Table 3-16: Assembling The Contactor Combination For Reversing (Frame Size S00) - Siemens sirius System Manual

Hide thumbs Also See for sirius:
Table of Contents

Advertisement

Kits
Electrical interlock
SIRIUS System Manual
GWA 4NEB 430 0999-02b
The following table shows you the components of the kit for the contactor
combination for reversing in frame size S00 and explains how to put it
together:
Drawing: frame size S00
5
3
2
1
4
6
6

Table 3-16: Assembling the contactor combination for reversing (frame size S00)

Note:
Contactors with an NC contact in the basic unit (3RT101.) are required for
the electrical interlock.
3RT1/3RH1 contactors
Step
Procedure
1/2/3 Mount the mechanical inter-
lock between the two contac-
tors.
4/5
Press the two connecting clips
from above and below onto the
two contactors.
6
Attach the wiring modules to
connect the main conducting
paths and to electrically inter-
lock the two contactors
(3RT10.1). Make sure that the
wiring modules are flush with
the contactor at the side.
3-35