1
2
3
Load
+
-
L N
Quick Start Guide
21