Table 8-21: Motor Feeder: Fused Configuration - Siemens sirius System Manual

Hide thumbs Also See for sirius:
Table of Contents

Advertisement

Fused configuration
SIRIUS System Manual
GWA 4NEB 430 0999-02b
The following table specifies the components of the fused configuration
(coordination type 1) for 3RW30/31; short-circuit current of 50 kA/400 V:
Order number
Order
of the soft
number
starter
of the fuse
MLFB
MLFB
3RW3014
3NA3810
3RW3016
3NA3810
3RW3024/
3NA3822
3RW3124
3RW3025/
3NA3822
3RW3125
3RW3026/
3NA3824
3RW3126
3RW3034
3NA3830
3RW3035
3NA3830
3RW3036
3NA3830
3RW3044
3NA3144
3RW3045
3NA3144
3RW3046
3NA3144

Table 8-21: Motor feeder: fused configuration

1) The selection and setting of the overload relay is based on the rated cur-
rent for the motor
2) Short-circuit current of 50 kA to max. 400 V
3) Short-circuit current of 50 kA to max. 500 V
4) 50 mm clearance is required above and below between the 3RW and
grounded parts
3RW3 semiconductor motor control unit
Order number
Fuse rated
of the therm.
current/
overload
frame size
1)
relay
A / size
MLFB
2)4)
25 / 00
3RU1116
2)4)
25 / 00
3RU1116
3)
63 / 00
3RU1126
3)
63 / 00
3RU1126
3)
80 / 00
3RU1126
3)
100 / 00
3RU1136
3)
100 / 00
3RU1136
3)
100 / 00
3RU1136
3)
250 / 1
3RU1146
3)
250 / 1
3RU1146
3)
250 / 1
3RU1146
Order
Order
number
number
of the elec-
of the
tron. over-
contactor
1)
load relay
MLFB
MLFB
2)4)
3RB1016
3RT1015
2)4)
3RB1016
3RT1016
3)
3RB1026
3RT1024
3)
3RB1026
3RT1025
3)
3RB1026
3RT1026
3RT1034
3RT1035
3RT1036
3RT1044
3RT1045
3RT1046
8-49