Trane IntelliPak SAHL Series Installation, Operation And Maintenance Manual page 158

Commercial single-zone rooftop air conditioners with cv, vav, or szvav controls
Table of Contents

Advertisement

Unit Start Up
4. Check the carbon dioxide levels after each adjustment.
5. Press the STOP key at the Human Interface Module in the unit control panel to stop the system
Table 52. Recommended manifold pressures and CO
Note:
1. Manifold pressures are given in inches w.c.
2. High fire manifold pressure is adjustable on all heaters.
3. Low fire manifold pressure is non-adjustable on 235 MBH and 350 MBH heaters.
Figure 83. Flue gas carbon dioxide and oxygen measurements
158
operation.
Furnace Stage
MBH
High-Fire
235
Low-Fire
117
High-Fire
350
Low-Fire
175
High-Fire
500
Low-Fire
250
High-Fire
850
Low-Fire
500
High-Fire
1000
Low-Fire
500
levels during furnace operation (see notes)
2
Firing Rate
%CO
100%
8.5 - 9.5
50%
6.0 - 7.0
100%
8.5- 9.5
50%
6.0 - 7.0
100%
8.5 - 9.5
50%
6.0 - 7.0
100%
8.5 - 9.5
50%
6.0 - 7.0
100%
8.5 - 9.5
50%
6.0 - 7.0
Manifold
Pressure
2
3.0 - 3.5
0.9
3.0 - 3.5
0.9
3.0 - 3.5
1.25
3.0 - 3.5
1.25
3.0 - 3.5
1.25
RT-SVX36G-EN