4. Do not run the AC low voltage wiring in the same conduit with the high voltage power wiring.

Controls using DC Analog Input/Outputs

Before installing any connecting wiring between the unit and components utilizing a DC analog
input/output signal, refer to the appropriate illustration in
electrical access locations provided on the unit and
Table 29
1. Use standard copper conductor thermostat wire unless otherwise specified.
2. Ensure that the wiring between the controls and the unit's termination point does not exceed
Note: Resistance in excess of 2.5 ohms per conductor can cause deviations in the accuracy of the
Table 29. DC Conductors
Distance from unit to
control
000-150 feet
151-240 feet
241-385 feet
386-610 feet
611-970 feet
3. Do not run the electrical wires transporting DC signals in or around conduit housing high
Units equipped with a Trane Communication Interface (TCI), BACnet Communication Interface
(BCI), or LonTalk communication Interface (LCI) option which utilizes a serial communication link;

Constant Volume System Controls

Remote Panel w/o NSB - (BAYSENS110*)
This electronic sensor features four system switch settings (Heat, Cool, Auto, and Off) and two fan
settings (On and Auto) with four system status LED's. It is a manual or automatic changeover
control with dual setpoint capability. It can be used with a remote zone sensor BAYSENS077*. Refer
to
Zone Temperature Control Zone Panel (5U68) - (BAYSENS108*)
This electronic sensor features four system switch settings (Heat, Cool, Auto, and Off) and two fan
settings (On and Auto). It is a manual or automatic changeover control with dual setpoint capability.

Variable Air Volume and Constant Volume System Controls

Remote Panel w/o NSB (5U59) - (BAYSENS021*)
The remote panel w/o Night setback has a system switch as well as a S/A temperature setpoint
indicator, a local sensor, and four LED's. These features allow the operator to control system
operation, and monitor unit operating status from a remote location. Use the installation
instructions that shipped with the panel to install it, and the unit's field wiring diagram to connect
it to the unit.
RT-SVX36G-EN
for conductor sizing guidelines and;
two and a half (2.5) ohms/conductor for the length of the run.
controls.
Recommended wire size
22 gauge
20 gauge
18 gauge
16 gauge
14 gauge
voltage wires.
Must be 18 AWG shielded twisted pair cable (Belden 8760 or equivalent).
Must not exceed 5,000 feet maximum for each link.
Must not pass between buildings.
Table 30
for the Temperature vs. Resistance coefficient.
Figure 9, p. 34
-
Figure 10, p. 36