Power cable specifications (continued)
Cross-sectional area
Terminals
External diameter range
NOTE:
The main disconnect and branch protection should be provided by the installer.
Configuration 2: 200–240 V line-to-line one-phase configuration
Printer specifications
Number of power lines
Input voltage (line to line)
Input frequency
Power consumption (typical)
Maximum load current (per phase)
Branch circuit breaker specifications
Power cable specifications
Configuration
Cross-sectional area
Terminals
External diameter range
Power cables
No power cable is provided with the processing station. The cables that you use must meet the minimum
specifications for the chosen configuration explained for each configuration.
32
Chapter 3 Site preparation requirements for the processing station
4 mm² or 12 AWG
Ferrule terminals, except the PE terminal, which uses the M6 ring type
8.5–14 mm
2 lines + PE
200–240 V~ (±10%)
50/60 Hz
2.6 kW
19 A
2 poles, 25 A, type J
2 lines + PE
4 mm² or 12 AWG
Ferrule terminals, except the PE terminal, which uses the M6 ring type
8.5–14 mm