Installation Instructions Kemlan Three Sided Natural Draft
DIRECT IGNITION
PROBLEM
PILOT WILL NOT LIGHT
PILOT LIGHTS BUT
VALVE DOES NOT OPEN TO LIGHT MAIN
BURNER
FLAME FAIL LOCKOUT
UNIT HAS DETECTED LOSS OF FLAME
AND LOCKED OUT
25/02/2021
Electronic Ignition Gas Fireplaces
POSSIBLE CAUSE
1) NO GAS
2) NO SPARK AT PILOT
1) FLAME SENSOR NOT
SENDING SIGNAL TO OPEN
VALVE
2) MODULE NOT SENDING
SIGNAL TO OPEN VALVE
3) FAULTY VALVE
1) POWER FAILURE
2) GAS SUPPLY
3) DIRTY ELECTRODE
4) PILOT BLOCKED
5) PRESSURE SWITCHES
Ver. 1
CORRECTIVE ACTION
- CHECK FOR GAS SUPPLY AND
TURN ON ALL CONNECTIONS
- CHECK GAS PRESSURE
- CHECK PILOT AND CLEAN INJECTOR
- CHECK ELECTRIC SUPPLY AND
TURN ON ALL SWITCHES
- CHECK ALL CONNECTIONS
- CHECK SPARK ELECTRODE CONNECTIONS
AND REPLACE ELECTRODE IF DAMAGED.
- CHECK SOLENOID CONNECTIONS AT VALVE
- CHECK ELECTRODE IS IN PILOT
FLAME
- CHECK ELECTRODE CONNETCTIONS
- CLEAN ELECTRODE
- CHECK ELECTRODE FOR DAMAGE
- REPLACE ELECRODE
- REPLACE MODULE
- REPLACE VALVE
- TURN ON/OFF SWITCH OFF AND
ON AGAIN TO RESET ONCE POWER
ESTABLISHED
- CHECK GAS PRESSURE AND ADJUST
- RESET AT ON/OFF SWITCH
- CLEAN ELECTODE OR REPLACE
- CLEAN PILOT INJECTOR
NOTE: TECHRITE IGNITION PACK FLASH CODES
(RED LED) TO IDENTIFY PROBLEM.