General Information
Figure 4. Unit Component Layout and "Ship with" Locations

Space Temperature Averaging

Space temperature averaging for Constant Volume applications is accomplished by wiring a
number of remote sensors in a series/parallel circuit.
The fewest number of sensors required to accomplish space temperature averaging is four. The
Space Temperature Averaging with Multiple Sensors figure illustrates a single sensor circuit
(Single Zone), four sensors wired in a series/parallel circuit (Four Zone), nine sensors wired in a
series/parallel circuit (Nine Zone). Any number squared, is the number of remote sensors required.
Wiring termination will depend on the type of remote panel or control configuration for the system.
Refer to the wiring diagrams that shipped with the unit.